| Plan Review Notes For Permit 05091265 |
| Permit Number |
05091265 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-08-28 00:00:00 | | | | | | | PASSED/PROVISO | | | | | | MANUF. SPECIFICATION SHEETS REQUIRED AT | | | THE TIME OF BUILD-0UT OF KITCHEN, AND AT | | | THE TIME OF APPLICATION FOR THE GAS | | | PERMIT FOR THE POOL HEATERS. - MANUF. SPECIFICATION | | | SHEET ALSO REQUIRED FOR | | | THE GAS REGULATORS. INDICATE THE MODEL | | | NUMBER FOR REGULATORS. REGULATORS SHALL | | | BE LISTED. | | | | | | | | | REVISION REQUIRED FOR SHT P3.16 | | | INDICATING THE CORRECT INLET PRESSURE | | | FROM THE METER, AND SHOWING UNIONS | | | DOWNSTREAM OF THE SHUT OFF VALVES FOR | | | THE REGULATORS.-PIPE SIZING SHALL BE | | | CHECKED WHEN INLET PRESSURE IS | | | CLARIFIED. |
|