Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop P
Sequence Number 21
Notes
Date Text
2007-11-01 15:22:06DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P2.01 REVISION SUBMITTED SHOWS THE LATEST
 REVISION AS #13. REVISIONS 13 & 14 WERE APPROVED ON
 10-15-07. REVISION RETURNED.
  
 2. SHT P2.05 KEY NOTE #13 NOT FOUND ON THE FLOOR PLAN.
 SOME REVISIONS WERE FOUND THAT HAD NO CLOUDS OR DELTA
 REVISION NUMBERS. PLEASE INDICATE ALL REVISIONS WITH
 CLOUDS AND REVISION NUMBERS. SECTION 106.1.3.
  
 3. SHT P2.17 PLANS AT THE TIME OF PERMIT SHOW REVISION
 #6 DATED 8-7-06. SHEET SUBMITTED SHOWS A NEW REVISION
 #6 DATED 4-27-07. FOR RECORD KEEPING A REVISION NUMBER
 IS ONLY USED ONCE AND A PROGRESSIVE SEQUENCE WILL BE
 USED. THE REVISION DATED 4-27-07 WAS NOT PREVIOUSLY
 SUBMITTED AND IS NOT APPROVED. SECTION 106.1.3.
  
 4. SHT P2.19 PLANS AT THE TIME OF PERMIT SHOW REVISION
 #6 DATED 8-7-06. SHEET SUBMITTED SHOWS A NEW REVISION
 #6 DATED 4-27-07. FOR RECORD KEEPING A REVISION NUMBER
 IS ONLY USED ONCE AND A PROGRESSIVE SEQUENCE WILL BE
 USED. THE REVISION DATED 4-27-07 WAS NOT PREVIOUSLY
 SUBMITTED AND IS NOT APPROVED. SECTION 106.1.3.--
 ALSO SEE THE FOLLOWING COMMENTS FROM THE PREVIOUS
 REVISION REVIEWS: --AS INDICATED IN THE REVISION
 DENIAL DATED 07/07/07, SEE THE FOLLOWING COMMENTS STILL
 NOT ADDRESSED:
 ***2. SHT P2.19 A RELIEF VENT IS REQUIRED FOR THE AAV
 TO THE SINK AT THE POOL DECK LEVEL. SECTION 917.3.2.
 ALSO A REVISION WILL BE REQUIRED FOR THE SANITARY RISER
 DIAGRAM TO REFLECT THE CHANGE TO THE SANT. SYSTEM.
 SECTION 106.1.1.---KEY NOTES #12 THE OVERFLOW
 FROM THE COLLECTOR TANKS SHALL DRAIN TO STORM, NOT
 SANITARY.---REVISION #6 INDICATED AS COORD. REV.
 01-17-07. PLANS WERE ISSUED WITH A REVISION #6 "BLDG
 DEPT COMM" 08-07-06. IN ORDER TO TRACK ALL REVISIONS,
 ONLY ONE REVISION PER REVISION NUMBER WILL BE ALLOWED.
 SECTION 106.1.3.****
  
 5. SHT P2.20 PLANS AT THE TIME OF PERMIT SHOW REVISION
 #6 DATED 8-7-06. SHEET SUBMITTED SHOWS A NEW REVISION
 #6 DATED 4-27-07. FOR RECORD KEEPING A REVISION NUMBER
 IS ONLY USED ONCE AND A PROGRESSIVE SEQUENCE WILL BE
 USED. THE REVISION DATED 4-27-07 WAS NOT PREVIOUSLY
 SUBMITTED AND IS NOT APPROVED. SECTION 106.1.3.--
 ALSO THIS REVISION THE SANITARY PIPING IS NOT SHOWN AT
 THE FIXTURES IN THE MEN'S AND WOMEN'S TOILET ROOMS AS
 WELL AS AT THE DRINKING FOUNTAINS. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 ***********NOTE: THE PREVIOUSLY APPROVED REVISIONS ON
 EACH SHEET SHALL BE TURNED OFF WHEN SUBMITTING
 REVISIONS FOR REVIEW. THIS HAS BEEN REQUESTED QUITE A
 FEW TIMES IN THE PAST BUT TO NO AVAIL. AS INDICATED
 PREVIOUSLY THE REVIEW TURN AROUND TIME AND THE PROCESS
 FOR REVISIONS IS SLOWED DOWN WHEN ONE HAS TO LOOK
 THROUGH ALL CLOUDS AND ALL REVISION NUMBERS FOR ALL
 REVISIONS, EVEN THOUGH MOST REVISIONS HAVE BEEN
 PREVIOUSLY BEEN APPROVED. THE PREVIOUSLY APPROVED
 REVISIONS ARE PART OF THE PLANS AND ARE NOT REVISIONS
 AFTER THAT. --- P L E A S E TURN OFF ALL PREVIOUSLY
 APPROVED REVISIONS WHEN SUBMITTING REVISIONS FOR
 REVIEW. THANKING YOU IN ADVANCE FOR YOUR COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]