| 2006-05-30 00:00:00 | ***DENIED*** |
| | |
| | PLEASE NOTE THAT WHEN RESUBMITTING |
| | PLANS, A RESPONSE LETTER INDICATING |
| | SHEET NUMBER WOULD HELP EXPEDITE THE |
| | PLAN REVIEW PROCESS. SOME REVISION |
| | CLOUDS ARE SHOWN, HOWEVER IT IS UNCLEAR |
| | WHAT THE CHANGE IS REFERENCING. |
| | |
| | PREVIOUS REVIEW COMMENTS: |
| | |
| | 1) BUILDING SHALL MEET THE REQUIREMENTS |
| | FOR HIGHRISE IN ACCORDANCE WITH NFPA |
| | 101, CHAPTER 11 AND APPLICABLE BUILDING |
| | CODES. |
| | |
| | 2) PARKING GARAGES SHALL MEET THE |
| | SEPARATION AND ALL OTHER REQUIREMENTS OF |
| | NFPA 88A AND FBC. |
| | |
| | 3) OK |
| | |
| | 4) DO TRASH CHUTES OBSTRUCT CORRIDORS |
| | GREATER THAN 1/2 THE WIDTH? |
| | |
| | 5) ILLUMINATED EXIT SIGNS TO BE MOUNTED |
| | AT DISTANCES NOT TO EXCEED 100' BETWEEN |
| | SIGNS. |
| | |
| | 6) OK |
| | |
| | 7) PLEASE PROVIDE QUANTITY AND TYPE OF |
| | STORAGE THAT WILL BE KEPT IN POOL |
| | EQUIPMENT ROOM. |
| | |
| | 8) EXIT STAIRS TO BE KEPT UP WITH |
| | CONSTRUCTION. |
| | |
| | 9) OK |
| | |
| | 10) OK |
| | |
| | 11) OK |
| | |
| | 12) OK |
| | |
| | 13) THE SQUARE FOOTAGE REQUIREMENT IS |
| | CALLED OUT ON PLANS. FIRE EXTINGUISHERS |
| | TO BE MOUNTED AT DISTANCES NOT TO EXCEED |
| | 75' TRAVEL DISTANCE REQUIREMENT. |
| | |
| | 14) OK |
| | |
| | 15) WARNING SIGNS REQUIRED IN ELEVATOR |
| | LOBBIES. |
| | |
| | 16) NO STORAGE PERMITTED IN ELECTRICAL |
| | AND MECHANICAL EQUIPMENT ROOMS. |
| | |
| | 17) OK |
| | |
| | 18) FIRE EXTINGUISHERS REQUIRED FOR EACH |
| | COMMERCIAL SPACE. |
| | |
| | 19) PLANS INDICATE THAT ALL INTERIOR |
| | FINISH IS CLASS A. DOES THAT INCLUDE ALL |
| | SPACES IE, EXIT ENCLOSURES, LOBBIES AND |
| | CORRIDORS, AND OTHER SPACES? |
| | |
| | 20) OK |
| | |
| | 21) OK |
| | |
| | 22) SEPARATE SHOP DRAWINGS AND PERMITS |
| | REQUIRED FOR FIRE SPRINKLER AND FIRE |
| | ALARM SYSTEMS. |
| | |
| | 23) FIRE ALARM TO MEET SURVIVABILITY |
| | REQUIREMENTS OF NFPA 72. |
| | |
| | 24) NOTE SHOULD READ: FIRE ALARM SYSTEM |
| | SHALL BE UL CERTIFIED FOR 'CENTRAL |
| | STATION SERVICE'. |
| | |
| | 25) OK |
| | |
| | 26) FIRE ALARM PLANS STILL DON'T SHOW |
| | SMOKE DETECTOR IN FIRE COMMAND ROOM. |
| | |
| | 27) OK |
| | |
| | 28) OK |
| | |
| | 29) OK |
| | |
| | 30) OK |
| | |
| | 31) OK |
| | |
| | 32) PLEASE ILLUSTRATE THE FIRE |
| | PROTECTION LAYOUT FOR THE TRASH CHUTES. |
| | |
| | 33) SEPARATE SHOP DRAWINGS, PERMIT AND |
| | MANUFACTURER SPEC SHEETS REQUIRED FOR |
| | FIRE PUMP AND ASSOCIATED EQUIPMENT. |
| | |
| | 34) OK |
| | |
| | 35) OK |
| | |
| | 36) OK |
| | |
| | NEW COMMENTS |
| | |
| | 37) LIFE SAFETY TO COMPLY WITH NFPA 101, |
| | 2003 EDITION |
| | |
| | 38) PLEASE INDICATE FIRE RATING OF DOORS |
| | IN TERMS OF HOURS OR MINUTES. |
| | |
| | 39) DUCT SMOKE DETECTORS SHALL INITIATE |
| | A GENERAL FIRE ALARM IN ACCORDANCE WITH |
| | LOCAL REQUIREMENTS. SHT FA 1.13 NOTE 17. |
| | |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |