Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop P
Sequence Number 3
Notes
Date Text
2006-08-04 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE WPB
  
 FROM PREVIOUS REVIEW: THE COMMENT
 NUMBERS SHALL REMAIN THE SAME AS FIRST
 REVIEW: - NO COMMENT RESPONSES SUBMITTED
 FOR THE FIRST REVIEW.
  
 2. OK
  
 3. SHT A1.0 THE DRINKING FOUNTAIN SHALL
 BE ACCESSIBLE. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTIONS 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 ***COMMENT CONCERNING 11-4.1.3(10)(A)
 NOT ADDRESSED. CLEAR FLOOR SPACE SHALL
 ALLOW FORWARD APPROACH. 11-4.15.5(1).
 ****RESPONSE NOTED, BUT PARALLEL
 APPROACH IS STILL SHOWN ON THE FLOOR
 PLANS ON DIFFERENT SHEETS.
  
 4. SHT A1.2 MEN'S & WOMEN'S TOILET ROOMS
 SHALL BE ACCESSIBLE. SUBMIT DETAILS
 SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19, 11-4.21, 11-4.22 AND
 ALL SUBSECTIONS. ALSO FOR THE BREAK ROOM
 SINK, 11-4.24 AND ALL SUBSECTIONS.
 ***COMMENT NOT ADDRESSED. SEE COMMENT
 NUMBER 2 FOR INFORMATION STILL REQUIRED
 FOR W/C'S AND LAVS.
 FOR SHOWERS
 A. 11-4.21.3 SEAT (FOLD-UP TYPE)
 B. 11-4.21.5 CONTROLS (FIG. 11-37)
 C. 11-4.21.6 SHOWER UNIT
 D. 11-4.21.7 CURBS
 SUBMIT ELEVATIONS FOR THE SHOWER SHOWING
 COMPLIANCE FOR THE PRIOR REQUIREMENTS.
 ****RESPONSE NOTED, BUT THE SHOWER UNIT
 REQUIRED BY 11-4.21.6 IS NOT SHOWN, AND
 CURBS ARE INDICATED, WHERE AS SECTION
 11-4.21.7 INDICATES CURBS ARE NOT TO BE
 INSTALLED. - NO BREAK ROOM SINK DETAIL
 OR ELEVATION IS FOUND. -
 DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 THE SHOWER SHALL SHOW A CLEAR FLOOR
 SPACE PER 11-4.21.2. SECTION
 11-4.22.2(1).
  
 5. SHT A1.18 MEN'S AND WOMEN'S LOCKER
 ROOMS TO BE ACCESSABLE. SUBMIT DETAILS
 SHOWING COMPLIANCE WITH SECTION 11-4.16,
 11-4.18, 11-4.19, 11-4.21, & 11-4.22 AND
 ALL SUBSECTIONS.
 ***COMMENT NOT ADDRESSED. SEE COMMENT
 NUMBER TWO FOR INFORMATION STILL
 REQUIRED. ALSO THE INFORMATION FOR THE
 URINAL STILL REQUIRED:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.4 FLUSH CONTROLS
 ****RESPONSE NOTED, BUT NO COMPLIANCE
 FOR THE FLUSH CONTROLS IS INDICATED.
  
 6.OK
 11. OK
  
 12. SHTS A9.2 THRU A9.24 ALL UNITS.
 CLEAR FLOOR SPACE FOR THE WATER CLOSETS
 SHALL BE APPLIED OR SUPERIMPOSED OVER A
 PLAN PER PAGE 7.43 PARAGRAPH ONE.
 ***COMMENT NOT ADDRESSED.
 ****THIS ISSUE HAS NOT BEEN ADDRESSED.
 CLEAR FLOOR SPACE FOR THE LAV & TUB ARE
 SHOWN BUT NOT THE W/C.
  
