| 2007-09-05 07:39:14 | BUILDING PLAN REVIEW |
| | PERMIT: 05091265 |
| | ADD: 480 HIBISCUS ST |
| | CONT: THE TOWER GROUP |
| | TEL: (561)635-6935 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/* WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | REVISION # 13REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A0.3 |
| | 1A) PLEASE INDICATE ON THE PLAN WHERE THE NEWSROOM CAF? |
| | WILL BE THIS SHEET ONLY INDICATES A NEWSROOM AND ANY |
| | OTHER SHEETS THAT MAY BE INVOLVED. |
| | |
| | 1B) FLOOR ELEVATIONS THERE ARE VARIOUS REVISIONS IN |
| | REGARDS TO FLOOR ELEVATION THAT DO NOT TAKE INTO |
| | ACCOUNT VERTICAL ACCESSIBILITY, IT WILL BE DISCUSSED IN |
| | DEPTH FURTHER IN THE REVIEW. |
| | |
| | 1C) COMMERCIAL AREA CALCULATIONS NEED TO BE |
| | RECALCULATED FOR # 15. SHEET A1.5 MEZZANINE AREA HAS |
| | BEEN REDESIGNED FOR UNIT # 15. |
| | |
| | 2) SHEET A0.15 MISSING SHEET |
| | |
| | 3) SHEET A1.10 |
| | |
| | 3A) IDENTIFY WHAT AREA IS CONSIDERED THE NEWS ROOM |
| | CAF?? |
| | |
| | 4) SHEET A1.1 |
| | |
| | A) COMMERCIAL SPACE # 14 AT THE REAR OF THE SPACE THERE |
| | IS A NEW 6? DROP OUT THE BACK EGRESS DOORS.1003.5.2 |
| | WHERE CHANGE IN ELEVATION OF 12 INCHES (305 MM) OR LESS |
| | OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND EXIT |
| | DISCHARGE, RAMPS COMPLYING WITH SECTION 1010 SHALL BE |
| | PROVIDED. |
| | 11-4.8.2 SLOPE & RISE. THE LEAST POSSIBLE SLOPE |
| | SHALL BE USED FOR ANY RAMP. THE MAXIMUM SLOPE FOR A |
| | RAMP IN NEW CONSTRUCTION SHALL BE 1 TO 12. THE MAXIMUM |
| | RISE FOR RUN SHALL BE 30" (SEE FIGURE 16). 11-4.8.4.(2) |
| | LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT BE LESS THAN |
| | 60" CLEAR, & THE BOTTOM OF EACH RAMP SHALL HAVE NOT |
| | LESS THAN 72" OF STRAIGHT & LEVEL CLEARANCE. |
| | |
| | |
| | 5) SHEET A1.2 |
| | |
| | 5A) THE ELEVATOR LOBBY HAS A NEW FINISH FLOOR HEIGHT OF |
| | 18.75? NGVD IT ISN?T INDICATED AS A CHANGE WITH A DELTA |
| | OR CLOUD, IS THIS A MISTAKE? REVISION# 10 STILL |
| | INDICATED 18.5?. |
| | |
| | 5B) THE ELEVATOR LOBBY REVISION# 13 AT DOOR # 30IS |
| | NOT CORRECTED IN DETAIL# 1 OF A7.2 GROUND FLOOR LEVEL. |
| | |
| | |
| | 5C) DOOR # 23 TO AN A/C CLOSET IS ELIMINATED, M2.02 |
| | INDICATES THAT AIR HANDLER UNIT # 15 IS LOCATED THERE. |
| | |
| | 5D) THE SWITCH GEAR ROOM, FPL TRANSFORMER VAULT AND |
| | COMMERCIAL TENANT SPACE NOW ALL SHOW A 7? STEP, SHOW |
| | COMPLIANCE WITH VERTICAL ACCESSIBILITY. 11-4.1.3. |
| | |
