| Date |
Text |
| 2006-05-26 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 BUILDING |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | MUNICIPAL CODE WPB |
| | |
| | FROM PREVIOUS REVIEW: THE COMMENT |
| | NUMBERS SHALL REMAIN THE SAME AS FIRST |
| | REVIEW: - NO COMMENT RESPONSES SUBMITTED |
| | FOR THE FIRST REVIEW. |
| | |
| | 2. SHT A1.0 MEN'S & WOMEN'S TOILET ROOMS |
| | SHALL BE ACCESSIBLE. SUBMIT DETAILS |
| | SHOWING COMPLIANCE WITH SECTIONS |
| | 11-4.16, 11-4.19, & 11-4.22 AND ALL |
| | SUBSECTIONS. |
| | *** COMMENT NOT ADDRESSED. SHOW THE |
| | FOLLOWING: FOR W/C'S |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.5 FLUSH CONTROLS |
| | FOR LAVS |
| | A. 11-4.19.2 CLEARANCES |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | D. 11-4.19.5 FAUCETS |
| | |
| | 3. SHT A1.0 THE DRINKING FOUNTAIN SHALL |
| | BE ACCESSIBLE. SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH SECTIONS 11-4.15 AND ALL |
| | SUBSECTIONS AS WELL AS SECTION |
| | 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO |
| | HAVE DIFFICULTY BENDING OR STOOPING. |
| | ***COMMENT CONCERNING 11-4.1.3(10)(A) |
| | NOT ADDRESSED. CLEAR FLOOR SPACE SHALL |
| | ALLOW FORWARD APPROACH. 11-4.15.5(1). |
| | |
| | 4. SHT A1.2 MEN'S & WOMEN'S TOILET ROOMS |
| | SHALL BE ACCESSIBLE. SUBMIT DETAILS |
| | SHOWING COMPLIANCE WITH SECTIONS |
| | 11-4.16, 11-4.19, 11-4.21, 11-4.22 AND |
| | ALL SUBSECTIONS. ALSO FOR THE BREAK ROOM |
| | SINK, 11-4.24 AND ALL SUBSECTIONS. |
| | ***COMMENT NOT ADDRESSED. SEE COMMENT |
| | NUMBER 2 FOR INFORMATION STILL REQUIRED |
| | FOR W/C'S AND LAVS. |
| | FOR SHOWERS |
| | A. 11-4.21.3 SEAT (FOLD-UP TYPE) |
| | B. 11-4.21.5 CONTROLS (FIG. 11-37) |
| | C. 11-4.21.6 SHOWER UNIT |
| | D. 11-4.21.7 CURBS |
| | SUBMIT ELEVATIONS FOR THE SHOWER SHOWING |
| | COMPLIANCE FOR THE PRIOR REQUIREMENTS. |
| | |
| | 5. SHT A1.18 MEN'S AND WOMEN'S LOCKER |
| | ROOMS TO BE ACCESSABLE. SUBMIT DETAILS |
| | SHOWING COMPLIANCE WITH SECTION 11-4.16, |
| | 11-4.18, 11-4.19, 11-4.21, & 11-4.22 AND |
| | ALL SUBSECTIONS. |
| | ***COMMENT NOT ADDRESSED. SEE COMMENT |
| | NUMBER TWO FOR INFORMATION STILL |
| | REQUIRED. ALSO THE INFORMATION FOR THE |
| | URINAL STILL REQUIRED: |
| | A. 11-4.18.2 HEIGHT |
| | B. 11-4.18.4 FLUSH CONTROLS |
| | |
| | 6. SHT A1.21 MEN'S & WOMEN'S TOILET |
| | ROOMS AND DRINKING FOUNTAIN SHALL BE |
| | ACCESSIBLE. (SEE COMMENTS 2, 3 & 5). |
| | ***COMMENT NOT ADDRESSED. SEE COMMENT |
| | NUMBER TWO FOR INFORMATION STILL |
| | REQUIRED. |
| | |
| | 11. SHT A9.24 UNITS C1.1, C1.2, & C1 |
| | OPENING FOR WATER CLOSET IN BATH #2 |
| | SHALL BE MINIMUM 33" . PLEASE INDICATE |
| | ON PLANS. PAGE 7.44. |
| | ***COMMENT NOT ADDRESSED. |
| | |
| | 12. SHTS A9.2 THRU A9.24 ALL UNITS. |
| | CLEAR FLOOR SPACE FOR THE WATER CLOSETS |
| | SHALL BE APPLIED OR SUPERIMPOSED OVER A |
| | PLAN PER PAGE 7.43 PARAGRAPH ONE. |
| | ***COMMENT NOT ADDRESSED. |
| | |
| | 13. SHTS A9.2 THRU A9.24 PER PAGE 7.7 |
| | MINIMUM CLEARANCES BETWEEN COUNTERS AND |
| | ALL OPPOSING ELEMENTS IS 40". PLEASE |
| | INDICATE ON THE PLANS THE MINIMUM |
| | CLEARANCE FOR ALL KITCHENS. |
| | ***COMMENT NOT ADDRESSED. |
| | |
| | 14. SHT P2.01 NO PIPING SHOWN TO 3 PAD'S |
| | PLEASE CLARIFY. SECTION 106.1.1. SHOW |
| | ALL PIPE SIZES FOR ALL PIPE SYSTEMS ON |
| | THE THE FLOOR PLAN. TABLES 710.1 & |
| | 1106.3. |
| | ***PAD'S STILL SHOWN, BUT NOT |
| | IDENTIFIED. PLEASE CLARIFY. - PIPE |
| | SIZING NOT SHOWN ON FLOOR PLAN PIPING. |
| | |
| | 15. SHT P2.02NO PIPING SHOWN TO 2 |
| | PAD'S. SECTION 106.1.1. - SHOW ALL PIPE |
| | SIZING FOR U/G BUILDING SANT. , STORM, |
| | COND., AND DRAIN PIPING. SECTION |
| | 106.1.1. TABLES 710.1 & 1106.3. |
| | ***PAD'S STILL SHOWN, BUT NOT |
| | IDENTIFIED, PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 19. SHTS P2.19 & P2.20 SUBMIT |
| | CALCULATIONS FOR PRIMARY AND SECONDARY |
| | STORM DRAINS. SHOW SQUARE FEET, 1/2 AREA |
| | OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS, AND AREA OF ROOFS DRAINING TO |
| | DECK AREA FROM ABOVE IN THE CALCULATIONS |
| | PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECITONS. - SHOW THE LOCATION OF ALL |
| | SECONDARY DRAINS. |
| | ***COMMENT NOT ADDRESSED. NO CALC'S |
| | FOUND. SECONDARY DRAIN LOCATIONS NOT |
| | SHOWN. CONTRIBUTION FROM THE PRIVACY |
| | WALLS TO BOTH SIDES AT THE DECK AREAS |
| | WERE NOT INDICATED. |
| | |
| | 23. SHT P3.02 2-WAY CLEANOUTS ARE |
| | REQUIRED ON BOTH THE ENTRANCE AND EXIT |
| | OF THE GREASE INTERCEPTOR PER UTILITY |
| | STANDARDS. - FIXTURE UNIT VALUE NOT |
| | SHOWN FOR 3 FUTURE STUB UPS. TABLE |
| | 710.1(1). |
| | ***2-WAY CLEANOUT NOT SHOWN ON THE INLET |
| | SIDE OF THE GREASE INTERCEPTOR. - |
| | FIXTURE UNIT VALUE STILL NOT SHOWN FOR |
| | ALL FUTURE STUB UPS. |
| | |
| | 26. SHT P3.08 KEY NOTES INFORMATION IS |
| | REVERSED FROM RISERS. PLEASE CORRELATE |
| | KEY NOTES AND RISERS. SECTION 106.1.1. |
| | ***THIS IS STILL NOT CHANGED ON ALL |
| | RISERS. |
| | |
| | |
| | 30. SHT P3.14 6PLEASE NUMBER |
| | OR PLACE A DESIGNATION ON THE LIFT |
| | STATIONS BOTH ON THE RISER DIAGRAMS AND |
| | THE FLOOR PLANS TO HELP EXPEDITE THE |
| | PLAN REVIEW. |
| | ***NOT ADDRESSED. |
| | |
| | 31. SHT P3.15 RISER DOES NOT REFLECT THE |
| | FLOOR PLAN. RISERS CD/37 & DR/37 ARE NOT |
| | SHOWN ON THE RISER DIAGRAM. |
| | ***NOT ADDRESSED. |
| | 32. DOMESTIC BOOSTER PUMPS, STORM LIFT |
| | STATION PUMPS SHALL BE LISTED. PLEASE |
| | SUBMIT MANUF. SPECIFICATION SHEETS FOR |
| | EACH. SECTION 303. |
| | ***NOT ADDRESSED. |
| | |
| | 33. GREASE INTECEPTOR SHALL BE SIZED BY |
| | THE ENVIRONMENTAL COMPLIANCE MANAGER. |
| | PLEASE CONTACT LYNN MASSON (561) |
| | 822-2271 OR BY FAX (561) 822-2279 OR BY |
| | E-MAIL [email protected]. |
| | ***NOT ADDRESSED. |
| | |
| | |
| | 35. PLANS SHOW A VENT IN THE WALL AND AN |
| | OPEN 2" DRAIN IN THE PLENUM. MORE |
| | INFORMATION IS REQUIRED. WILL THE ROOM |
| | AS A PLENUM PULL THE AIR FROM THE 2" |
| | OPEN DRAIN AND INTRODUCE THE HUMID, WARM |
| | AIR INTO THE AIR CONDITIONED AIR OF THE |
| | UNIT? IS THIS PRACTICE ACCEPTABLE TO THE |
| | MECHNAICAL ENGINEER? - ALSO THE VENT |
| | TERMINATION SHALL EITHER VENT THRU THE |
| | ROOF OR TERMINATE ABOVE THE CEILING 6" |
