| 2006-08-04 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 BUILDING |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | MUNICIPAL CODE WPB |
| | |
| | FROM PREVIOUS REVIEW: THE COMMENT |
| | NUMBERS SHALL REMAIN THE SAME AS FIRST |
| | REVIEW: - NO COMMENT RESPONSES SUBMITTED |
| | FOR THE FIRST REVIEW. |
| | |
| | 2. OK |
| | |
| | 3. SHT A1.0 THE DRINKING FOUNTAIN SHALL |
| | BE ACCESSIBLE. SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH SECTIONS 11-4.15 AND ALL |
| | SUBSECTIONS AS WELL AS SECTION |
| | 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO |
| | HAVE DIFFICULTY BENDING OR STOOPING. |
| | ***COMMENT CONCERNING 11-4.1.3(10)(A) |
| | NOT ADDRESSED. CLEAR FLOOR SPACE SHALL |
| | ALLOW FORWARD APPROACH. 11-4.15.5(1). |
| | ****RESPONSE NOTED, BUT PARALLEL |
| | APPROACH IS STILL SHOWN ON THE FLOOR |
| | PLANS ON DIFFERENT SHEETS. |
| | |
| | 4. SHT A1.2 MEN'S & WOMEN'S TOILET ROOMS |
| | SHALL BE ACCESSIBLE. SUBMIT DETAILS |
| | SHOWING COMPLIANCE WITH SECTIONS |
| | 11-4.16, 11-4.19, 11-4.21, 11-4.22 AND |
| | ALL SUBSECTIONS. ALSO FOR THE BREAK ROOM |
| | SINK, 11-4.24 AND ALL SUBSECTIONS. |
| | ***COMMENT NOT ADDRESSED. SEE COMMENT |
| | NUMBER 2 FOR INFORMATION STILL REQUIRED |
| | FOR W/C'S AND LAVS. |
| | FOR SHOWERS |
| | A. 11-4.21.3 SEAT (FOLD-UP TYPE) |
| | B. 11-4.21.5 CONTROLS (FIG. 11-37) |
| | C. 11-4.21.6 SHOWER UNIT |
| | D. 11-4.21.7 CURBS |
| | SUBMIT ELEVATIONS FOR THE SHOWER SHOWING |
| | COMPLIANCE FOR THE PRIOR REQUIREMENTS. |
| | ****RESPONSE NOTED, BUT THE SHOWER UNIT |
| | REQUIRED BY 11-4.21.6 IS NOT SHOWN, AND |
| | CURBS ARE INDICATED, WHERE AS SECTION |
| | 11-4.21.7 INDICATES CURBS ARE NOT TO BE |
| | INSTALLED. - NO BREAK ROOM SINK DETAIL |
| | OR ELEVATION IS FOUND. - |
| | DOORS SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACE REQUIRED FOR ANY FIXTURE. |
| | THE SHOWER SHALL SHOW A CLEAR FLOOR |
| | SPACE PER 11-4.21.2. SECTION |
| | 11-4.22.2(1). |
| | |
| | 5. SHT A1.18 MEN'S AND WOMEN'S LOCKER |
| | ROOMS TO BE ACCESSABLE. SUBMIT DETAILS |
| | SHOWING COMPLIANCE WITH SECTION 11-4.16, |
| | 11-4.18, 11-4.19, 11-4.21, & 11-4.22 AND |
| | ALL SUBSECTIONS. |
| | ***COMMENT NOT ADDRESSED. SEE COMMENT |
| | NUMBER TWO FOR INFORMATION STILL |
| | REQUIRED. ALSO THE INFORMATION FOR THE |
| | URINAL STILL REQUIRED: |
| | A. 11-4.18.2 HEIGHT |
| | B. 11-4.18.4 FLUSH CONTROLS |
| | ****RESPONSE NOTED, BUT NO COMPLIANCE |
| | FOR THE FLUSH CONTROLS IS INDICATED. |
| | |
| | 6.OK |
| | 11. OK |
| | |
| | 12. SHTS A9.2 THRU A9.24 ALL UNITS. |
| | CLEAR FLOOR SPACE FOR THE WATER CLOSETS |
| | SHALL BE APPLIED OR SUPERIMPOSED OVER A |
| | PLAN PER PAGE 7.43 PARAGRAPH ONE. |
| | ***COMMENT NOT ADDRESSED. |
| | ****THIS ISSUE HAS NOT BEEN ADDRESSED. |
| | CLEAR FLOOR SPACE FOR THE LAV & TUB ARE |
| | SHOWN BUT NOT THE W/C. |
| | |
| | 13. SHTS A9.2 THRU A9.24 PER PAGE 7.7 |
| | MINIMUM CLEARANCES BETWEEN COUNTERS AND |
| | ALL OPPOSING ELEMENTS IS 40". PLEASE |
| | INDICATE ON THE PLANS THE MINIMUM |
| | CLEARANCE FOR ALL KITCHENS. |
| | ***COMMENT NOT ADDRESSED. |
