| 2007-10-16 09:17:18 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT P2.16 NOT ALL REVISIONS HAVE BEEN CLOUDED, NOR |
| | DO ALL REVISIONS HAVE A REVISION NUMBER ATTACHED. |
| | PLEASE INDICATE ALL CHANGES/REVISIONS WITH A CLOUD AND |
| | A REVISION NUMBER. -- THE STORM LINE INDICATED BY KEY |
| | NOTE NUMBER 17 HAS BEEN DELETED, BUT THE KEY NOTE IS |
| | STILL SHOWN ON THE PLANS WHERE THE STORM LINE WAS |
| | LOCATED. PLEASE CLARIFY. SECTION 106.1.1.**NOTE: THE |
| | REVISION TURN AROUND TIME IS GREATLY INCREASED BECAUSE |
| | OF THE FACT THAT PREVIOUS REVISION CLOUDS AND REVISION |
| | NUMBER ARE STILL SHOWN ON THE PLANS. I HAVE ASKED |
| | REPEATEDLY FOR ALL REVISIONS THAT HAVE BEEN PREVIOUSLY |
| | APPROVED TO BE TURNED OFF. PLEASE COMPLY OR EXPLAIN WHY |
| | THIS CAN NOT BE DONE. |
| | |
| | 2. SHT P2.19THE 4" ED, (1180SF). PLEASE IDENTIFY |
| | WHICH ROOF DRAINS WILL ADD UP TO 1180SF.--THE 6" |
| | ED, (1730SF). PLEASE IDENTIFY WHICH ROOF DRAINS WILL |
| | ADD UP TO 1730SF.--6" ED, (3240SF). PLEASE IDENTIFY |
| | WHICH ROOF DRAINS WILL ADD UP TO 3240SF.--4"ED, |
| | (1300SF). PLEASE IDENTIFY WHICH ROOF DRAINS WILL ADD UP |
| | TO 1300SF.--IF EACH DECK DRAIN HAS TO BE NUMBERED, |
| | (DD-1, DD-2 ETC), AND THEN TIED TO A NUMBERED EMERGENCY |
| | DRAIN, (ED-1, ED-2 ETC) TO CLARIFY WHICH DECK DRAINS |
| | SQUARE FOOTAGE ADDS UP TO WHICH EMERGENCY DRAIN, THIS |
| | WOULD HELP IN SHOWING ALL SQUARE FOOTAGE OF THE DECK |
| | DRAINS IS ACCOUNTED FOR IN THE EMERGENCY DRAINS. -- KEY |
| | NOTES #10 STATES "SEE SHT P2.20 FOR CONTINUATION". SHT |
| | P2.20 DOES NOT SHOW THE CONTINUATION. PLEASE CLARIFY. |
| | SECTION 106.1.1.--AS INDICATED IN THE REVISION |
| | DENIAL DATED 07/07/07, SEE THE FOLLOWING COMMENTS STILL |
| | NOT ADDRESSED: |
| | ***2. SHT P2.19 A RELIEF VENT IS REQUIRED FOR THE AAV |
| | TO THE SINK AT THE POOL DECK LEVEL. SECTION 917.3.2. |
| | ALSO A REVISION WILL BE REQUIRED FOR THE SANITARY RISER |
| | DIAGRAM TO REFLECT THE CHANGE TO THE SANT. SYSTEM. |
| | SECTION 106.1.1.---KEY NOTES #12 THE OVERFLOW |
| | FROM THE COLLECTOR TANKS SHALL DRAIN TO STORM, NOT |
| | SANITARY.---REVISION #6 INDICATED AS COORD. REV. |
| | 01-17-07. PLANS WERE ISSUED WITH A REVISION #6 "BLDG |
| | DEPT COMM" 08-07-06. IN ORDER TO TRACK ALL REVISIONS, |
| | ONLY ONE REVISION PER REVISION NUMBER WILL BE ALLOWED. |
| | SECTION 106.1.3.**** |
| | |
| | 3. SHT P3.01 THE OVERFLOW FROM THE COLLECTOR TANKS FOR |
| | THE POOL AND SPA SHALL DRAIN TO STORM, NOT SANITARY AS |
| | SHOWN. |
| | |
| | 4. SHT P3.12 PD 310SF IS NOT SHOWN ON THE RISER DIAGRAM |
| | FOR THAT AREA. (DP/3). PLEASE INDICATE WHAT RISER THE |
| | PD CONNECTS TO. SECTION 106.1.2.--RISER DIAGRAM |
| | DOES NOT REFLECT THE FLOOR PLAN FOR DP/4 WHERE THE |
| | TRENCH DRAINS CONNECT TO THE BRANCH DRAIN. DD'S ON |
| | STRUCTURAL SLAB CONNECT DOWNSTREAM OF THE TRENCH DRAINS |
| | ON THE FLOOR PLAN.--2 DECK DRAINS INDICATED AS |
| | BEING ON THE STRUCTURAL SLAB, BUT ALL 3 DECK DRAINS ARE |
| | SHOWN ON THE SAME ELEVATION PER THE RISER DIAGRAM. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 5. 8-1/2" BY 11" REVISIONS SUBMITTED MIRROR THE |
| | REVISIONS SUBMITTED ON SHEETS P2.01, P3.01, |
| | P3.05,P2.16, P2.19 & P3.12 SO THESE ARE NOT REQUIRED. |
| | THE AMOUNT OF SPACE REQUIRED FOR THE STORAGE OF PLANS |
| | SUBMITTED FOR PUBLIC RECORD IS LIMITED AND DUPLICATE |
| | INFORMATION NOT REQUIRED WILL NOT BE APPROVED. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |