Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop P
Sequence Number 35
Notes
Date Text
2008-12-01 10:09:27REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P2.05 REVISION NUMBER 12, KEY NOTES 12 & 13 NOT
 FOUND ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1
  
 2. SHT P2.05 CHANGES TO THE CONDENSATE ARE NOT CLOUDED
 OR INDICATED WITH A REVISION NUMBER. PLEASE CLOUD AND
 NUMBER ALL REVISIONS TO THE PREVIOUSLY REVIEWED AND
 STAMPED SHEET. SECTION 106.1.3. (ALSO SEE KEY NOTES 12,
 13 & 14 ADDED WITHOUT CLOUD/NUMBER).
  
 3. SHT P2.05 REVISION NUMBER 13 INDICATED ON THE
 REVISION INDEX IS NOT FOUND ON THE FLOOR PLAN AND
 REVISION NUMBER 6 PREVIOUSLY INDICATED IN THE REVISION
 INDEX ON SHEET PREVIOUSLY REVIEWED AND STAMPED HAS BEEN
 DELETED. THE REVISION INDEX HISTORY SHALL BE MAINTAINED
 FROM REVISION TO REVISION. PLEASE CORRELATE. SECTION
 106.1.1.
  
 4. SHT P2.06 REVISIONS 7 & 9 INDICATED ON THE REVISION
 INDEX WERE NOT FOUND ON THE FLOOR PLAN. PLEASE
 CORRELATE. ALSO CLOUD AND NUMBER ALL KEY NOTE CHANGES
 OR REVISIONS ON THE FLOOR PLAN. SECTION 106.1.3.
  
 5. SHT P2.17 REVISION 14 INDICATED ON THE REVISION
 INDEX WAS NOT FOUND ON THE FLOOR PLAN. PLEASE
 CORRELATE. SECTION 106.1.3.
  
 6. SHT P2.17 NEW KEY NOTES 18, 19 & 20 WERE NOT CLOUDED
 OR NUMBERED AND KEY NOTE 18 WAS NOT FOUND ON THE FLOOR
 PLAN. PLEASE CORRELATE AND CLOUD ALL CHANGES SECTION
 106.1.3.
  
 7. SHT P2.17 KEY NOTE NUMBER 16 TO THE RIGHT OF COL.
 LINE "K" DESIGNATION & LEFT OF COL. LINE 11-1 SHOWS NO
 PIPING. PLEASE CLARIFY. SECTION 106.1.1.
  
 8. SHT P2.18 REVISION NUMBER 6 INDICATED ON THE ISSUED
 SET OF PLANS HAS BEEN BEEN DELETED. NO NEW REVISION
 NUMBER HAS BEEN ADDED. THE COMPLETE HISTORY OF
 REVISIONS SHALL BE MAINTAINED FROM REVISION TO
 REVISION. SECTION 106.1.3.
  
 9. SHT P2.21 REVISION NUMBER 6 INDICATED ON THE ISSUED
 SET OF PLANS HAS BEEN BEEN DELETED. NO NEW REVISION
 NUMBER HAS BEEN ADDED. THE COMPLETE HISTORY OF
 REVISIONS SHALL BE MAINTAINED FROM REVISION TO
 REVISION. SECTION 106.1.3.
  
 10. SHT P2.22 SUBMIT A U/L RATING & DETAIL OF FIRE
 RATING OF THE WALL & SUBMIT A DETAIL SHOWING HOW THE
 STRUCTURAL INTEGRITY OF THE COLUMN IS MAINTAINED WHERE
 THE LAV ARE IS ROUTED THRU THE COLUMN. SECTION 106.1.2.
  
 11. SHT P2.25 SUBMIT A U/L RATING & DETAIL OF FIRE
 RATING OF THE WALL & SUBMIT A DETAIL SHOWING HOW THE
 STRUCTURAL INTEGRITY OF THE COLUMN IS MAINTAINED WHERE
 THE LAV ARE IS ROUTED THRU THE COLUMN. SECTION 106.1.2.
  
