| 2006-08-01 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05091265 |
| | ADD: 430 HIBISCUS |
| | CONT:PROJECT |
| | TEL: (561)586-2913 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | ARCHITECT: COHEN, FREEDMAN, ENCINOSA |
| | & ASSOC. STUART COHEN/ GULLERMO ENCINOSA |
| | 8085 N. W. 155 ST |
| | MIAMI, FL |
| | T(305)826-4155 |
| | |
| | STRUCTURAL: DE LOS REYESENGINEERING, INC |
| | 8726 S. W. 26 TH STREET SUITE 1&2 |
| | HECTOR DE LOS REYES |
| | MIAMI, FL |
| | T(305)477-8826 |
| | |
| | 3RD REVIEW |
| | ACTION: DENIED |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | 1) COMPLIED |
| | |
| | 2) COMPLIED |
| | |
| | 3) THIS WILL BE A NEW REQUEST SINCE THE |
| | REDESIGN OF THE CLUBHOUSE. AS DISCUSSED |
| | EARLIER IN PREVIOUS MEETINGS, A 2 HR |
| | FIRE RATING WILL NEED TO BE PROVIDED FOR |
| | THE STEEL ROOF FRAMING MEMBERS. TO DATE |
| | NO INFORMATION HAS BEEN PROVIDED. |
| | |
| | 4) 2ND REQUEST, MOST OF THE SUBMITTALS |
| | ARE FILED UNDER THE 2001 FBC, THIS |
| | PROJECT IS FILED UNDER THE 2004 FBC, |
| | PLEASE SCROLL THROUGH THE 2004 REPORTS. |
| | NOT ALL PRODUCTS FILED UNDER THE 2001 |
| | MEET THE 2004 STANDARDS. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 5) 3RD REQUEST, FL BLD CODE 1606.1.5: |
| | COMPONENTS & CLADDING, PROVIDE 2 |
| | COPIES(3 IF THRESH- OLD OR RESIDENT |
| | INSPECTOR) OF PRODUCT TESTING |
| | REPORTS,MISSING REPORTS ARE AS FOLLOWS: |
| | A) EXTERIOR FIXED WINDOWS |
| | RC ALUMINIUM SUBMITED 2001 APPROVAL, |
| | SERIES FX 345 NOT FOUND UNDER THE |
| | FBC 2004. PLEASE HIGHLIGHT TYPE OF |
| | GLASS IF MULTIPLE SYSTEMS AVAILABLE. |
| | B) EXTERIOR WINDOWS OPERATABLE: |
| | RC ALUMINIUM SUBMITTED 2001 APPROVAL, |
| | C) MULLIONS: MAY OR MAY NOT BE INCLUDED |
| | |
| | IN NOA DEPENDING ON SPANS. |
| | D) EXTERIOR GLAZED DOORS: |
| | RC ALUMINIUM SUBMITTED 2001 APPROVAL |
| | E) EXTERIOR ROLL UP DOORS: |
| | CORNELL IRON WORKS, IS MISSING THE |
| | EVALUAATION REPORT ER-05-0003 |
| | PAGES 1-3, PLUS 23 TECHNICAL SHEETS. |
| | HIGHLIGHT WHICH TABLE (PSF) AND SPANS |
| | |
| | USED. |
| | F) EXTERIOR SWING DOORS: |
| | BARON METAL IND. INC. 2004 COVERSHEET |
| | TIES TO THE NOA 04-0330.01 NOT THE |
| | REPORT SUBMITTED. NOTE REPORT IS ONLY |
| | |
| | GOOD FOR +/-75 PSF. END PRESSURES ARE |
| | |
| | PROFESSIONALS STAMP REVIEWED IF |
| | PRODUCT DOESN'T WORK!!!!! |
| | G) LOUVER: SUBMITTED 2001 REPORT. |
| | H) SHUTTERS: HURST PRINT OUT CURRENT |
| | REPORTTHAT IS APPROVED, SUBMITTED |
| | STATES PENDING.SUBMIT THE CURRENT NOA |
| | THAT TIES TO THIS REPORT. THE ONE |
| | SUBMITTED IS EXPIRED. |
| | I) ROOFING ASSEMBLIES: |
| | MODIFIED, PLEASE HIGHLIGHT WHICH |
| | SUBSYSTEM TO BE USED. PLEASE CHECK |
| | COMPONENTS TO MATCH SUBSYSTEM. ALSO |
| | SEE NOTE# 7 SYSTEMS LIMITATION & RAS |
| | 117 CALCULATIONS FOR ADDITIONAL |
| | FASTENING. |
| | J) METAL ROOFING, SUBMITTED 2001 REPORT, |
| | HIGHLIGHT SUBSYSTEM TO BE USED. |
| | K) TRUSS ANCHOR NO REPORT SUBMITTED |
| | L) EXTERIOR RAILINGS: NO REPORT |
| | SUBMITTED |
| | 6) ENERGY CALCS BOTH 2001 AND 2004 CALCS |
| | |
| | HAVE BEEN SUBMITTED. |
| | |
| | 7) ONLY ONE SET OF SOILS REPORT |
| | SUBMITTED, COPIED NOT SEALED. |
| | PLANS, SPECIFICATIONS, REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 8)STRUCTURAL PLANS: |
| | RULE 61G155-23.001(1) F.A.C. |
| | THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEERS HAS CLEANED UP THE APPEARANCE |
| | OF THE SEAL BY ELIMINATING OBSOLETE |
| | CONTENT AND CHANGING THE WORD |
| | "CERTIFICATE" TO "LICENSE". A GRACE |
| | PERIOD RAN THROUGH DEC. 31,2005. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |