| 2008-09-16 14:44:00 | |
| | ** DENIED REVIEW OF SELECTIVE COORDINATION STUDY** |
| | |
| | 1) NOTE: PLEASE SEE THERE ARE MANY ITEMS ON THE SCS |
| | WHICH DO NOT COORDINATE WITH THE PLANS ON FILE. PLEASE |
| | SEE 240.12,700.27 AND 701.18. |
| | THE FOLLOWING WILL BE SOME EXAMPLES ONLY AND ARE IN NO |
| | WAY ALL ITEMS ON THE REPORT WHICH DOES NOT MATCH WITH |
| | PLANS. |
| | |
| | A) PLEASE SEE SECTION #5 OF THE REPORT AND OTHER |
| | SECTIONS WHICH DO NOT SEEM TO INDICATE THE EDPH PANEL |
| | AS CONTAINING A MAIN CIRCUIT BREAKER. PLANS SHOW A 100K |
| | RATED MCB. |
| | |
| | B) PLEASE SEE THE HEC PANEL LISTED IN SECTION #5 ON |
| | EDPH WHICH SHOWS A 300AMP BREAKER YET THE PLANS ON FILE |
| | INDICATE A 150AMP BREAKER. THE PANEL HEC IS NOT EVEN |
| | RATED FOR 300AMPS. |
| | |
| | C) PLEASE SEE DAPPER FAULT ANALYSIS INPUT REPORT. |
| | SWB MSBE SHOWS COPPER BUS DUCT STAB. PLEASE VERIFY. |
| | PLEASE SEE OTHERS SUCH AS ATS/MSBE SHOWS COPPER, EDPH |
| | COPPER, FIRE PUMP COPPER, ETC ETC |
| | PLEASE SEE THE SIZE OF CONDUCTORS FOR ITEMS SUCH AS |
| | FIRE PUMP WHICH ARE SHOWN AS 3/0 COPPER YET THE RISER |
| | ON FILE SHOWS 250MCM ALUMINUM. |
| | PLEASE SEE THE DISTANCE OF FEEDERS FOR THE FIRE PUMP |
| | UNDER NORMAL AND EMERGENCY WHICH IS SHOWN AS 500FEET. |
| | THIS IS NOT POSSIBLE. |
| | PLEASE SEE OTHER PANELS FOR FEEDERS, DISTANCE, WHICH |
| | DOES NOT MATCH. |
| | GEHB SHOWS 3/0 ON REPORT AND SHOWS 1/0 ON PLANS. THE |
| | DISTANCE ON THIS FEEDER ALONE CALLS FOR 75FEET HOWEVER |
| | BASED ON THE LOCATION OF THIS PANEL ON THE PLANS THE |
| | DISTANCE IS FAR GREATER. |
| | HEA, 3/0 ON REPORT, SHOWS 1/0 ON PLANS. |
| | HEC SHOWS 3/0 ON REPORT YET SHOWS 1/0 ON PLANS. |
| | REHA SHOWS 500 MCM ON REPORT AND 400MCM ON PLANS. |
| | REHC SHOWS 500MCM ON REPORT AND 400MCM ON PLANS. |
| | |
| | **** TO BE NOTED ONCE AGAIN. THESE ARE ONLY SOME |
| | EXAMPLES OF THE INCONSISTENCIES AND ARE NOT ALL |
| | POSSIBLE COORDINATION ISSUES. |
| | ONE COPY OF THE REPORT WILL BE RETAINED BY THIS OFFICE. |
| | |
| | 2) NOTE: PLEASE KNOW A REVISION FEE OF $60 IS DUE. FBC |
| | 108.3 |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |