Date Text
2006-05-08 00:00:00REVIEW IN PROGRESS
 *********** UNSAT ************
  
 ** 2ND REVIEW, 1ST REVIEW UNDER PERMIT.
 PLEASE KNOW, WILL ALSO HAVE ONE FREE
 RESUB FOR NEXT REVIEW.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES WHICH NEED TO
 BE ADDRESSED.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW AND NEW
 NOTES ARE ADDED TO THE LOWER PORTION OF
 REVIEW COMMENTS.
  
 *** UNSAT ***
  
 CITY PALMS
 10-STORY CONDO
  
 1)NOTE: NOTE #1, NO, PLEASE SEE NEW NOTE
 PERTAINING TO THE NEW 2004 FBC AND
 CHAPTER 13.
  
 ** PREVIOUS REVIEW **
 PLEASE KNOW, PLANS WERE SUBMITTED FOR
 "PLAN REVIEW" ONLY AND WERE NOT
 SUBMITTED FOR PERMIT BEFORE THE CODE
 CHANGE OF OCT 1ST, 2005 TO THE NEW
 2004 FBC.
 PLEASE SEE THAT ANY CHANGES WILL BE
 NEEDED WHEN SUBMITTING FOR PERMIT.
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE: NOTE #3 OK, HOWEVER SEE NOTE
 WITH RESPECT TO 110.26 AND ELECTRICAL
 ROOMS AND SOME ELECTRICAL EQUIPMENT AND
 REQ'D CLEARENCE.
  
 4)NOTE: NOTE #4 OK
  
 5)NOTE: NOTE #5 NO, PLEASE KNOW, PLANS
 SHALL BE SPECIFIC TO THE CODE IN EFFECT
 AND THE DESIGN IN WHICH THE BUILDING IS
 BUILT.
 PLEASE REFERENCE THE FOLLOWING CODES, AS
 THESE CODES WERE NOT FOUND ON THE
 ARCHITECTURAL PLANS.
 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-110, 1999 NFPA-20.
  
 ** PREVIOUS NOTE **
 PLEASE BE SURE PLANS ARE SPECIFIC TO
 THE 2002 NEC WHICH IS CURRENTLY IN
 EFFECT.
 PLEASE KNOW: DEPENDING ON WHEN PLANS ARE
 SUBMITTED FOR PERMIT, A CODE CHANGE TO
 THE 2005 NEC SHOULD BE COMING ABOUT IN
 MID 2006.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: NOTE #7NO, PLEASE SEE SOME
 WERE SUBMITTED FOR GARAGE AND CORRIDORS,
 HOWEVER STAIRWAYS COULD NOT BE LOCATED.
 PLEASE ALSO KNOW, LEVELS UNDER EM POWER
 SHALL BE PROVIDED.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE COMPLETE "PHOTO-METRICS"
 FOR ALL CORRIDORS, STAIRWELLS AND EGRESS
 AREAS PER 2003 NFPA-101 7.8 AND 7.9.
 PLEASE SEE A MIN OF 10 FT CANDLES IS NOW
 REQUIRED FOR STAIR TOWERS UNDER NORMAL
 EGRESS CONDITIONS.
  
 8)NOTE: NOTE #8 OK, PLEASE SEE NEW
 COMMENTS FOR GEN RM.
  
 ** PREVIOUS NOTE **
 PLEASE BE SURE THERE ARE EMERGENCY
 BATTERY BACK UP TYPE FIXTURES LOCATED IN
 ALL ELECTRICAL ROOMS, ELEVATOR EQUIPMENT
 ROOMS, FIRE PUMP, GENERATOR, AND FIRE
 COMMAND ROOM.
 PLEASE KNOW, SOME OF THESE ARE ALREADY
 SHOWN ON PLANS, HOWEVER SOME AREAS MAY
 BE REDLINED FOR THESE.
 NFPA-101 7.8,7.9, NEC 700.16 ETC.
  
 8)NOTE: NOTE #8 ( # MISPRINT)NO, PLEASE
 SEE STAIRS INDICATE A BATTERY ABCK UP AT
 EVERY OTHER LEVEL WHICH IS OK. PLEASE
 SEE CORRIDORS AND GARAGES EGRESS PATHS
 ARE TO CONTAIN A MININUM OF SOME SORT OF
 BATTERY BACK UP TYPE FIXTURE TO PROVIDE
 A MINIMAL AMOUNT OF LIGHT TO ACCESS THE
 EGRESS TOWERS . LOCATIONS CAN BE GONE
 OVER IN A MEETING WHICH IS MOST CERTAIN
 FORTH COMING AFTER ALL REVIEWS ARE
 COMPLETED. PLEASE SEE COMMENT FOR
 FIXTURES AS THIS COMMENT MAY ALREADY BE
 ADDRESSED HOWEVER IS UNCLEAR DUE TO SOME
 FIXTURES SHOWN ON PLANS WHICH ARE NOT
 LISTED ON FIXTURES SCHEDULE.
  
 ** PREVIOUS NOTE **
 PLEASE SEE THAT EGRESS CORRIDORS, AND
 STAIR TOWERS WILL BE REQUIRED TO CONTAIN
 A MIN BATTERY BACK UP TYPE OF FIXTURE
 FOR EMERGENCY EGRESS OF 1 FT CANDLE.
 7.9 LS 101 THE TRIPPING OF A SINGLE
 SWITCH OR BREAKER SHALL NOT LEAVE ANY
 ONE AREA IN TOTAL DARKNESS.
  
 9)NOTE: NOTE #9 OK.
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE: NOTE #11 OK.
  
 12)NOTE:NOTE #12 NO, THIS NOTE COULD
 NOT BE LOCATED, ONLY A NOTE WITH
 REFERENCE TO POOL PERMIT.
 PLEASE PLACE NOTE ON PLANS FOR ALL MIN
 CLEARENCES 10' FOR 120V W/ GFI
 PROTECTION AND 5' FOR LV. 680.22,411.4.
  
 ** PREVIOUS NOTE **
 PLEASE NOTE ON PLANS THE MIN
 CLEARNECES FOR LT FIXTURES IN PROXIMITY
 OF POOL AND WATER FEATURES WATER'S EDGE.
 PLEASE SEE A MINOF 10' IS REQUIRED FOR
 FIXTURES OVER 30V.411.4
 PLEASE SEE 680.22 FOR A MIN OF 5' FROM
 WATER'S EDGE WITH EXCEPTIONS.
  
 13)NOTE: NOTE #13 OK.
  
 14)NOTE: NOTE #14 OK, REMOVED FROM
 PLANS. SEE NEW NOTES.
  
 15)NOTE: NOTE #17 OK. MOST ALL FLR
 SUBMITTED. PLEASE SEE HOWEVER THERE
 STILL APPEARS TO BE A MISSING SHEET FOR
 INTERMEDIATE ROOF LAYOUT EAST/ SOUTHEAST
 LAYOUT.
  
 16)NOTE: NOTE #16 NO, COULD NOT LOCATE
 ANY NOTES ON ANY OF THE ROOF TOP PLANS.
 NOTE MUST BE ON PLANS.
 PLEASE KNOW, THERE ARE MANY "SYSTEMS"
 ON THE MARKET BEING PROPOSED AND
 ADVERISED AS BEING ACCEPTABLE AND
 MEETING CODE ETC. PLEASE KNOW, ONLY
 SYSTEMS CONTAINING THE RECOGNIZED UL
 LISTINGS/CERTIFICATIONS WHICH ARE UNDER
 NFPA-780 WILL BE PERMITTED TO BE
 INSTALLED.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE NOTE ON ROOF-TOP
 PLANS WHICH WILL STATE THAT ANY
 LIGHTNING PROTECTION SYSTEMS MUST BE IN
 COMPLIANCE WITH NFPA-780. (OR WORDS TO
 THAT AFFECT).
  
 17)NOTE: NOTE #17 OK.
  
 18)NOTE: NOTE #18 NO, PLEASE SEE THERE
 ARE AREAS OF PLANS WHICH ARE STILL
 MISSING CIRCUITING AND SOME AREAS WHERE
 FIXTURES SEEM TO BE "LIGHT" ALTHOUGH AND
 CIRCUITING LINE IS SHOWN TO THESE
 FIXTURES.
 PLEASE SEE REDLINED PLANS.
  
 **PREVIOUS NOTE **
 PLEASE SEE NO CIRCUITING SHOWN FOR SOME
 "HOUSE AREAS". PLEASE SEE REDLINED PLANS
 ON 2.32, STORAGE RM ETC.
  
 19)NOTE: NOTE #19 NO, PLEASE SEE SOME
 ROOMS WHERE RECEPT CIRCUITS FEED MORE
 THAN ONE ROOM.
 PLEASE SEE REDLINED PLANS.
  
 ** PREVIOUS NOTE **
 PLEASE SEE 680.23 AND 680.24 WHICH
 REQUIRES "NO OTHER" LIGHTING OR RECEPTS
 ON ELEVATOR MACHINE RMS CIRUITS OR ELEV
 PITS. PLEASE SEE 2.34,2.35 AND ANY OTHER
 ARES WHICH MAY BE FED FROM ANY OF THESE
 CIRCUITS.
  
 20)NOTE: NOTE 320 OK, HOWEVER SEE SOME
 NEW NOTES FOR CIRCUITING NOW THAT
 CIRCUITS ARE SHOWN.
  
 ** PREVIOUS NOTE **
 PLEASE SHOW CIRCUITING FOR ALL UNITS AND
 CORRELATE WITH THE PANEL SCHEDULES
 SUBMITTED. PLEASE KNOW, CODE COMPLIANCE
 FOR SOME ITEMS CAN NOT BE DONE AT THIS
 TIME.
  
 21)NOTE: NOTE #21 NO/YES, PLEASE SEE
 MOST WERE ADDRESSED, HOWEVER PLEASE SEE
 NOW UNTI B2 INDICATES 60A OCP FOR 5KW
 UNIT.
 PLEASE ALSO CORRELATE ALL KW HEAT STRIPS
 WITH MECHANICAL PLANS AND ADJUST LOADS
 AS ALL UNITS ON "M" SHEETS ARE SHOWN W/
 5KW HEAT.
  
 ** PREVIOSU NOTE **
 PLEASE SEE 424.3B FOR MIN OCP FOR AHU'S
 AND HEAT.
 PLEASE SEE MANY PANEL SCHEDULES INDICATE
 LOADS AT 11KW ETC @65%?? PLEASE CLARIFY
 AS 11KW SI SHOWN AS THE DERATED LOAD.
 PLEASE SEE IF 11KW IS THE DE-REATED
 LOAD, THEN THE ACTUAL KW RATING FOR AHU
 WOULD BE ALMOST 15KW??
  
  
 22)NOTE: NOTE #22 OK.
  
 23)NOTE: NOTE #23 OK.
  
 24)NOTE: NOTE #24 OK,HOWEVER SEE NOTES.
  
 25)NOTE: NOTE #25 OK.
  
 26)NOTE: NOTE #26 NO, PLEASE SEE PLANS
 STILL MENTIONS TO USE 310.15B, HOWEVER
 PLEASE KNOW, "B6" CAN NOT BE SUED IN
 DERATING.
 PLEASE ALSO SEE NEW NOTE MENTIONS THE
 CONTRACTOR MAY SUBSTITUTE W/ ALUM.
 PLEASE KNOW, THE CONTRACTOR MAY NOT MAKE
 THIS DECISION OR REVISION. PLEASE KNOW
 ONLY THE DESIGNER AND ENGINEER OF RECORD
 CAN MAKE ANY CHANGES TO CONDUCTORS WHICH
 MUST BE PROPOSED IN A REVISION, SIGNED
 DATED, SEALED AND SUBMITTED FOR REVIEW
 BEFORE CHANGES CAN BE MADE ON THE
 JOBSITE.
  
 ** PREVIOUS NOTE **
 PLEASE SEE NOTE #8, ON PANEL SCHEDULE
 NOTES. PLEASE SEE 310.15B6, WHICH DOES
 NOTES INLCUDE 120/208V SYSTEMS.THIS IS
 FOR INFORMATION ONLY.
  
 27)NOTE: NOTE #27 OK.
  
 28)NOTE: NOTE #28 OK.
  
 29)NOTE: NOTE #29 OK, HOWEVER SEE NOTES
 FOR 210.52/210.52C1 REDLINED
  
 ** PREVIOUS NOTE **
 PLEASE SEE UNIT A-8 FOR MISSING RECEPT
 PER 210.52. PLEASE BE SURE TO CHECK
 REDLINED PLANS FOR ANY OTHER POSSIBLE
 LOCATIONS WHICH MAY REQUIRE A RECEPT.
  
 30)NOTE: NOTE #30 OK.
  
 31)NOTE: NOTE #31 OK.
  
 32)NOTE: NOTE #32 OK.
  
 33)NOTE: NOTE #33 OK, HOWEVER SEE NEW
 NOTES FOR CORRELATION OF NOTES AND
 RISER.
  
 34)NOTE: NOTE #34 OK, HOWEVER SEE NEW
 NOTES DUE TO CHANGES IN RISER/PLANS.
  
 ** PREVIOUS NOTE **
 PLEASE SEE COMPLETE RISER DIAGRAM WITH
 LABELING OF FEEDERS FOR FEEDER SCHEDULE
 AND CORRELATING ALL NUMERCICAL
 IDENTIFICATION.
  
 35)NOTE: NOTE #35 OK.
  
 36)NOTE: NOTE #36 NO, NO SUBMITTIALS
 WERE SUBMITTED FOR REVIEW. PLEAS EKNOW,
 SPECS FOR THESE ITEMS MUST BE SUBMITTED
 TO REVIEW FOR CODE COMPLIANCE. PLEASE
 SEE THERE ARE MANY ITEMS IN NFPA-20
 CHAPTER 6 AND NFPA-110 WHICH CAN NOT BE
 VERIFIED AT THIS TIME AND FURTHER
 COMMENTS MAY ARISE AS CODE COMPLIANCE
 CAN NOT BE DONE AT THIS TIME.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT ALL INFORMATION
 FOR FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE ALSO PROVIDE MANUFACTURES
 SPECS/CUT SHEETS FOR ABOVE.
  
 37)NOTE: NOTE #37 NO, PLEASE SEE NO
 SPECS WERE SUBMITTED. PLEASE ALSO SEE
 RISER INDICATES THE 4-POLE ATS, HOWEVER
 NOTES MENITON THIS IS NOT A SEPARATELY
 DERIVED GENERATOR? PLEASE SEE AS A
 4-POLE ATS, THE GEN IS "SEP DERIVED" AND
 GROUNDING SHALL BE DONE ACCORDINGLY.
 PLEASE SEE MISSING BONDING AT FIRST
 MENAS OF DISCONNECT , EQUIPMENT GROUNDD
 ETC. PLEASE SEE NFPA-110 6.2.15*. PLEASE
 VERIFY WITH MANUFACTURE OF EQUIPMENT.
 PLEASE SEE NEW NOTES FOR ATS AND MAIN.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT ALL INFORMATION
 FOR GENERATOR/ ATS. PLEASE SUBMIT THE
 SPECS/CUT FROM MANUFACTURE.
 PLEASE VERIFY OF THE ATS WILL BE A
 4-POLE SWITCH.
 PLEASE SEE 700.7D AND IF YOU HAVE THE
 HANDBOOK, SEE EXPLANATION OF ARTICLE.
 I HAVE ATTACHED BOTH, JUST IN CASE.
  
 (D) GROUND FAULT. TO INDICATE A GROUND
 FAULT IN SOLIDLY GROUNDED WYE
 EMERGENCY SYSTEMS OF MORE THAN 150 VOLTS
 TO GROUND AND CIRCUIT-PROTECTIVE
 DEVICES RATED 1000 AMPERES OR MORE. THE
 SENSOR FOR THE GROUND-FAULT SIGNAL
 DEVICES SHALL BE LOCATED AT, OR AHEAD
 OF, THE MAIN SYSTEM DISCONNECTING
 MEANS FOR THE EMERGENCY SOURCE, AND THE
 MAXIMUM SETTING OF THE SIGNAL
 DEVICES SHALL BE FOR A GROUND-FAULT
 CURRENT OF 1200 AMPERES. INSTRUCTIONS
 ON THE COURSE OF ACTION TO BE TAKEN IN
 EVENT OF INDICATED GROUND FAULT
 SHALL BE LOCATED AT OR NEAR THE SENSOR
 LOCATION.
  
 ALTHOUGH 700.26 INDICATES THAT
 GROUND-FAULT PROTECTION OF EQUIPMENT IS
 NOT
 REQUIRED ON THE ALTERNATE SOURCE FOR
 EMERGENCY SYSTEMS, GROUND FAULTS CAN
 OCCUR ON SUCH SYSTEMS, AND THEY CAN
 RESULT IN EQUIPMENT BURNDOWN. BECAUSE
 OF THE EMERGENCY NATURE OF SUCH SYSTEMS,
 AUTOMATIC DISCONNECT IN THE EVENT
 OF A GROUND FAULT IS INAPPROPRIATE.
 DETECTION OF SUCH A FAULT, HOWEVER, IS
 DESIRABLE SO THAT THE CONDITION CAN BE
 CORRECTED.
 IN MY READING AND THE INFORMATION FROM A
 COULE OF MANUFACURES OF ATS SWITCHES, A
 4-POLE ATS IS REQUIRED. PLEASE RESERCH
 THE INFORMATION AND ADJUST.
  
 38)NOTE: NOTE #38, OK.P
  
 39)NOTE: NOTE #39 YES/ NO, PLEASE NOW
 SEE TWO SETS OF DRAWING KEYNOTES, WHICH
 AS NOTED IN ONE SET MOST DO NOT
 CORRELATE WITH RISER DIAGRAM. PLEASE SEE
 SOME COMMENTS FOR OTHER.
  
 ** PREVIOUS NOTE **
 PLEASE COMPLETE DRAWING KEYNOTES TO
 CORRELATE WITH PLANS.
  
 40)NOTE:NOTE #40 OK, PLEASE SEE SEC'S
 ARE NOW SHOWN AS UNDER GROUND. SEE NEW
 NOTES FOR ROOM LAYOUT.
  
 **PREVIOUS NOTE **PLEASE VERIFY RISER
 DIAGRAM SEC'S AND CONDUITS FOR FIRE
 PUMP, RISER APPEARS TO SHOW FEED
 OVERHEAD?
 PLEASE SEE NFPA-20, 70 WHICH REQUIRES
 COMPLETE ENCASEMENT OF FEEDS.
  
 41)NOTE: NOTE #41 OK, PLEASE SEE MORE
 INFORMATION ON PLANS WAS COMPLETED AND
 SUBMITTED FOR REVIEW, PLEASE SEE ANY NEW
 COMMENTS FOR REVIEW.
  
 ** PREVIOUS NOTE **
 PLEASE COMPLETE ALL PANELS, WITH
 INFORMATION ON PANELS, SIZE, MLO,
 MCB ETC.
 PLEASE COMPLETE LOAD CALCULATIONS FOR
 REVIEW.
  
 42)NOTE: NOTE #42 ?? NO?, PLEASE SEE
 PLANS NOTE WIND LOAD PRESSURES TO MEET
 140 MPH, HOWEVER IT IS NOT KNOWN WHERE
 THESE ARE FOR REVIEW.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE WIND LOAD
 CALCUALTIONS FOR BLDG REVIEW OF ANY SITE
 LIGHTING/ROOF TOP LT POLES.
  
 **************************************
 *************************************
 ********* NEW NOTES *****************
  
  
 43) NOTE: PLEASE KNOW, A FULL AND
 COMPLETE TYPE WRITTEN RESPONSE FROM THE
 DESIGN TEAM WHICH RESPONSES TO THE PLANS
 REVIEWERS COMMENTS WILL HELP IN
 EXPEDITING THE PLAN REVIEW PROCESS. THIS
 NUMERICAL REPONSE WILL HELP TO
 ALLEAVIATE ANY BACK AND FORTH QUESTIONS
 OR CONFUSION.
 NO, RESPONSE LETTERS WERE SUBMITTED WHEN
 PLANS WERE BROUGHT BACK FOR REVIEW.
  
