Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop G
Sequence Number 2
Notes
Date Text
2006-08-07 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 FROM PLUMBING REVIEW:
  
 34B. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT THE GAS LINE TO
 THE POOL HEATER APPEARS TO BE RUN IN THE
 5TH FLOOR CEILING. WILL THE POOL HEATER
 BE LOCATED IN THE CEILING, OR WILL THERE
 BE A DROP TO THE HEATER. PLEASE CLARIFY.
  
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). (EACH SYSTEM).
 ****RESPONSE NOTED, BUT THE TABLE SHOWN
 IS FROM FBC-2001 FUEL GAS CODE. PLEASE
 DESIGN AND INDICATE TABLE FROM FBC-2004
 FUEL GAS CODE.
 C. OK
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. (EACH SYSTEM).
 ****NOT ADDRESSED.
  
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505. (EACH SYSTEM).
 ****NOT ADDRESSED.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. (EACH
 SYSTEM).
 ****NOT ADDRESSED. ITS UNDERSTOOD THE
 KITCHEN GAS EQUIPMENT WILL BE SUBMITTED
 AT KITCHEN BUILD-OUT, BUT THE POOL
 HEATER SPECIFICATIONS SHEETS WILL BE
 REQUIRED.
  
 G. AT KITCHEN BUILD-0UT.
  