 ** DENIED REVIEW OF SELECTIVE COORDINATION STUDY**
  
 1) NOTE: PLEASE SEE THERE ARE MANY ITEMS ON THE SCS
 WHICH DO NOT COORDINATE WITH THE PLANS ON FILE. PLEASE
 SEE 240.12,700.27 AND 701.18.
 THE FOLLOWING WILL BE SOME EXAMPLES ONLY AND ARE IN NO
 WAY ALL ITEMS ON THE REPORT WHICH DOES NOT MATCH WITH
 PLANS.
  
 A) PLEASE SEE SECTION #5 OF THE REPORT AND OTHER
 SECTIONS WHICH DO NOT SEEM TO INDICATE THE EDPH PANEL
 AS CONTAINING A MAIN CIRCUIT BREAKER. PLANS SHOW A 100K
 RATED MCB.
  
 B) PLEASE SEE THE HEC PANEL LISTED IN SECTION #5 ON
 EDPH WHICH SHOWS A 300AMP BREAKER YET THE PLANS ON FILE
 INDICATE A 150AMP BREAKER. THE PANEL HEC IS NOT EVEN
 RATED FOR 300AMPS.
  
 C) PLEASE SEE DAPPER FAULT ANALYSIS INPUT REPORT.
 SWB MSBE SHOWS COPPER BUS DUCT STAB. PLEASE VERIFY.
 PLEASE SEE OTHERS SUCH AS ATS/MSBE SHOWS COPPER, EDPH
 COPPER, FIRE PUMP COPPER, ETC ETC
 PLEASE SEE THE SIZE OF CONDUCTORS FOR ITEMS SUCH AS
 FIRE PUMP WHICH ARE SHOWN AS 3/0 COPPER YET THE RISER
 ON FILE SHOWS 250MCM ALUMINUM.
 PLEASE SEE THE DISTANCE OF FEEDERS FOR THE FIRE PUMP
 UNDER NORMAL AND EMERGENCY WHICH IS SHOWN AS 500FEET.
 THIS IS NOT POSSIBLE.
 PLEASE SEE OTHER PANELS FOR FEEDERS, DISTANCE, WHICH
 DOES NOT MATCH.
 GEHB SHOWS 3/0 ON REPORT AND SHOWS 1/0 ON PLANS. THE
 DISTANCE ON THIS FEEDER ALONE CALLS FOR 75FEET HOWEVER
 BASED ON THE LOCATION OF THIS PANEL ON THE PLANS THE
 DISTANCE IS FAR GREATER.
 HEA, 3/0 ON REPORT, SHOWS 1/0 ON PLANS.
 HEC SHOWS 3/0 ON REPORT YET SHOWS 1/0 ON PLANS.
 REHA SHOWS 500 MCM ON REPORT AND 400MCM ON PLANS.
 REHC SHOWS 500MCM ON REPORT AND 400MCM ON PLANS.
  
 **** TO BE NOTED ONCE AGAIN. THESE ARE ONLY SOME
 EXAMPLES OF THE INCONSISTENCIES AND ARE NOT ALL
 POSSIBLE COORDINATION ISSUES.
 ONE COPY OF THE REPORT WILL BE RETAINED BY THIS OFFICE.
  
 2) NOTE: PLEASE KNOW A REVISION FEE OF $60 IS DUE. FBC
 108.3
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved