| 2007-11-01 15:22:06 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT P2.01 REVISION SUBMITTED SHOWS THE LATEST |
| | REVISION AS #13. REVISIONS 13 & 14 WERE APPROVED ON |
| | 10-15-07. REVISION RETURNED. |
| | |
| | 2. SHT P2.05 KEY NOTE #13 NOT FOUND ON THE FLOOR PLAN. |
| | SOME REVISIONS WERE FOUND THAT HAD NO CLOUDS OR DELTA |
| | REVISION NUMBERS. PLEASE INDICATE ALL REVISIONS WITH |
| | CLOUDS AND REVISION NUMBERS. SECTION 106.1.3. |
| | |
| | 3. SHT P2.17 PLANS AT THE TIME OF PERMIT SHOW REVISION |
| | #6 DATED 8-7-06. SHEET SUBMITTED SHOWS A NEW REVISION |
| | #6 DATED 4-27-07. FOR RECORD KEEPING A REVISION NUMBER |
| | IS ONLY USED ONCE AND A PROGRESSIVE SEQUENCE WILL BE |
| | USED. THE REVISION DATED 4-27-07 WAS NOT PREVIOUSLY |
| | SUBMITTED AND IS NOT APPROVED. SECTION 106.1.3. |
| | |
| | 4. SHT P2.19 PLANS AT THE TIME OF PERMIT SHOW REVISION |
| | #6 DATED 8-7-06. SHEET SUBMITTED SHOWS A NEW REVISION |
| | #6 DATED 4-27-07. FOR RECORD KEEPING A REVISION NUMBER |
| | IS ONLY USED ONCE AND A PROGRESSIVE SEQUENCE WILL BE |
| | USED. THE REVISION DATED 4-27-07 WAS NOT PREVIOUSLY |
| | SUBMITTED AND IS NOT APPROVED. SECTION 106.1.3.-- |
| | ALSO SEE THE FOLLOWING COMMENTS FROM THE PREVIOUS |
| | REVISION REVIEWS: --AS INDICATED IN THE REVISION |
| | DENIAL DATED 07/07/07, SEE THE FOLLOWING COMMENTS STILL |
| | NOT ADDRESSED: |
| | ***2. SHT P2.19 A RELIEF VENT IS REQUIRED FOR THE AAV |
| | TO THE SINK AT THE POOL DECK LEVEL. SECTION 917.3.2. |
| | ALSO A REVISION WILL BE REQUIRED FOR THE SANITARY RISER |
| | DIAGRAM TO REFLECT THE CHANGE TO THE SANT. SYSTEM. |
| | SECTION 106.1.1.---KEY NOTES #12 THE OVERFLOW |
| | FROM THE COLLECTOR TANKS SHALL DRAIN TO STORM, NOT |
| | SANITARY.---REVISION #6 INDICATED AS COORD. REV. |
| | 01-17-07. PLANS WERE ISSUED WITH A REVISION #6 "BLDG |
| | DEPT COMM" 08-07-06. IN ORDER TO TRACK ALL REVISIONS, |
| | ONLY ONE REVISION PER REVISION NUMBER WILL BE ALLOWED. |
| | SECTION 106.1.3.**** |
| | |
| | 5. SHT P2.20 PLANS AT THE TIME OF PERMIT SHOW REVISION |
| | #6 DATED 8-7-06. SHEET SUBMITTED SHOWS A NEW REVISION |
| | #6 DATED 4-27-07. FOR RECORD KEEPING A REVISION NUMBER |
| | IS ONLY USED ONCE AND A PROGRESSIVE SEQUENCE WILL BE |
| | USED. THE REVISION DATED 4-27-07 WAS NOT PREVIOUSLY |
| | SUBMITTED AND IS NOT APPROVED. SECTION 106.1.3.-- |
| | ALSO THIS REVISION THE SANITARY PIPING IS NOT SHOWN AT |
| | THE FIXTURES IN THE MEN'S AND WOMEN'S TOILET ROOMS AS |
| | WELL AS AT THE DRINKING FOUNTAINS. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | ***********NOTE: THE PREVIOUSLY APPROVED REVISIONS ON |
| | EACH SHEET SHALL BE TURNED OFF WHEN SUBMITTING |
| | REVISIONS FOR REVIEW. THIS HAS BEEN REQUESTED QUITE A |
| | FEW TIMES IN THE PAST BUT TO NO AVAIL. AS INDICATED |
| | PREVIOUSLY THE REVIEW TURN AROUND TIME AND THE PROCESS |
| | FOR REVISIONS IS SLOWED DOWN WHEN ONE HAS TO LOOK |
| | THROUGH ALL CLOUDS AND ALL REVISION NUMBERS FOR ALL |
| | REVISIONS, EVEN THOUGH MOST REVISIONS HAVE BEEN |
| | PREVIOUSLY BEEN APPROVED. THE PREVIOUSLY APPROVED |
| | REVISIONS ARE PART OF THE PLANS AND ARE NOT REVISIONS |
| | AFTER THAT. --- P L E A S E TURN OFF ALL PREVIOUSLY |
| | APPROVED REVISIONS WHEN SUBMITTING REVISIONS FOR |
| | REVIEW. THANKING YOU IN ADVANCE FOR YOUR COOPERATION. |
| | |