 44) NOTE: PLEASE SEE ALL PLANS, SHEETS,
 DOCUMENTS BEING SIGNED, DATED OR SEALED
 BY A LICENSED PE, SHALL ONLY CONTAIN A
 SEAL WITH THE WORDING OF "LICENSE".
 PLEASE SEE A RULING BY THE FLORIDA BOARD
 OF PROFESSINAL ENGINEERS DATED IN
 FEBUARY "04", RULED IN 61G15-23.001,
 THAT ALL SEALS SHALL NO LONGER USE
 "CERTIFICATE" IN SAID SEAL. PLEAS KNOW,
 AN EXTENSION WAS GIVEN TO THE DATE OF
 DEC. 31ST , 2005.PLEASE SEE THIS IS
 NOT A COMMENT FOR STEVEN FELLER AS SEAL
 IS CORRECT. PLEASE SEE OTHER DOCUMENTS
 SUBMITTED DO CONTAIN THE SEAL WHICH IS
 NO LONGER ACCEPTABLE.
 PLEASE SEE DE LOS REYES ENG.AND ANY
 OTHERS WHICH MAY STILL BE UTILIZING OLD
 SEAL.
 PLEASE KNOW, THIS COMMENT IS MADE FOR
 ALL PLANS AND DOCUMENTS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 45) NOTE: PLEASE SEE FBC 2004 CHAPTER
 13, 13-415.1.ABC.1.1, &.2, &.3.
 PLEASE SHOW AND PROVIDE DEVICES,
 CONTROLS ETC FOR ALL AREAS NOW REQUIRED
 TO CONTAIN ENERGY CONSERVATION MEASURES.
 PLEASE SEE 13-413.1ABC.1 AND PROVIDE
 NOTES/WORST CASE FOR VOLTAGE DROP.
 PLEASE SEE 13-415.1.ABC.2 FOR AREA
 LIGHTING.
 PLEASE SEE THESE CHANGES ARE COMPLETELY
 DIFFERENT FORM THE 2001 FBC.
 THESE CHANGES BECAME FEDERALLY MANDATED
 FOR ALL STATES TO COMPLY IN THE NEXT
 CODE CYCLE/CHANGE. THIS FEDERAL MANDATE
 WAS PASSED JULY 2004
 PLEASE SEE NOTE #1 FROM PREVIOUS REVIE
 MENTIONED TO SEE ALL 2004 FBC FOR ALL
 CHANGES IN DESIGN AS PROJECT WAS NOT
 SUBMITTED FOR PERMIT UNDER THE 2001 FBC.
  
 46) NOTE: PLEASE SEE NFPA-110,7.3.3 FOR
 MIN LIGHTING LEVELS IN GENERATOR ROOM TO
 BE 30FT CANDLES. PLEASE SEE
 PHOTO-METRICS FOR THIS AREA SHOULD BE
 SHOWN.
  
 47) NOTE:
 A) PLEASE SEE NFPA-110, 7.9.3.1,
 GALVANIZED LINES SHALL NOT BE USED FOR
 PIPNG TO GENERATOR. THIS IS NOTED FOR
 PLUMBING/ ENGINEERING AS SOME LOCATIONS
 IN THE JURISDICTION HAS INSTALLED THESE
 AND HAVE HAD TO CHANGE TYPES OF PIPING.
 PLEASE KNOW THIS IS A NOTE AT THIS TIME
 FOR INFORMATIONAL PURPOSE ONLY.
 B) PLEASE ALSO SEE NFPA-20, NFPA-110 ,
 NOTES AND SPECS FOR FUEL TYPE AND
 STORAGE WAS NOTE SUBMITTED, PLEASE SEE
 MIN RUNNING TIME CAN NOT BE VERIFIED.
 PLEASE SEE 6-6.2 FOR A MIN OF 8 HRS
 @100% ALONG WITH ALL OTHER MIN REQUIRED
 LIFE SAFETY LOADS.
 THE AMOUNT OF FUEL, AND GPH SHOULD BE
 NOTED ON PLANS. ONE OF THE DRAWING KEY
 NOTES MENTIONS 500 GAL TANK?TBD.
  
 48) NOTE: PLEASE SEE THERE ARE FIXTURES
 ON PLANS WHICH ARE NOTE ON FIXTURE
 SCHEDULE? R-1, R-2, W-1,,
  
 49) NOTE: PLEASE SEE SOME FIXTURES ON
 PLANS DO NOT CONTAIN FIXTURE
 DESIGNATIONS.
 "REDLINED ON PLANS"
  
 50) NOTE: PLEASE SEE LAYOUT ON MEZZ LVEL
 FOR DOM PUMP RM AND FIRE PUMP RM. PLEASE
 SEE THESE SEEM TO BE MISSING
 WALLS/SEPARATION FROM GARAGE/RAMP
 AREAS.? 2.05
 215.5
  
 51) NOTE:PLEASE INDICATE IF GHB
 CONTAINS "FEED-THRU LUGS" OR DOES THIS
 PANEL CONTAIN OCP TO FEED "GHB2"?
 215.5
  
 52) NOTE: PLEASE SEE "LA", DOES THIS
 PANEL ALSO CONTAIN "FEED-THRU LUGS" OR
 DOES IT CONTAIN OCP TO FEED"LA2"?
 IF SO, PLEASE INDICATE THE OCP AND AWG
 SIZES.
 215.5
  
 53) NOTE: PLEASE SEE CORRELATION FOR
 "KEYNOTES" AS RISER CONTAINS #11,10,
 12,13 ETC WHICH DO NOT MATCH AS NOTED
 ABOVE.
  
