| Date |
Text |
| 2006-05-09 00:00:00 | DENIED: |
| | PLEASE NOTE, A RESPONSE LETTER TO |
| | COMMENTS GENERATED 12/27/05 WAS NOT |
| | SUBMITTED.PLEASE PROVIDE RESPONSE |
| | LETTER WITH THE NEXT RESUBMITTAL TO HELP |
| | EXPEDITE PLANS. |
| | |
| | THE FOLLOWING COMMENTS FROM REVIEW DATED |
| | 12/27/05 WERE NOT ADDRESSED: |
| | |
| | COMMENT #1:MECHANICAL PLANS ARE |
| | SIGNED, SEALED, AND DATED BY THE |
| | ENGINEER.THE ARCHITECT'S SEAL IS NOT |
| | LEGIBLE. |
| | |
| | COMMENT #2:OK |
| | |
| | COMMENT #3:OK |
| | |
| | COMMENT #4:SMOKE EXHAUST/CONTROL FOR |
| | THE RETAIL SPACE.PLAN SHEET M2.01, |
| | 2.02, & 2.03 ALL INDICATE FIRE SMOKE |
| | DAMPERS AND SUPPLY & RETURN DUCTS.PLAN |
| | SHEET M0.00 & M2.03 STATE "SMOKE EXHAUST |
| | THROUGH NATURAL VENTILATION" FROM |
| | WINDOWS AND PANELS OPERABLE FROM THE |
| | FIRE FLOOR OR PANELS OF APPROVED, FIXED, |
| | FULLY TEMPERED GLASS LOCATED AROUND THE |
| | PERIMETER.THIS IS NOT DEMONSTRATED. |
| | PLEASE CLARIFY.PLEASE SPECIFY WHAT |
| | "OAFR" & SXFR" STAND FOR.PLEASE NOTE, |
| | PLAN SHEET M2.01 "OAFR" DEPICTS SUPPLY |
| | GRILLES TO THE RETAIL SPACE & SXFR |
| | DEPICTS RETURN WITH BOTH RUNS TO RETAIL |
| | SPACE 3 THROUGH 7 TERMINATING INTO THE |
| | ENCLOSED PARKING GARAGE.PER 2004 FMC |
| | 401.5.1, INTAKE OPENINGS SHALL BE |
| | LOCATED A MINIMUM OF 10 FT FROM ANY |
| | HAZARDOUS OR NOXIOUS CONTAMINANT SUCH AS |
| | PARKING LOTS & LOADING DOCKS.PLEASE |
| | ALSO REFERENCE 2004 FMC 510.5.5, MAKEUP |
| | AIR SHALL BE LCOATED SO AS TO AVOID |
| | RECIRCULATION OF CONTAMINATED AIR. |
| | |
| | COMMENT #5:OK.PLEASE NOTE, |
| | MECHANICAL ROOMS USED AS RETURN AIR |
| | PLENUM, NO FLOOR DRAINS PERMITED IN |
| | MECHANICAL ROOMS PER 2004 FPC 901.2 & |
| | ASHRAE 62-01 8.4.1.11. |
| | |
| | COMMENT #6:OK |
| | |
| | COMMENT #7:WAS NOT ADDRESSED - PLAN |
| | SHEET M2.01 (ROOM #006 &011) FLEX DUCTS |
| | PENETRATING WALLS/PARTITIONS WITH FIRE |
| | RATING.FIRE DAMPERS ARE NOT INDICATED |
| | ON THE PLAN SHOW COMPLIANCE WITH 2004 |
| | FMC 607.5.3 #2 OR PROVIDE FIRE DAMPERS. |
| | LOCATION OF ALL FIRE DAMPERS ARE TO |
| | INDICATED ON PLANS 2004 FMC 607.8. |
| | |
| | COMMENT #8:INDICATE LOCATION OF ALL |
| | FIRE DAMPERS & ACCESS DOORS PER 2004 FMC |
| | 607.8. |
| | |
| | COMMENT #9:ADDRESSED ON PLAN SHEET |
| | M6.02. |
| | |
| | COMMENT #10: OK |
| | |
| | COMMENT #11: SUBMITTALS ON EQUIPMENT WAS |
| | NOT SUBMITTED. |
| | |
| | COMMENT #12: ENERGY CALCULATIONS WERE |
| | NOT SUBMITTED. |
| | |
| | COMMENT #13: SUBMITTAL ON THE GENERATOR |
| | WAS NOT SUBMITTED. |
| | **************************************** |
| | NEW COMMENTS: |
| | 14. PLAN SHEET M2.01, AIR MAKE-UP TO THE |
| | SMOKE CONTROL SYSTEM FOR THE RETAIL |
| | AREAS IS COMING FROM THE GARAGE.PER |
| | FMC 401.5.1 & 510.5.5, FRESH AIR INTAKES |
| | SHALL BE LOCATED A MINIMUM OF 10 FT FROM |
| | PARKING LOTS OR LOADING DOCKS AND AVOID |
| | THE RECIRCULATION OF OF CONTAMINTED AIR. |
| | PLEASE NOTE THE OAFR LOCATED IN RETAIL |
| | SPACE #7, INDICATES EXHAUST NOT INTAKE. |
| | |
| | 15. PLAN SHEET M2.03, PLEASE PROVIDE THE |
| | ELEVATION FOR THE MUFFLER & RADIATOR |
| | EXHAUST TERMINTION (BOTTOM OF PIPE & |
| | BOTTOM OF LOUVER).PLEASE NOTE, PER |
| | 2004 NFPA 37 6.3.5.4.2, EXHAUST |
| | VENTILATION SHALL BE TO A SAFE LOCATION |
| | OUTSIDE THE BUILDING, WITHOUT |
| | RECIRCULATION OF THE EXHAUST AIR. |
| | PLEASE NOTE, EXHAUST IS WITHIN 10 FT OF |
| | THE INTAKE LOUVER AND THE SWITCHGEAR |
| | ROOM DOOR. |
| | |
| | 16. PLAN SHEET M2.04, PLEASE CLARIFY THE |
| | RATING OF THE MECHANICAL CLOSET IN WHICH |
| | AHU-12 IS LOCATED. PLAN SHEET A1.3 DOES |
| | NOT SPECIFY RATING AT THE MEZZANINE |
| | LEVEL. |
| | |