| | ****RESPONSE NOTED, BUT THE CLEARANCE |
| | SHOWN IS NOT THE MINIMUM CLEARANCE. (SEE |
| | ATTACHED SHEET FROM FHA DESIGN MANUAL) |
| | |
| | 14. OK |
| | 15. OK |
| | 19. OK |
| | 23. OK |
| | 26. OK |
| | 30. SOK |
| | 31. OK |
| | 32. OK - TO BE A SUBMITTAL |
| | |
| | 33. GREASE INTECEPTOR SHALL BE SIZED BY |
| | THE ENVIRONMENTAL COMPLIANCE MANAGER. |
| | PLEASE CONTACT LYNN MASSON (561) |
| | 822-2271 OR BY FAX (561) 822-2279 OR BY |
| | E-MAIL [email protected]. |
| | ***NOT ADDRESSED. |
| | ****WAITING FOR APPROVAL FROM L. MASSON |
| | |
| | |
| | 35. PLANS SHOW A VENT IN THE WALL AND AN |
| | OPEN 2" DRAIN IN THE PLENUM. MORE |
| | INFORMATION IS REQUIRED. WILL THE ROOM |
| | AS A PLENUM PULL THE AIR FROM THE 2" |
| | OPEN DRAIN AND INTRODUCE THE HUMID, WARM |
| | AIR INTO THE AIR CONDITIONED AIR OF THE |
| | UNIT? IS THIS PRACTICE ACCEPTABLE TO THE |
| | MECHNAICAL ENGINEER? - ALSO THE VENT |
| | TERMINATION SHALL EITHER VENT THRU THE |
| | ROOF OR TERMINATE ABOVE THE CEILING 6" |
| | ABOVE THE INSULATION. |
| | ***NOT ADDRESSED. |
| | ****RESPONSE NOTED, BUT VENT IS STILL |
| | SHOWN IN THE WALL, AND THE DRAIN IS |
| | STILL SHOWN ALSO. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | ***NO COMMENT RESPONSE WAS SUBMITTED AND |
| | BECAUSE OF THAT AND PLAN DEVELOPMENT |
| | BETWEEN REVIEWS, THE RESUBMITTAL WAS |
| | TREATED AS A COMPLETE REVIEW OF THE |
| | PLAN. THIS CONTRIBUTES TO A LONGER TURN |
| | AROUND TIME FOR PLAN REVIEW. |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. OK |
| | 2B. OK |
| | 3B. OK |
| | 4B.OK |
| | 5B. OK |
| | |
| | 6B. SHT P2.06 SHOWS RWL/35 BETWEEN COLS. |
| | 28.1 AND 29. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | ****RESPONSE NOTED, BUT RWL 35 STILL |
| | SHOWN. |
| | |
| | 7B. OK |
| | 8B. OK |
| | |
| | 9B. SHT P2.20 3"PD(68SF) & 3"PD(92SF) |
| | ARE NOT SHOWN ON ANY RISER DIAGRAM. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT NOW 68SF IS NOT |
| | SHOWN ON THE PLUMBING PLAN, & 92SF IS |
| | NOT SHOWN ON THE RISER DIAGRAM. PLEASE |
| | CORRELATE. |
| | |
| | 10B. OK |
| | 11B. OK |
| | |
| | 12B. SHTS P2.23 & P2.24 MATCH LINE DOES |
| | NOT MATCH FLOOR PLAN AT COL. LINE "22". |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THERE IS MISSING |
| | INFORMATION FOR THE FLOOR PLAN ON SHT |
| | P2.23. |
| | |
| | 13B. OK |
| | 14B. OK |
| | 15B. OK |
| | 16B. OK |
| | 17B. OK |
| | |
| | 18B. SHT P3.01 RECHECK ADDITION OF DFU'S |
| | AS THEY ACCUMULATE IN THE SANT. SYSTEM. |
| | TABLE 710.1(1). |
| | ****RESPONSE NOTED, BUT ADDITION OF |
| | DFU'S INCORRECT IN SOME AREAS. |
| | |
| | 19B. OK |
| | 20B. OK |
| | 21B. OK |
| | 22B. OK |
| | 23B. OK |
| | |
| | 24B. SHT P3.06 2 W/4 RISERS SHOWN, 2 |
| | W/11 RISERS SHOWN, 2 W/8 RISERS SHOWN & |
| | 2 W/28 RISERS SHOWN. PLEASE CORRELATE |
| | RISER DIAGRAM WITH FLOOR PLAN. |
| | ****RESPONSE NOTED, BUT SHT P3.07 STILL |
| | SHOWS 2 W/28 RISERS. |
| | |
| | 25B. OK |
| | 26B. OK |
| | 27B. OK |
| | |
| | 28B. SHT P3.13 3" PAD (136SF) NOT |
| | INDICATED ON DECK PLAN. PLEASE |
