Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop P
Sequence Number 25
Notes
Date Text
2007-12-17 12:56:49REVISIONS DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P2.03 REVISIONS 7, 8 & 13 WERE NOT FOUND. THE
 PREVIOUS APPROVED SHEET P2.03 WAS DATED 10-06-2006 AND
 HAD REVISIONS 3, 4 & 5. PLEASE CLOUD ALL REVISIONS NOT
 PREVIOUSLY APPROVED AND INDICATE ALL REVISIONS WITH A
 NUMBERED TRIANGLE. SECTION 106.1.3.
  
 2. SHT P2.19 REVISIONS11 & 13 WERE NOT FOUND. THE
 PREVIOUS APPROVED SHEET P2.19 WAS DATED 10-06-2006 AND
 HAD REVISIONS 3, 4, 5 & 6. PLEASE CLOUD ALL REVISIONS
 NOT PREVIOUSLY APPROVED AND INDICATE ALL REVISIONS WITH
 A NUMBERED TRIANGLE. SECTION 106.1.3.
  
 3. SHT P2.20 REVISIONS 7, 8 & 13 WERE NOT FOUND. THE
 PREVIOUS APPROVED SHEET P2.20 WAS DATED 11-20-2007 AND
 HAD REVISIONS 3, 4, 5 & 6. PLEASE CLOUD ALL REVISIONS
 NOT PREVIOUSLY APPROVED AND INDICATE ALL REVISIONS WITH
 A NUMBERED TRIANGLE. SECTION 106.1.3.
  
 4. SHT P3.02 REVISIONS8 & 13 WERE NOT FOUND. THE
 PREVIOUS APPROVED SHEET P3.02 WAS DATED 11-20-2007 AND
 HAD REVISIONS 3, 4, 5, 6 & 7. PLEASE CLOUD ALL
 REVISIONS NOT PREVIOUSLY APPROVED AND INDICATE ALL
 REVISIONS WITH A NUMBERED TRIANGLE. SECTION 106.1.3.
  
 5. SHT P3.12 REVISION 14 WAS NOT FOUND. THE PREVIOUS
 APPROVED SHEET P3.12 WAS DATED 11-20-2007 AND HAD
 REVISIONS 3, 4 & 5. PLEASE CLOUD ALL REVISIONS NOT
 PREVIOUSLY APPROVED AND INDICATE ALL REVISIONS WITH A
 NUMBERED TRIANGLE. SECTION 106.1.3.
  
 6. SHT P4.02 REVISION IS INDICATED AS AN ADDITION OF
 THE GENERATOR WITH DIESEL INFORMATION ONLY. THE DIESEL
 PERMIT IS A MECHANICAL PERMIT AND AS SUCH ALL REVISIONS
 FOR DIESEL SHALL BE SUBMITTED ON THE MECHANICAL SHEETS,
 NOT THE PLUMBING SHEETS.
  