Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop P
Sequence Number 19
Notes
Date Text
2007-10-16 09:17:18DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P2.16 NOT ALL REVISIONS HAVE BEEN CLOUDED, NOR
 DO ALL REVISIONS HAVE A REVISION NUMBER ATTACHED.
 PLEASE INDICATE ALL CHANGES/REVISIONS WITH A CLOUD AND
 A REVISION NUMBER. -- THE STORM LINE INDICATED BY KEY
 NOTE NUMBER 17 HAS BEEN DELETED, BUT THE KEY NOTE IS
 STILL SHOWN ON THE PLANS WHERE THE STORM LINE WAS
 LOCATED. PLEASE CLARIFY. SECTION 106.1.1.**NOTE: THE
 REVISION TURN AROUND TIME IS GREATLY INCREASED BECAUSE
 OF THE FACT THAT PREVIOUS REVISION CLOUDS AND REVISION
 NUMBER ARE STILL SHOWN ON THE PLANS. I HAVE ASKED
 REPEATEDLY FOR ALL REVISIONS THAT HAVE BEEN PREVIOUSLY
 APPROVED TO BE TURNED OFF. PLEASE COMPLY OR EXPLAIN WHY
 THIS CAN NOT BE DONE.
  
 2. SHT P2.19THE 4" ED, (1180SF). PLEASE IDENTIFY
 WHICH ROOF DRAINS WILL ADD UP TO 1180SF.--THE 6"
 ED, (1730SF). PLEASE IDENTIFY WHICH ROOF DRAINS WILL
 ADD UP TO 1730SF.--6" ED, (3240SF). PLEASE IDENTIFY
 WHICH ROOF DRAINS WILL ADD UP TO 3240SF.--4"ED,
 (1300SF). PLEASE IDENTIFY WHICH ROOF DRAINS WILL ADD UP
 TO 1300SF.--IF EACH DECK DRAIN HAS TO BE NUMBERED,
 (DD-1, DD-2 ETC), AND THEN TIED TO A NUMBERED EMERGENCY
 DRAIN, (ED-1, ED-2 ETC) TO CLARIFY WHICH DECK DRAINS
 SQUARE FOOTAGE ADDS UP TO WHICH EMERGENCY DRAIN, THIS
 WOULD HELP IN SHOWING ALL SQUARE FOOTAGE OF THE DECK
 DRAINS IS ACCOUNTED FOR IN THE EMERGENCY DRAINS. -- KEY
 NOTES #10 STATES "SEE SHT P2.20 FOR CONTINUATION". SHT
 P2.20 DOES NOT SHOW THE CONTINUATION. PLEASE CLARIFY.
 SECTION 106.1.1.--AS INDICATED IN THE REVISION
 DENIAL DATED 07/07/07, SEE THE FOLLOWING COMMENTS STILL
 NOT ADDRESSED:
 ***2. SHT P2.19 A RELIEF VENT IS REQUIRED FOR THE AAV
 TO THE SINK AT THE POOL DECK LEVEL. SECTION 917.3.2.
 ALSO A REVISION WILL BE REQUIRED FOR THE SANITARY RISER
 DIAGRAM TO REFLECT THE CHANGE TO THE SANT. SYSTEM.
 SECTION 106.1.1.---KEY NOTES #12 THE OVERFLOW
 FROM THE COLLECTOR TANKS SHALL DRAIN TO STORM, NOT
 SANITARY.---REVISION #6 INDICATED AS COORD. REV.
 01-17-07. PLANS WERE ISSUED WITH A REVISION #6 "BLDG
 DEPT COMM" 08-07-06. IN ORDER TO TRACK ALL REVISIONS,
 ONLY ONE REVISION PER REVISION NUMBER WILL BE ALLOWED.
 SECTION 106.1.3.****
  
 3. SHT P3.01 THE OVERFLOW FROM THE COLLECTOR TANKS FOR
 THE POOL AND SPA SHALL DRAIN TO STORM, NOT SANITARY AS
 SHOWN.
  
 4. SHT P3.12 PD 310SF IS NOT SHOWN ON THE RISER DIAGRAM
 FOR THAT AREA. (DP/3). PLEASE INDICATE WHAT RISER THE
 PD CONNECTS TO. SECTION 106.1.2.--RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN FOR DP/4 WHERE THE
 TRENCH DRAINS CONNECT TO THE BRANCH DRAIN. DD'S ON
 STRUCTURAL SLAB CONNECT DOWNSTREAM OF THE TRENCH DRAINS
 ON THE FLOOR PLAN.--2 DECK DRAINS INDICATED AS
 BEING ON THE STRUCTURAL SLAB, BUT ALL 3 DECK DRAINS ARE
 SHOWN ON THE SAME ELEVATION PER THE RISER DIAGRAM.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 5. 8-1/2" BY 11" REVISIONS SUBMITTED MIRROR THE
 REVISIONS SUBMITTED ON SHEETS P2.01, P3.01,
 P3.05,P2.16, P2.19 & P3.12 SO THESE ARE NOT REQUIRED.
 THE AMOUNT OF SPACE REQUIRED FOR THE STORAGE OF PLANS
 SUBMITTED FOR PUBLIC RECORD IS LIMITED AND DUPLICATE
 INFORMATION NOT REQUIRED WILL NOT BE APPROVED.
  