| Plan Review Notes For Permit 05091265 |
| Permit Number |
05091265 |
|
| Review Stop |
E |
| Sequence Number |
23 |
|
| Notes |
| Date |
Text |
| 2008-09-04 15:00:38 | REVSIONS. | | | | | | ***REQUIRED BEFORE TCO. | | | NEED COORDINATION STUDY OF EMERGECNY | | | SYSTEMS/PANELS/EQUIPMENT PER 240.12, NFPA-110 6.5 | | | PROTECTION. | | | | | | 6.5.1* GENERAL. THE OVERCURRENT PROTECTIVE DEVICES IN | | | THE EPSS SHALL BE COORDINATED TO OPTIMIZE SELECTIVE | | | TRIPPING OF THE CIRCUIT OVERCURRENT PROTECTIVE DEVICES | | | WHEN A SHORT CIRCUIT OCCURS. | | | | | | 6.5.2 SHORT CIRCUIT CURRENT. THE MAXIMUM AVAILABLE | | | SHORT CIRCUIT CURRENT FROM BOTH THE UTILITY SOURCE AND | | | THE EMERGENCY ENERGY SOURCE SHALL BE EVALUATED FOR | | | ABILITY TO SATISFY THIS COORDINATION CAPABILITY. | | | | | | 6.5.3* OVERCURRENT PROTECTIVE DEVICE RATING. THE | | | OVERCURRENT PROTECTIVE DEVICE SHALL HAVE AN | | | INTERRUPTING RATING EQUAL TO OR GREATER THAN THE | | | MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT AT ITS | | | LOCATION. | | | | | | 6.5.4 ACCESSIBILITY. OVERCURRENT DEVICES IN EPSS | | | CIRCUITS SHALL BE ACCESSIBLE TO AUTHORIZED PERSONS | | | ONLY. | | | | | | | | | |
|