 13. SHTS A9.2 THRU A9.24 PER PAGE 7.7
 MINIMUM CLEARANCES BETWEEN COUNTERS AND
 ALL OPPOSING ELEMENTS IS 40". PLEASE
 INDICATE ON THE PLANS THE MINIMUM
 CLEARANCE FOR ALL KITCHENS.
 ***COMMENT NOT ADDRESSED.
 ****RESPONSE NOTED, BUT THE CLEARANCE
 SHOWN IS NOT THE MINIMUM CLEARANCE. (SEE
 ATTACHED SHEET FROM FHA DESIGN MANUAL)
  
 14. OK
 15. OK
 19. OK
 23. OK
 26. OK
 30. SOK
 31. OK
 32. OK - TO BE A SUBMITTAL
  
 33. GREASE INTECEPTOR SHALL BE SIZED BY
 THE ENVIRONMENTAL COMPLIANCE MANAGER.
 PLEASE CONTACT LYNN MASSON (561)
 822-2271 OR BY FAX (561) 822-2279 OR BY
 E-MAIL [email protected].
 ***NOT ADDRESSED.
 ****WAITING FOR APPROVAL FROM L. MASSON
  
  
 35. PLANS SHOW A VENT IN THE WALL AND AN
 OPEN 2" DRAIN IN THE PLENUM. MORE
 INFORMATION IS REQUIRED. WILL THE ROOM
 AS A PLENUM PULL THE AIR FROM THE 2"
 OPEN DRAIN AND INTRODUCE THE HUMID, WARM
 AIR INTO THE AIR CONDITIONED AIR OF THE
 UNIT? IS THIS PRACTICE ACCEPTABLE TO THE
 MECHNAICAL ENGINEER? - ALSO THE VENT
 TERMINATION SHALL EITHER VENT THRU THE
 ROOF OR TERMINATE ABOVE THE CEILING 6"
 ABOVE THE INSULATION.
 ***NOT ADDRESSED.
 ****RESPONSE NOTED, BUT VENT IS STILL
 SHOWN IN THE WALL, AND THE DRAIN IS
 STILL SHOWN ALSO.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ***NO COMMENT RESPONSE WAS SUBMITTED AND
 BECAUSE OF THAT AND PLAN DEVELOPMENT
 BETWEEN REVIEWS, THE RESUBMITTAL WAS
 TREATED AS A COMPLETE REVIEW OF THE
 PLAN. THIS CONTRIBUTES TO A LONGER TURN
 AROUND TIME FOR PLAN REVIEW.
  
 **************NEW COMMENTS**************
  
 1B. OK
 2B. OK
 3B. OK
 4B.OK
 5B. OK
  
 6B. SHT P2.06 SHOWS RWL/35 BETWEEN COLS.
 28.1 AND 29. PLEASE CLARIFY. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT RWL 35 STILL
 SHOWN.
  
 7B. OK
 8B. OK
  
 9B. SHT P2.20 3"PD(68SF) & 3"PD(92SF)
 ARE NOT SHOWN ON ANY RISER DIAGRAM.
 PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT NOW 68SF IS NOT
 SHOWN ON THE PLUMBING PLAN, & 92SF IS
 NOT SHOWN ON THE RISER DIAGRAM. PLEASE
 CORRELATE.
  
 10B. OK
 11B. OK
  
 12B. SHTS P2.23 & P2.24 MATCH LINE DOES
 NOT MATCH FLOOR PLAN AT COL. LINE "22".
 PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THERE IS MISSING
 INFORMATION FOR THE FLOOR PLAN ON SHT
 P2.23.
  
 13B. OK
 14B. OK
 15B. OK
 16B. OK
 17B. OK
  
 18B. SHT P3.01 RECHECK ADDITION OF DFU'S
 AS THEY ACCUMULATE IN THE SANT. SYSTEM.
 TABLE 710.1(1).
 ****RESPONSE NOTED, BUT ADDITION OF
 DFU'S INCORRECT IN SOME AREAS.
  
 19B. OK
 20B. OK
 21B. OK
 22B. OK
 23B. OK
  
 24B. SHT P3.06 2 W/4 RISERS SHOWN, 2
 W/11 RISERS SHOWN, 2 W/8 RISERS SHOWN &
 2 W/28 RISERS SHOWN. PLEASE CORRELATE
 RISER DIAGRAM WITH FLOOR PLAN.
 ****RESPONSE NOTED, BUT SHT P3.07 STILL
 SHOWS 2 W/28 RISERS.
  