 54) NOTE: PLEASE SEE PANELS "HB", LB",
 AND TRANSFORMER, AS LAYOUT DOES NOT SEEM
 TO MEET 110.26
 4.01
  
 55) NOTE: PLEASE SEE PREVIOUS NOTE WITH
 RESPECT TO THE ATS AND 4-POLE,
 SEPARATELY DERIVED SYSTEM.
 PLEASE SEE 250.6,250.24B AND 250.122 FOR
 SIZING ANY EQUIPMENT GORUNDING
 CONDUCTORS.
  
 56) NOTE: PLEASE SEE DINING AREAS IN
 A4A, A5, C1 WHICH SHOW RECEPT ON LIVING
 RM CIRCUIT.
 210.52B1
 PLEASE VERIFY ALL DINING AREAS AS SHOWN
 AS IDENTIFY AS NEEDED FOR AREA
 DESIGNATIONS. MOST ARE OK.
 SEE REDLINED.
  
 57) NOTE: PLEASE SEE AREA IN UNIT "B3"
 WHICH SEEMS TO SHOW COUNTERSPACE AND
 WALL AREA ?
 PLEASE SEE 210.52 IF WALL , AND 210.52C1
 IF COUNTER SPACE. (GFI)210.8A6
  
 58) NOTE: PLEASE SEE LOAD SUMMARY FOR
 FIRE PUMP ON RISER WHICH CONTAINS AN "*"
 ASTERISK FOR NOTE OF MAGNETIC ONLY 6X
 LR, HOWEVER THIS "*" IS NOT ABOVE FOR
 FIRE PUMP. SEE REDLINES THIS IS NOTED AS
 PLANS ARE COMING BACK FOR COMMENTS.
  
 59) NOTE: PLEASE SEE EM MAIN SHOLD NOT
 BE LOCATED DIRECTLY NEXT TO EXISTING
 MAIN DISTRIBTUTION EQUIPMENT. THIS MAY
 BE IN THE SAME ROOM, HOWEVER SHOULD BE
 LOCATED ON THE OTHER SIDE OF ROOM.
 PLEASE SEE IF THE ATS IS 4-POLE AND
 SERVICE ENTRANCE RATED, THE MSBE WOULD
 NOT BE NEEDED, THE EDPH COULD CONTAIN A
 MCB AND WOULD MEET THE NEC.
 PLEASE KNOW, IN EITHER CASE A MEANS OF
 DISCONNECT ON THE LOAD OR LINE SIDE OF
 ATS FOR FEED COMING FROM GENERARATOR
 WOULD BE NEEDED GROUPED IN CLOSE
 PROXIMITY TO THE ATS, EM MAIN. PLEASE
 CALL TO GO OVER. SOME ITEMS ARE NOT
 KNOWN AT THIS TIME.
  
 60) NOTE: PLEASE SEE RISER AND OTHER
 PANELS INDICATE PANELS "HP AND LP" ,
 HOWEVER NEITHER OF THESE ARE SUBMITTED
 TO VERIFY AT THIS TIME. PLEASE SHOW.
 215.5
  
 61) NOTE: PLEASE PROVIDE ELEVATION FOR
 EPSS. PLEASE SEENFPA-110 7.2.3*,THE
 ELEVATION OF THE EPSS SHALL BE 6" ABOVE
 THE "SLOSH" PREDICATION LEVELS.
 "SEA, LAKE, OVERLAND SURGES BY
 HURRICANCES. CHARTS BASED ON SURGES FROM
 A CAT 4 STORM.
  
 62) NOTE: WHEN AND BEFORE RESUBMITTING
 PLANS, PLEASE COMPLETELY REMOVE ANY AND
 ALL OLD/VOIDED SHEETS FROM SETS. PLEASE
 ONLY INSERT ONLY NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STMAPING.
 PLEASE KNOW, THIS WAS DONE ON THIS
 SUBMITTAL.
  
 ** PLEASE SEE LOCATIONS ON PLANS IN
 WHICH MANY OF THE ABOVE ITEMS HAVE BEEN
 REDLINED AT LOCATIONS OF COMMENTS.
  
 ** PLEASE BE AWARE OF ANY COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT COMPLETED PLANS FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 **
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
2006-05-04 00:00:00ROLLS OF MEP IN ELEC FOR REVIEW TO
 COMMENCE.