Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop B
Sequence Number 3
Notes
Date Text
2006-08-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05091265
 ADD: 430 HIBISCUS
 CONT:PROJECT
 TEL: (561)586-2913
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECT: COHEN, FREEDMAN, ENCINOSA
 & ASSOC. STUART COHEN/ GULLERMO ENCINOSA
 8085 N. W. 155 ST
 MIAMI, FL
 T(305)826-4155
  
 STRUCTURAL: DE LOS REYESENGINEERING, INC
 8726 S. W. 26 TH STREET SUITE 1&2
 HECTOR DE LOS REYES
 MIAMI, FL
 T(305)477-8826
  
 3RD REVIEW
 ACTION: DENIED
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) COMPLIED
  
 2) COMPLIED
  
 3) THIS WILL BE A NEW REQUEST SINCE THE
 REDESIGN OF THE CLUBHOUSE. AS DISCUSSED
 EARLIER IN PREVIOUS MEETINGS, A 2 HR
 FIRE RATING WILL NEED TO BE PROVIDED FOR
 THE STEEL ROOF FRAMING MEMBERS. TO DATE
 NO INFORMATION HAS BEEN PROVIDED.
  
 4) 2ND REQUEST, MOST OF THE SUBMITTALS
 ARE FILED UNDER THE 2001 FBC, THIS
 PROJECT IS FILED UNDER THE 2004 FBC,
 PLEASE SCROLL THROUGH THE 2004 REPORTS.
 NOT ALL PRODUCTS FILED UNDER THE 2001
 MEET THE 2004 STANDARDS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) 3RD REQUEST, FL BLD CODE 1606.1.5:
 COMPONENTS & CLADDING, PROVIDE 2
 COPIES(3 IF THRESH- OLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING
 REPORTS,MISSING REPORTS ARE AS FOLLOWS:
 A) EXTERIOR FIXED WINDOWS
 RC ALUMINIUM SUBMITED 2001 APPROVAL,
 SERIES FX 345 NOT FOUND UNDER THE
 FBC 2004. PLEASE HIGHLIGHT TYPE OF
 GLASS IF MULTIPLE SYSTEMS AVAILABLE.
 B) EXTERIOR WINDOWS OPERATABLE:
 RC ALUMINIUM SUBMITTED 2001 APPROVAL,
 C) MULLIONS: MAY OR MAY NOT BE INCLUDED
  
 IN NOA DEPENDING ON SPANS.
 D) EXTERIOR GLAZED DOORS:
 RC ALUMINIUM SUBMITTED 2001 APPROVAL
 E) EXTERIOR ROLL UP DOORS:
 CORNELL IRON WORKS, IS MISSING THE
 EVALUAATION REPORT ER-05-0003
 PAGES 1-3, PLUS 23 TECHNICAL SHEETS.
 HIGHLIGHT WHICH TABLE (PSF) AND SPANS
  
 USED.
 F) EXTERIOR SWING DOORS:
 BARON METAL IND. INC. 2004 COVERSHEET
 TIES TO THE NOA 04-0330.01 NOT THE
 REPORT SUBMITTED. NOTE REPORT IS ONLY
  
 GOOD FOR +/-75 PSF. END PRESSURES ARE
  
 PROFESSIONALS STAMP REVIEWED IF
 PRODUCT DOESN'T WORK!!!!!
 G) LOUVER: SUBMITTED 2001 REPORT.
 H) SHUTTERS: HURST PRINT OUT CURRENT
 REPORTTHAT IS APPROVED, SUBMITTED
 STATES PENDING.SUBMIT THE CURRENT NOA
 THAT TIES TO THIS REPORT. THE ONE
 SUBMITTED IS EXPIRED.
 I) ROOFING ASSEMBLIES:
 MODIFIED, PLEASE HIGHLIGHT WHICH
 SUBSYSTEM TO BE USED. PLEASE CHECK
 COMPONENTS TO MATCH SUBSYSTEM. ALSO
 SEE NOTE# 7 SYSTEMS LIMITATION & RAS
 117 CALCULATIONS FOR ADDITIONAL
 FASTENING.
 J) METAL ROOFING, SUBMITTED 2001 REPORT,
 HIGHLIGHT SUBSYSTEM TO BE USED.
 K) TRUSS ANCHOR NO REPORT SUBMITTED
 L) EXTERIOR RAILINGS: NO REPORT
 SUBMITTED
 6) ENERGY CALCS BOTH 2001 AND 2004 CALCS
  
 HAVE BEEN SUBMITTED.
  
 7) ONLY ONE SET OF SOILS REPORT
 SUBMITTED, COPIED NOT SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 8)STRUCTURAL PLANS:
 RULE 61G155-23.001(1) F.A.C.
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS HAS CLEANED UP THE APPEARANCE
 OF THE SEAL BY ELIMINATING OBSOLETE
 CONTENT AND CHANGING THE WORD
 "CERTIFICATE" TO "LICENSE". A GRACE
 PERIOD RAN THROUGH DEC. 31,2005.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  