Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop E
Sequence Number 19
Notes
Date Text
2008-06-16 14:00:12** DENIED / PASSED REVISIONS**
  
 1) NOTE: PLEASE SEE FEEDER F-8 IS SHOWN FROM GENERATOR
 TO FIRE PUMP WITH 250AMP OVER CURRENT PROTECTION.
 PLEASE SEE 250.122 AS THE EQUIPMENT GROUNDING CONDUCTOR
 IS REQUIRED TO BE SIZED FOR THE OCP>
 PLAN SHOWS #6 WHICH IS RATED FOR 200AMPS ONLY.
 THIS COULD HAVE BEEN REDLINED HOWEVER PLANS ARE FOR
 FINAL AS-BUILTS.
  
 2) NOTE: REVISED 6.01, 6.02, 6.03 OK, STAMPED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717