| Plan Review Notes For Permit 05091265 |
| Permit Number |
05091265 |
|
| Review Stop |
P |
| Sequence Number |
16 |
|
| Notes |
| Date |
Text |
| 2007-09-13 14:33:12 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1. PRO-SLOPE SUBMITTAL DENIED. NO APPROVAL BY A | | | RECOGNIZED TESTING SHOWING COMPLIANCE WITH ALL CODES | | | FOR BUILDING MATERIALS.INDICATE REFERENCE STANDARD | | | PRODUCT BUILT TO AND SHOWAPPROVAL PER SECTIONS 303.2 | | | & 303.4. | | | | | | 2. SHOW COMPLIANCE WITH SECTION 417.5 REQUIREMENTS FOR | | | BEING IMPERVIOUS. IF THE PRO-SLOPE IS SHOWN TO COMPRESS | | | UNDER WEIGHT THIS WILL AFFECT THE REQUIREMENT. PLEASE | | | SHOW TESTING. | | | | | | 3. FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL | | | BE LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY | | | SOUND BASE. SECTION 417.5.1. PLEASE SUBMIT TESTING | | | SHOWING HOW THE ADVERTISED RATING OF 500LB PER SQUARE | | | FOOT WAS PROVEN. THE PRODUCT DOES NOT MEET THE INTENT | | | OF THE CODE THAT REQUIRES A UNIFORM SLOPE AT 1/4"/FT | | | BECAUSE NO TESTING HAS BEEN SHOWN TO INDICATE THAT THE | | | PRO-SLOPE WILL NOT COMPRESS AND LEAVE DIPS IN THE | | | PRODUCT AND ULTIMATELY CRACKING IN THE TILE. | | | | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|