| | ABOVE THE INSULATION. |
| | ***NOT ADDRESSED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | ***NO COMMENT RESPONSE WAS SUBMITTED AND |
| | BECAUSE OF THAT AND PLAN DEVELOPMENT |
| | BETWEEN REVIEWS, THE RESUBMITTAL WAS |
| | TREATED AS A COMPLETE REVIEW OF THE |
| | PLAN. THIS CONTRIBUTES TO A LONGER TURN |
| | AROUND TIME FOR PLAN REVIEW. |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. SHT A9.27 DETAIL ELEVATIONS 3 & 5 NO |
| | DISPENSER SHOWN. STALL DOES NOT REFLECT |
| | FIG. 30E. LAV TO BE A MINIMUM 60" OFF |
| | THE W/C WALL. (MIN. 15" OFF WALL TO |
| | CENTERLINE OF LAV). WATER CLOSET TO BE |
| | 17" TO 19" OFF FLOOR TO SEAT. INDICATE |
| | ON PLANS. SHOW CLEARANCE FOR LAVS TO BE |
| | 2'3". SECTIONS 11-4.16.3, 11-4.16.6, |
| | 11-4.19.2, |
| | |
| | 2B. SHTS P2.01 THRU P2.0-5, P2.07, |
| | P2.08, P2.10, P2.11, P2.13, P2.14, |
| | P2.16, & P2.17 IDENTIFY ALL RISERS FOR |
| | ALL SYSTEMS. SECTION 106.1.1. |
| | |
| | 3B. SHT P2.02 8" FD TO STORM IN MAINT. |
| | ROOM. PLEASE INDICATE WHAT IS BEING |
| | DRAINED. IF NOT STORM WATER, DRAIN TO BE |
| | CONNECTED TO SANITARY. MUNICIPAL CODE |
| | SECTION 90-203. |
| | |
| | 4B. SHT P2.03 FITTING CONNECTING 2" |
| | DRAIN BETWEEN COLS. 28 & 29 TO BUILDING |
| | SANT. FITTING IS NOT INSTALLED TO GUIDE |
| | SEWAGE AND WASTE IN THE DIRECTION OF |
| | FLOW AS REQUIRED IN SECTION 706.3. |
| | |
| | 5B. SHT P2.05 SHOWS 2 W/26 RISERS. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 6B. SHT P2.06 SHOWS RWL/35 BETWEEN COLS. |
| | 28.1 AND 29. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 7B. SHTS P2.07, P2.10, & P2.13 SHOWS |
| | RWL/18 BETWEEN COLS. 5 & 6. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 8B. SHT P2.19 4"DD (1,525SF) & 3"PD |
| | (92SF) NOT SHOWN ON ANY RISER DIAGRAM. - |
| | EXTRA FD SHOWN @ COL LINE 7 BETWEEN |
| | COLS. O & N. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 9B. SHT P2.20 3"PD(68SF) & 3"PD(92SF) |
| | ARE NOT SHOWN ON ANY RISER DIAGRAM. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 10B. SHTS P2.22, P2.23, P2.24 INDICATES |
| | "TYPICAL FLOOR". PLEASE INDICATE WHAT |
| | ITS TYPICAL OF. SECTION 106.1.1. |
| | |
| | 11B. SHTS P2.22 & P2.23 MATCH LINE DOES |
| | NOT MATCH FLOOR PLAN AT COL. LINE "N". |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 12B. SHTS P2.23 & P2.24 MATCH LINE DOES |
| | NOT MATCH FLOOR PLAN AT COL. LINE "22". |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 13B. SHTS P2.22 & P2.25 RISER |
| | DESIGNATION FOR S/46 COVERED UP BY RISER |
| | RWL/12 DESIGNATION. PLEASE INDICATE |
| | CLEARLY RISER DESIGNATION S/46. SECTION |
| | 106.1.1. |
| | |
| | 14B. SHT P2.26 WATER LINE FROM M/B TO |
| | KITCHEN IN UNIT 'A 5.2' NOT ON PLANS. |
| | SECTION 106.1.1. |
| | |
| | 15B. SHT P2.31 2 VTR'S IN EGRESS |
| | STAIRWELL ARE NOT APPROVED. NFPA 101 |
| | SECTION 7.1.3.2.1(6). |
| | |
| | 16B. SHTS P2.31, P2.32, P2.33 PLEASE |
| | IDENTIFY ROOF DRAINS WITH A NUMBER |
| | DESIGNATION THAT CORRELATES WITH A RWL |
| | DESIGNATION. (EXAMPLE RD-1 WITH RWL-1) |
| | |
| | 17B. SHT P2.33 NO SF SHOWN FOR AREA NEXT |
| | TO 6"RD(1560SF). |