 12. SHT P2.28 SUBMIT A U/L RATING & DETAIL OF FIRE
 RATING OF THE WALL & SUBMIT A DETAIL SHOWING HOW THE
 STRUCTURAL INTEGRITY OF THE COLUMN IS MAINTAINED WHERE
 THE LAV ARE IS ROUTED THRU THE COLUMN. SECTION 106.1.2.
  
 13. SHT P2.28 SHOW REVISION 11 IN TRIANGLE FOR REVISION
 NUMBER 11 ON THE FLOOR PLAN. SECTION 106.1.3. (TRIANGLE
 BLANK).
  
 14. SHT P2.31 REVISION INDEX REVISION NUMBERS 1 & 2
 WERE DELETED, REVISION NUMBER 2 WAS CHANGED TO REVISION
 NUMBER 4, ADDENDUM NUMBER 5 WAS ADDED TO REVISION
 NUMBER 5, KEY NOTES NUMBER 3 CHANGED WITH REVISION
 NUMBER 6 WAS NOT FOUND ON THE FLOOR PLAN, REVISON
 NUMBER 7 WAS FOUND ON THE FLOOR PLAN BUT NOT IN THE
 REVISION INDEX, AND KEY NOTES 4 & 5 ADDED BUT NO CLOUD
 OR REVISION NUMBER INDICATING THE REVISION. PLEASE
 CORRELATE, MAINTAIN THE REVISION HISTORY, SHOW ALL
 REVISIONS WITH CLOUDS & REVISION NUMBERS ETC. SECTIONS
 106.1.1, 106.1.2 & 106.1.3.
  
 15. SHT P2.33 REVISION INDEX ON THE SHEET STAMPED AND
 REVIEWED BY THE CITY WPB ON SEPT. 08, 2006 SHOWS
 REVISIONS 2, 3 & 4. THE NEW REVISIED SHEET SUBMITTED
 HAS REVISIONS 3, 4, 5, 6 & 11. REVISION 2 HAS BEEN
 DELETED, REVISION 3 HAS A DIFFERENT DATE, REVISION 4
 HAS A DIFFERENT DATE, & REVISION 5 WAS NOT FOUND ON THE
 FLOOR PLAN. THE REVISION HISTORY SHALL BE MAINTAINED
 THRU THE LIFE THE THE PLANS. CORRELATE NEW REVISION
 NUMBERS WITH THE FLOOR PLAN. SECTION 106.1.3.
  
 16. SHT P3.01 RISERS FOR 2, 3, 10, 11, 12 & 13 AND 36,
 37, 42 & 44 SHOW A 3" DRAINAGE LINE FROM THE COLLECTOR
 TANK OVERFLOWS. THE OVERFLOW SHALL DRAIN TO THE STORM
 SYSTEM. MUNICIPAL CODE ARTICLE III SECTION
 90-125(B)(5).
  
 17. SHT P3.10 SHOWS REVISION NUMBER 4 ON THE FLOOR PLAN
 BUT IS NOT INDICATED ON THE REVISION INDEX. THE
 REVISIONS IN KEY NOTES ARE NOT INDICATED WITH CLOUDS OR
 REVISION NUMBER. SECTION 106.1.3.
  
 18. SHT P3.11 KEY NOTES NUMBER 4 DOES NOT REFLECT
 CHANGES ON THE WATER UNIT DETAILS. PLEASE
 CLARIFY/CORRELATE. SECTIONS 106.1.1 & 106.1.2.
  
 19. SHT P3.14 REVISION NUMBER 6 HAS BEEN DELETED FROM
 THE REVISION HISTORY. PLEASE MAINTAIN THE REVISION
 HISTORY THRU THE LIFE TO THE PLANS. SECTION 106.1.3.
  
 20. SHT P4.01 REVISION NUMBER 2 HAS BEEN DELETED FROM
 THE REVISION HISTORY. PLEASE MAINTAIN THE REVISION
 HISTORY THRU THE LIFE TO THE PLANS. THE FUEL PIPING
 DETAIL FOR FOR THE MECHANICAL PLAN REVIEWER. PLEASE
 DELETE FROM PLUMBING AND SUBMIT REVISION UNDER THE
 MECHANICAL PLANS. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  