2008-09-04 15:00:38REVSIONS.
  
 ***REQUIRED BEFORE TCO.
 NEED COORDINATION STUDY OF EMERGECNY
 SYSTEMS/PANELS/EQUIPMENT PER 240.12, NFPA-110 6.5
 PROTECTION.
  
 6.5.1* GENERAL. THE OVERCURRENT PROTECTIVE DEVICES IN
 THE EPSS SHALL BE COORDINATED TO OPTIMIZE SELECTIVE
 TRIPPING OF THE CIRCUIT OVERCURRENT PROTECTIVE DEVICES
 WHEN A SHORT CIRCUIT OCCURS.
  
 6.5.2 SHORT CIRCUIT CURRENT. THE MAXIMUM AVAILABLE
 SHORT CIRCUIT CURRENT FROM BOTH THE UTILITY SOURCE AND
 THE EMERGENCY ENERGY SOURCE SHALL BE EVALUATED FOR
 ABILITY TO SATISFY THIS COORDINATION CAPABILITY.
  
 6.5.3* OVERCURRENT PROTECTIVE DEVICE RATING. THE
 OVERCURRENT PROTECTIVE DEVICE SHALL HAVE AN
 INTERRUPTING RATING EQUAL TO OR GREATER THAN THE
 MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT AT ITS
 LOCATION.
  
 6.5.4 ACCESSIBILITY. OVERCURRENT DEVICES IN EPSS
 CIRCUITS SHALL BE ACCESSIBLE TO AUTHORIZED PERSONS
 ONLY.
  
  
  