| | CORRELATE. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT 3" PAD (136SF) |
| | STILL NOT FOUND. - NEW COMMENT NEW 2ND |
| | 4" DD (378SF) SHOWN ON RISER NOT FOUND |
| | ON DECK PLAN. |
| | |
| | 29B. SHT P3.14 6" REQUIRED AT SD |
| | (1657SF). TABLE 1106.3. |
| | ****RESPONSE NOTED, BUT PIPES ARE |
| | UNDERSIZED DOWNSTREAM OF 4" DD (763SF) |
| | RISER DP7, DOWNSTREAM OF 3" PD (134SF) |
| | RISER DP8, & DOWNSTREAM OF 3" PD (81SF) |
| | SHOWS 8" THEN REDUCING TO 6" IN THE |
| | DIRECTION OF FLOW. SECTION 704.2. |
| | |
| | 30B. OK |
| | 31B. OK |
| | 32B. OK |
| | 33B. OK |
| | |
| | 34B. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR THE GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ****RESPONSE NOTED, BUT THE GAS LINE TO |
| | THE POOL HEATER APPEARS TO BE RUN IN THE |
| | 5TH FLOOR CEILING. WILL THE POOL HEATER |
| | BE LOCATED IN THE CEILING, OR WILL THERE |
| | BE A DROP TO THE HEATER. PLEASE CLARIFY. |
| | |
| | B. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). (EACH SYSTEM). |
| | ****RESPONSE NOTED, BUT THE TABLE SHOWN |
| | IS FROM FBC-2001 FUEL GAS CODE. PLEASE |
| | DESIGN AND INDICATE TABLE FROM FBC-2004 |
| | FUEL GAS CODE. |
| | C. OK |
| | |
| | D. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. (EACH SYSTEM). |
| | ****NOT ADDRESSED. |
| | |
| | E. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. (EACH SYSTEM). |
| | ****NOT ADDRESSED. |
| | |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. (EACH |
| | SYSTEM). |
| | ****NOT ADDRESSED. ITS UNDERSTOOD THE |
| | KITCHEN GAS EQUIPMENT WILL BE SUBMITTED |
| | AT KITCHEN BUILD-OUT, BUT THE POOL |
| | HEATER SPECIFICATIONS SHEETS WILL BE |
| | REQUIRED. |
| | |
| | G. AT KITCHEN BUILD-0UT |
| | |
| | 35B. THERE IS ONE SET OF "RED LINED" |
| | PLANS. PLEASE RETURN THIS SET AND |
| | COMMENT RESPONSES TO HELP EXPEDITE THE |
| | NEXT PLAN REVIEW. |
| | ****COMMENT NOT ADDRESSED. |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1C. CONDENSATE/PAN DRAIN LINE TO BE |
| | SEPARATE. CONDENSATE LINES CAN BACK UP |
| | BECAUSE OF THE BUILD-UP AND THE EXHAUST |
| | FROM THE PARKING GARAGE CAN ENTER THE |
| | A/C CLOSETS. PAN DRAIN LINES SHOULD |
| | TERMINATE OUTSIDE THE BUILDING, OR BE |
| | PIPED INDIRECTLY TO THE SANITARY SYSTEM. |
| | SECTION 504.7.2. |
| | |
| | 2C. SHT P3.04 RISER 139 WASH MACHINE TO |
| | DISCHARGE DOWNSTREAM OF BATHROOM |
| | FIXTURES. VENT REQUIRED FOR W/C & |
| | SHOWER. SECTIONS 901.2 & 909.1 |
| | |
| | 3C. SHT P3.04 RISER 98 FITTING TO BE |
| | INSTALLED TO GUIDE SEWAGE AND WASTE IN |
| | THE DIRECTION OF FLOW. SECTION 706.3. |
| | |
| | 4C. EMERGENCY DRAINS FOR THE DECK SHALL |
| | DRAIN THE TOTAL AREA OF THE DRAIN. SOME |
| | AREAS HAVE NO EMERGENCY DRAINS, AND ITS |
| | UNDERSTOOD THAT THOSE AREAS WILL DRAIN |
| | TO THE EMERGENCY DRAINS SHOWN. THE |
| | EMERGENCY DRAINS SHALL BE SIZED FOR THE |
| | TOTAL AREA THAT WILL BE DRAINED FOR EACH |
| | AREA. PLEASE INDICATE THE TOTAL AREA |
| | BEING DRAINED FOR EACH EMERGENCY DRAIN |
| | AND SIZE ED'S ACCORDINGLY. SECTION |
| | 1107.3. |
| | |
| | REVIEW BY KEN STEVENS |