| | 5E) THE TRASH ROOM # 017 AND CORRIDOR ALSO HAVE |
| | ACCESSIBILITY ISSUES. THIS AREA IS 6? HIGHER THAN THE |
| | SURROUNDING TENANT SLABS CREATING ACCESSIBILITY |
| | PROBLEMS, THE PLAN INDICATES A 3? RAMP PLUS A 6? STEP |
| | AT THE FRONT OF THE BUILDING. PLEASE CORRECT THIS WHOLE |
| | AREA, AGAIN VERTICAL ACCESSIBILITY. |
| | |
| | 5F)COMMERCIAL TENANT SPACE # 15 ALSO HAS A 6? STEP TO |
| | GAIN ACCESS INTO THIS UNIT, AGAIN PLEASE INDICATE |
| | COMPLIANCE WITH VERTICAL ACCESSIBILITY.11-4.1.2 |
| | NOTHING IN THIS CODE SHALL BE CONSTRUED TO RELIEVE THE |
| | OWNER OF ANY BUILDING, STRUCTURE OR FACILITY FROM THE |
| | DUTY TO PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS |
| | ABOVE AND BELOW THE OCCUPIABLE GRADE LEVEL, REGARDLESS |
| | OF WHETHER THE CODE REQUIRES AN ELEVATOR TO BE |
| | INSTALLED IN SUCH BUILDING, STRUCTURE OR FACILITY, |
| | |
| | 6) THIS IS A COMMON COMMENT FOR ALL ELECTRICAL ROOMS ON |
| | ALL FLOORS WHERE THE BLOCK WALL INDICATES A REVISION# |
| | 13 TO A METAL STUD WALL AND DRYWALL NO WALL |
| | IDENTIFICATION TAG IS PROVIDED INDICATING RATING. |
| | |
| | 7) COMMON TO ALL SHEETS INDICATING A METAL AWNING, TO |
| | BE UNDER SEPARATE PERMIT WITH ASSOCIATED FEES AND |
| | REVIEWS. TO GET THE PLANS ISSUED SHEET A4.0 8/24/06 THE |
| | ARCHITECT SIGNED THE PLANS THAT THE BAHAMA STYLE METAL |
| | SHUTTERS WOULD BE UNDER A SEPARATE PERMIT NOT PART OF |
| | THE MASTER BUILDING. PLEASE PLACE NOT ON PLANS WHERE |
| | THIS TYPE AWNING IS LOCATED. |
| | |
| | 8) SHEET A2.1 : |
| | |
| | 8A) THE DOOR REMOVED AGAIN INDICATES THAT IT WENT TO |
| | AHU# 15 SEE SHEET M2.02 |
| | |
| | 8B) DOOR # 30 MOVED BEHIND THIS DOOR 4?-3? THERE IS A |
| | HEAVY LINE WHAT IS THIS LINE INDICATE? |
| | |
| | 8C) FLOOR ELEVATION 18.75? ISN?T SHOWN AS A CHANGE SEE |
| | REVISION # 10 STILL AT 18.50?. |
| | |
| | 9) SHEET A4.1; |
| | |
| | 9A)AGAIN THIS DETAIL INDICATES EXTERIOR STEPS WITHOUT |
| | VERTICAL ACCESSIBILITY.NOTHING IN THIS CODE SHALL |
| | BE CONSTRUED TO RELIEVE THE OWNER OF ANY BUILDING, |
| | STRUCTURE OR FACILITY FROM THE DUTY TO PROVIDE VERTICAL |
| | ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE |
| | OCCUPIABLE GRADE LEVEL, REGARDLESS OF WHETHER THE CODE |
| | REQUIRES AN ELEVATOR TO BE INSTALLED IN SUCH BUILDING, |
| | STRUCTURE OR FACILITY, |
| | SWITCH GEAR |
| | TRANSFORMER VAULT |
| | EXTERIOR CORRIDOR |
| | COMMERCIAL TENANT# 15 |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | |
| | |
| | |
| | |
| | TEL: (561)805-6715 |