| 2006-04-14 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05091265 |
| | ADD: 430 HIBISCUS |
| | CONT:PROJECT |
| | TEL: (561)586-2913 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | ARCHITECT: COHEN, FREEDMAN, ENCINOSA |
| | & ASSOC. STUART COHEN/ GULLERMO ENCINOSA |
| | 8085 N. W. 155 ST |
| | MIAMI, FL |
| | T(305)826-4155 |
| | |
| | STRUCTURAL: DE LOS REYESENGINEERING, INC |
| | 8726 S. W. 26 TH STREET SUITE 1&2 |
| | HECTOR DE LOS REYES |
| | MIAMI, FL |
| | T(305)477-8826 |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) COMMENT# 21 FROM THE PREVIOUS REVIEW, |
| | A0.4 MEZZANINE LEVEL PROVIE THE |
| | SQUARE FOOT OF EACH COMMERCIAL TEANANT |
| | FOR THE FIRST FLOOR LEVEL AS WELL AS THE |
| | MEZZANINE LEVEL. 505.2 AREA LIMITATION. |
| | THE AGGREGATE AREA OF A MEZZANINE OR |
| | MEZZANINES WITHIN A ROOM SHALL NOT |
| | EXCEED ONE-THIRD OF THE AREA OF THAT |
| | ROOM OR SPACE IN WHICH THEY ARE LOCATED. |
| | THE ENCLOSED PORTIONS OF ROOMS SHALL NOT |
| | BE INCLUDED IN A DETERMINATION OF THE |
| | SIZE OF THE ROOM IN WHICH THE MEZZANINE |
| | IS LOCATED. IN DETERMINING THE ALLOWABLE |
| | MEZZANINE AREA, THE AREA OF THE |
| | MEZZANINE SHALL NOT BE INCLUDED IN THE |
| | AREA OF THE ROOM. |
| | 1A) REVIEW THE SQ FT FOR FIRST FLOOR AND |
| | TOTAL FOR COMMERCIAL #1 & #2. |
| | 1B) COMMERCIAL UNIT# 8 PLEASE |
| | RECALCULATE THE MEZZANINE LEVEL IT |
| | APPEARS TO BE OVER THE 1/3RD BY 20 SQ |
| | FT. |
| | NOTE!!!!!! 110.2* (F) THIS WILL BE A |
| | BUILDING SITULATION THAT MUST APPEAR ON |
| | THE C.O.!!!!!!!!!!!!! |
| | FBC 505.2 COMMERCIAL BUILDOUTS, NO WALLS |
| | CAN BE ADDED BENEATH THE MEZZANINE |
| | LEVEL.THE AGGREGATE AREA OF A MEZZANINE |
| | OR MEZZANINES WITHIN A ROOM SHALL NOT |
| | EXCEED ONE-THIRD OF THE AREA OF THAT |
| | ROOM OR SPACE IN WHICH THEY ARE LOCATED. |
| | THE ENCLOSED PORTIONS OF ROOMS SHALL NOT |
| | BE INCLUDED IN A DETERMINATION OF THE |
| | SIZE OF THE ROOM IN WHICH THE MEZZANINE |
| | IS LOCATED. |
| | |
| | 2) COMMENET# 22B) FROM THE PREVIOUS |
| | REVIEW, DOOR 14 & 36 BOTH ARE OVERHEAD |
| | DOORS ON THE REFUSE ROOMS. 707.1.13.4 |
| | DOORS TO BE 3/4 HR AND SELF CLOSING OR |
| | AUTOMATICALLY TO CLOSE IF SMOKE IS |
| | DETECTED. HOW OR WHAT TYPE OF DEVICE |
| | WILL ACCOMPLISH THIS ACTION? PROVIDE |
| | SPEC SHEETS. |
| | |
| | 3) COMMENT# 28D) THE HEALTH CLUB NOW |
| | INDICATES THE USE OF HEAVY TIMBER AND 1 |
| | 1/2 WOOD DECKING, TABLE 601 FORA TYPE |
| | 1A CONSTRUCTION FOR ROOF CONSTRUCTION |
| | INCLUDING SUPPORTING BEAMS AND JOIST |
| | REQUIRE A 1 1/2 HR FIRE RESISTANCE |
| | RATING. FOOTNOTE "C"(2)(III)TYPE "1" |
| | OVER 2 STORIES DOES ALLOW FRT WOOD IF A |
| | 20' CLEAR FROM THE UPPER FLOOR TO THE |
| | ROOFIS ALLOWED AS IN THE PENTHOUSE |
| | UNITS. THIS CASSE THERE IS N'T 20'-0" |
| | CLEAR.ALSO SEE 602.2 TYPE I & II. |
| | |
| | 4) COMMENT# 31 FROM THE PREVIOUS REVIEW, |
| | |
| | 31) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 5) COMMENT# 32 FROM THE PREVIOUS REVIEW |
| | 32)W P B ADMINISTRTIVE CODE 106.3.3* |
| | PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 6) COMMENT# 33 FROM THE PREVIOUS REVIEW |
| | 33) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) EXTERIOR WINDOWS FIXED |
| | B) EXTERIOR WINDOWS OPERATABLE |
| | C) MULLIONS |
| | D) EXTERIOR GLAZED DOORS |
| | E) EXTERIOR ROLL UP DOORS |
| | F) LOUVERS |
| | G) TRUSS ANCHOR ATTACHMENTS |
| | H) STORM SHUTTERS |
| | I) EFIS SYSTEMS |
| | J) EXTERIOR RAILINGS |
| | K) ROOFING ASSEMBLIES FLAT AND SLOPED |
| | ALL OF THE ABOVE MENTIONED PRODUCTS |
| | WILL REQUIRE THE DESIGNER OF RECORD TO |
| | SIGN OFF THAT THE REPORTS HAVE BEEN |
| | REVIEWEDAND APROVED BY THEIR OFFICE. |
| | |
| | ---NEW COMMENTS--- |
| | |
| | 7)1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING |
| | ASSEMBLIES SEPARATING DWELLING UNITS |
| | FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND |
| | TRANSMISSION CLASS (STC) OF NOT LESS |
| | THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 90. PENETRATIONS |
| | OR OPENINGS IN CONSTRUCTION ASSEMBLIES |
| | FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| | CABINETS; BATHTUBS; SOFFITS; OR HEATING, |
| | VENTILATING OR EXHAUST DUCTS SHALL BE |
| | SEALED, LINED, INSULATED OR OTHERWISE |
| | TREATED TO MAINTAIN THE REQUIRED |
| | RATINGS. THIS REQUIREMENT SHALL NOT |
| | APPLY TO DWELLING UNIT ENTRANCE DOORS; |
| | HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | |
| | 8) 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING |
| | UNIT AND A PUBLIC OR SERVICE AREA WITHIN |
| | THE STRUCTURE SHALL HAVE AN IMPACT |
| | INSULATION CLASS (IIC) RATING OF NOT |
| | LESS THAN 50 (45 IF FIELD TESTED) WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |