Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop E
Sequence Number 17
Notes
Date Text
2008-04-18 13:37:50** DENIEDREVIEW OF REVISIONS **
  
 THE FOLLOWING IS FOR ELECTRICAL REVISIONS SUBMITTED
 3/19/08 AND 4/7/08.
  
 1) NOTE: PLEASE COORDINATE ALL REVISIONS ALONG WITH
 REVISED TITLE BLOCKS AND REVISIONS ON PLANS.
 FOR EXAMPLE:
 PLEASE SEE SHEETS E0.01, E5.1 ETC WHICH ARE SIGNED,
 DATED AND SEALED ABOUT 3WEEKS APART YET THE PLANS ARE
 THE SAME. THESE SHEETS SHOW THE SAME EXACT REVISIONS.
 SHEET E0.01 DATED 3/17/08 ARE SHOWING REVISIONS 16 AND
 17 AND REVISED SHEET E0.01 DATED 4/3/08 SHOW THE SAME.
  
 THIS IS THE SAME FOR SOME OF THE OTHER SHEETS AS WELL.
 PLEASE GO THOUGH BOTH SETS, REVISE PLANS, TITLE BLOCKS
 AND SUBMIT COMPLETED SETS FOR REVIEW.
 ** PLEASE KNOW ANY OTHER REVIEW COMMENTS FOR FEEDERS
 ETC SHOULD BE INCORPORATED INTO CHANGES.
  
 2) NOTE: PLEASE SEE THIS REVIEWER'S PREVIOUS COMMENT
 WITH RESPECT TO GROUND FAULT PROTECTION ON MAINS AND
 OTHER EQUIPMENT WAS THAT THE EDPH WAS NOT TO CONTAIN
 GFP. NOW THE MSBE HAS THE GROUND FAULT PROTECTION
 REMOVE WHICH WAS LOCATED ON ORIGINAL PLANS.
 PLEASE SEE 240.13, 230.95 ETC WHICH DOES REQUIRE GFP ON
 THE MAIN. THE CODE DOES NOT REQUIRE GFP ON THE
 EQUIPMENT AFTER THE MAIN IN THIS SITUATION. THERE ARE
 SOME CIRCUMSTANCES IN THE CODE WHICH DOES REQUIRE GFP
 ON THE EQUIPMENT AFTER THE MAIN HOWEVER NOT ON THE
 EMERGENCY SIDE AND NOT IN THIS OCCUPANCY.
 PLEASE PLACE THE GFP BACK ON MSBE AND PLEASE BE SURE
 GFP IS NOT ON EDPH.
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE CONTACT THIS
 OFFICE.
  
 3) NOTE: PLEASE KNOW THE REVISED ENERGY CALCULATIONS
 SUBMITTED WERE NOT REVIEWED. THESE ARE CONSIDERED A
 REVISION AND WOULD BE SUBMITTED ACCORDINGLY.
 BASED ON THE FACT THAT THERE ARE CHANGES BEING MADE TO
 PLANS AND PROJECT THE REVISED CALCULATIONS SHOULD ONLY
 BE SUBMITTED FOR FINAL REVIEW ONCE *ALL* CHANGES TO
 PROJECT ARE KNOWN AND WILL BE THE FINAL REVISION BEFORE
 FINAL/CO.
 PLEASE CALL IF THERE ARE ANY QUESTIONS ON THIS.
 ** PLEASE ALSO KNOW THAT ANY REVISED ENERGY
 CALCULATIONS WILL ALSO BE REVIEWED BY MECHANICAL,
 BUILDING AND POSSIBLY PLUMBING. PLEASE BE SURE ALL
 PLANS FOR OTHER TRADES HAVE BEEN UPDATE TO THE POINT
 FOR FINAL REVIEW SO THE PLANS ON FILE WILL COORDINATE
 WITH CALCULATIONS.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717