Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-05-30 00:00:00***DENIED***
  
 PLEASE NOTE THAT WHEN RESUBMITTING
 PLANS, A RESPONSE LETTER INDICATING
 SHEET NUMBER WOULD HELP EXPEDITE THE
 PLAN REVIEW PROCESS. SOME REVISION
 CLOUDS ARE SHOWN, HOWEVER IT IS UNCLEAR
 WHAT THE CHANGE IS REFERENCING.
  
 PREVIOUS REVIEW COMMENTS:
  
 1) BUILDING SHALL MEET THE REQUIREMENTS
 FOR HIGHRISE IN ACCORDANCE WITH NFPA
 101, CHAPTER 11 AND APPLICABLE BUILDING
 CODES.
  
 2) PARKING GARAGES SHALL MEET THE
 SEPARATION AND ALL OTHER REQUIREMENTS OF
 NFPA 88A AND FBC.
  
 3) OK
  
 4) DO TRASH CHUTES OBSTRUCT CORRIDORS
 GREATER THAN 1/2 THE WIDTH?
  
 5) ILLUMINATED EXIT SIGNS TO BE MOUNTED
 AT DISTANCES NOT TO EXCEED 100' BETWEEN
 SIGNS.
  
 6) OK
  
 7) PLEASE PROVIDE QUANTITY AND TYPE OF
 STORAGE THAT WILL BE KEPT IN POOL
 EQUIPMENT ROOM.
  
 8) EXIT STAIRS TO BE KEPT UP WITH
 CONSTRUCTION.
  
 9) OK
  
 10) OK
  
 11) OK
  
 12) OK
  
 13) THE SQUARE FOOTAGE REQUIREMENT IS
 CALLED OUT ON PLANS. FIRE EXTINGUISHERS
 TO BE MOUNTED AT DISTANCES NOT TO EXCEED
 75' TRAVEL DISTANCE REQUIREMENT.
  
 14) OK
  
 15) WARNING SIGNS REQUIRED IN ELEVATOR
 LOBBIES.
  
 16) NO STORAGE PERMITTED IN ELECTRICAL
 AND MECHANICAL EQUIPMENT ROOMS.
  
 17) OK
  
 18) FIRE EXTINGUISHERS REQUIRED FOR EACH
 COMMERCIAL SPACE.
  
 19) PLANS INDICATE THAT ALL INTERIOR
 FINISH IS CLASS A. DOES THAT INCLUDE ALL
 SPACES IE, EXIT ENCLOSURES, LOBBIES AND
 CORRIDORS, AND OTHER SPACES?
  
 20) OK
  
 21) OK
  
 22) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 23) FIRE ALARM TO MEET SURVIVABILITY
 REQUIREMENTS OF NFPA 72.
  
 24) NOTE SHOULD READ: FIRE ALARM SYSTEM
 SHALL BE UL CERTIFIED FOR 'CENTRAL
 STATION SERVICE'.
  
 25) OK
  
 26) FIRE ALARM PLANS STILL DON'T SHOW
 SMOKE DETECTOR IN FIRE COMMAND ROOM.
  
 27) OK
  
 28) OK
  
 29) OK
  
 30) OK
  
 31) OK
  
 32) PLEASE ILLUSTRATE THE FIRE
 PROTECTION LAYOUT FOR THE TRASH CHUTES.
  
 33) SEPARATE SHOP DRAWINGS, PERMIT AND
 MANUFACTURER SPEC SHEETS REQUIRED FOR
 FIRE PUMP AND ASSOCIATED EQUIPMENT.
  
 34) OK
  
 35) OK
  
 36) OK
  
 NEW COMMENTS
  
 37) LIFE SAFETY TO COMPLY WITH NFPA 101,
 2003 EDITION
  
 38) PLEASE INDICATE FIRE RATING OF DOORS
 IN TERMS OF HOURS OR MINUTES.
  
 39) DUCT SMOKE DETECTORS SHALL INITIATE
 A GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS. SHT FA 1.13 NOTE 17.
  
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  