| 2006-08-07 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | FROM PLUMBING REVIEW: |
| | |
| | 34B. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR THE GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ****RESPONSE NOTED, BUT THE GAS LINE TO |
| | THE POOL HEATER APPEARS TO BE RUN IN THE |
| | 5TH FLOOR CEILING. WILL THE POOL HEATER |
| | BE LOCATED IN THE CEILING, OR WILL THERE |
| | BE A DROP TO THE HEATER. PLEASE CLARIFY. |
| | |
| | B. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). (EACH SYSTEM). |
| | ****RESPONSE NOTED, BUT THE TABLE SHOWN |
| | IS FROM FBC-2001 FUEL GAS CODE. PLEASE |
| | DESIGN AND INDICATE TABLE FROM FBC-2004 |
| | FUEL GAS CODE. |
| | C. OK |
| | |
| | D. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. (EACH SYSTEM). |
| | ****NOT ADDRESSED. |
| | |
| | E. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. (EACH SYSTEM). |
| | ****NOT ADDRESSED. |
| | |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. (EACH |
| | SYSTEM). |
| | ****NOT ADDRESSED. ITS UNDERSTOOD THE |
| | KITCHEN GAS EQUIPMENT WILL BE SUBMITTED |
| | AT KITCHEN BUILD-OUT, BUT THE POOL |
| | HEATER SPECIFICATIONS SHEETS WILL BE |
| | REQUIRED. |
| | |
| | G. AT KITCHEN BUILD-0UT. |
| | |