 25B. OK
 26B. OK
 27B. OK
  
 28B. SHT P3.13 3" PAD (136SF) NOT
 INDICATED ON DECK PLAN. PLEASE
 CORRELATE. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT 3" PAD (136SF)
 STILL NOT FOUND. - NEW COMMENT NEW 2ND
 4" DD (378SF) SHOWN ON RISER NOT FOUND
 ON DECK PLAN.
  
 29B. SHT P3.14 6" REQUIRED AT SD
 (1657SF). TABLE 1106.3.
 ****RESPONSE NOTED, BUT PIPES ARE
 UNDERSIZED DOWNSTREAM OF 4" DD (763SF)
 RISER DP7, DOWNSTREAM OF 3" PD (134SF)
 RISER DP8, & DOWNSTREAM OF 3" PD (81SF)
 SHOWS 8" THEN REDUCING TO 6" IN THE
 DIRECTION OF FLOW. SECTION 704.2.
  
 30B. OK
 31B. OK
 32B. OK
 33B. OK
  
 34B. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT THE GAS LINE TO
 THE POOL HEATER APPEARS TO BE RUN IN THE
 5TH FLOOR CEILING. WILL THE POOL HEATER
 BE LOCATED IN THE CEILING, OR WILL THERE
 BE A DROP TO THE HEATER. PLEASE CLARIFY.
  
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). (EACH SYSTEM).
 ****RESPONSE NOTED, BUT THE TABLE SHOWN
 IS FROM FBC-2001 FUEL GAS CODE. PLEASE
 DESIGN AND INDICATE TABLE FROM FBC-2004
 FUEL GAS CODE.
 C. OK
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. (EACH SYSTEM).
 ****NOT ADDRESSED.
  
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505. (EACH SYSTEM).
 ****NOT ADDRESSED.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. (EACH
 SYSTEM).
 ****NOT ADDRESSED. ITS UNDERSTOOD THE
 KITCHEN GAS EQUIPMENT WILL BE SUBMITTED
 AT KITCHEN BUILD-OUT, BUT THE POOL
 HEATER SPECIFICATIONS SHEETS WILL BE
 REQUIRED.
  
 G. AT KITCHEN BUILD-0UT
  
 35B. THERE IS ONE SET OF "RED LINED"
 PLANS. PLEASE RETURN THIS SET AND
 COMMENT RESPONSES TO HELP EXPEDITE THE
 NEXT PLAN REVIEW.
 ****COMMENT NOT ADDRESSED.
  
 **************NEW COMMENTS**************
  
 1C. CONDENSATE/PAN DRAIN LINE TO BE
 SEPARATE. CONDENSATE LINES CAN BACK UP
 BECAUSE OF THE BUILD-UP AND THE EXHAUST
 FROM THE PARKING GARAGE CAN ENTER THE
 A/C CLOSETS. PAN DRAIN LINES SHOULD
 TERMINATE OUTSIDE THE BUILDING, OR BE
 PIPED INDIRECTLY TO THE SANITARY SYSTEM.
 SECTION 504.7.2.
  
 2C. SHT P3.04 RISER 139 WASH MACHINE TO
 DISCHARGE DOWNSTREAM OF BATHROOM
 FIXTURES. VENT REQUIRED FOR W/C &
 SHOWER. SECTIONS 901.2 & 909.1
  
 3C. SHT P3.04 RISER 98 FITTING TO BE
 INSTALLED TO GUIDE SEWAGE AND WASTE IN
 THE DIRECTION OF FLOW. SECTION 706.3.
  
 4C. EMERGENCY DRAINS FOR THE DECK SHALL
 DRAIN THE TOTAL AREA OF THE DRAIN. SOME
 AREAS HAVE NO EMERGENCY DRAINS, AND ITS
 UNDERSTOOD THAT THOSE AREAS WILL DRAIN
 TO THE EMERGENCY DRAINS SHOWN. THE
 EMERGENCY DRAINS SHALL BE SIZED FOR THE
 TOTAL AREA THAT WILL BE DRAINED FOR EACH
 AREA. PLEASE INDICATE THE TOTAL AREA
 BEING DRAINED FOR EACH EMERGENCY DRAIN
 AND SIZE ED'S ACCORDINGLY. SECTION
 1107.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]