| | |
| | 18B. SHT P3.01 RECHECK ADDITION OF DFU'S |
| | AS THEY ACCUMULATE IN THE SANT. SYSTEM. |
| | TABLE 710.1(1). |
| | |
| | 19B. P3.01 LINE TO (A)(47FU), WHERE IS |
| | THE CONTINUATION TO THIS LINE. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 20B. SHT P3.01 TOILET ROOM ISOMETRIC, |
| | PLEASE INDICATE WHICH RISER THE SANT. |
| | BRANCH LINE CONNECTS TO. SECTION |
| | 106.1.1. |
| | |
| | 21B. SHT P3.01 AAV FOR 2" STACK TO SINK |
| | NOT APPROVED. SECTION 917.3. |
| | |
| | 22B. SHTS P3.03 & P3.04 CHECK RED LINE |
| | CORRECTION FOR FIXTURE UNITS AT EACH |
| | STACK INCICATED. FLOOR DRAINS OVER 2", |
| | FIXTURE UNITS PER TABLE 709.2. |
| | |
| | 23B. P3.05 FUTURE WATER SUPPLY SHOWN AS |
| | KEY NOTE #1, (6" WATER SERVICE) & SUB |
| | METERS ARE SHOWN AS #2 (BACKFLOWS). |
| | PLEASE CORRELATE KEY NOTES AND FLOOR |
| | PLAN. SECTION 106.1.1. |
| | |
| | 24B. SHT P3.06 2 W/4 RISERS SHOWN, 2 |
| | W/11 RISERS SHOWN, 2 W/8 RISERS SHOWN & |
| | 2 W/28 RISERS SHOWN. PLEASE CORRELATE |
| | RISER DIAGRAM WITH FLOOR PLAN.. |
| | |
| | 25B. SHT P3.06 3/4" WATER SUPPLY TO |
| | URINAL IS CONNECTING TO 1/2" WATER |
| | SUPPLY. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 26B. SHTS P3.12, P3.13, P3.14, & P3.15 |
| | INDICATE RISER NUMBER FOR ALL "PAD" |
| | RISERS, AND 5TH FLOOR DECK DRAIN/PLANTER |
| | DRAIN RISERS TO BE ABLE TO TRACK RISERS |
| | FROM THE BUILDING DRAIN THRU TO THE |
| | DRAINS. SECTION 106.1.1. |
| | |
| | 27B. P3.12 CHECK ADDITION ON SF FOR SOME |
| | RISERS. ALSO RWL/2 SF AT ROOF DRAIN |
| | SHOWS (1866SF), BUT (1849SF) ON THE |
| | RISER DIAGRAM. PLEASE CORRELATE. SECTION |
| | 106.1.1. |
| | |
| | 28B. SHT P3.13 3" PAD (136SF) NOT |
| | INDICATED ON DECK PLAN. PLEASE |
| | CORRELATE. SECTION 106.1.1. |
| | |
| | 29B. SHT P3.14 6" REQUIRED AT SD |
| | (1657SF). TABLE 1106.3 |
| | |
| | 30B. SHT P3.14 RISER DOES NOT REFLECT |
| | THE FLOOR PLAN. PLEASE CORRELATE. |
| | SECTION 106.1.1. |
| | |
| | 31B. SHT P3.14 RISER SHOWS 2 2ND FLOORS |
| | AND 2 4TH FLOORS. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 32B. SHT P3.14 CHECK ADDITION OF STORM |
| | DRAIN PRIOR TO DRAINAGE WELL. TABLE |
| | 1106.3. |
| | |
| | 33B. SHT P3.15 PAD RISER DOES NOT |
| | REFLECT FLOOR PLAN AT THE MEZZ. LEVEL. |
| | PLEASE CORRELATE. SECTION 106.1.1. |
| | |
| | 34B. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR THE GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | B. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). (EACH SYSTEM). |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). (EACH |
| | SYSTEM). |
| | D. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. (EACH SYSTEM). |
| | E. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. (EACH SYSTEM). |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. (EACH |
| | SYSTEM). |
| | G. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. (FOR |
| | KITCHEN SYSTEM ONLY). |
| | |
| | 35B. THERE IS ONE SET OF "RED LINED" |
| | PLANS. PLEASE RETURN THIS SET AND |
| | COMMENT RESPONSES TO HELP EXPEDITE THE |
| | NEXT PLAN REVIEW. |
| | |
| | REVIEW BY KEN STEVENS |