Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop E
Sequence Number 15
Notes
Date Text
2007-09-22 18:53:16** DENIED REVISIONS **
  
  
 ** PLEASE SEE REVISIONS DATED THE SAME DATE OF 9/22/07
 WHICH NOTES WERE PROVIDED ON REVISIONS SUBMITTED ON
 8/23/07.
 PLEASE SEE SOME ITEMS BELOW FOR REVISIONS SUBMITTED
 9/20/07 NEED TO BE ADDRESSED.
  
 1) NOTE: PLEASE SEE THESE REVISIONS INDICATE A NEW 2500
 GALLON CON-VAULT YET NO PLANS OR SUBMITTALS COULD BE
 FOUND REVISING THESE ITEMS.
 PLEASE KNOW ANY MANUFACTURES SPECS/CUT SHEETS FOR FUEL
 TANK WILL BE REQUIRED TO BE REVIEWED BY FIRE AND
 MECHANICAL REVIEWERS.
 PLEASE ALSO KNOW REVISED PLANS FOR LOCATION ETC WILL
 NEED TO BE SUBMITTED.
  
 2) NOTE: THE NEW PLANS INDICATE THE GENERATOR WILL BE
 OPERATING AT A REDUCED LOAD FOR THE EXTENDED TIMES AS
 LISTED. THERE ARE SEVERAL ITEMS ON PANELS WHICH
 INDICATE A REDUCED LOAD HOWEVER NO DETAILS ON HOW THESE
 LOADS WILL BE SHED FROM THE PANEL(S) OR THE GENERATOR
 WAS SUBMITTED.
 HOW WILL LOADS BE TAKEN FROM THE PANELS?
 HOW WILL FANS, EXHAUST ETC BE SHED AND WILL THESE
 SYSTEMS FOR VENTILATION STILL BE OPERABLE IN THE EVENT
 OF LEVELS OF AIR GO INTO HIGH LEVELS ETC.
 PLEASE PROVIDE MORE INFORMATION ON SYSTEMS, WIRING,
 DETAILS, SHEDDING OF LOADS DOWN TO THE 255 AS NOTED
 ETC.
 FBC 106.1.2 ADMIN SECTION FOR INFORMATION NEEDED.
  
 3) NOTE: PLEASE SEE THE FEEDERS ON FEEDERS SCHEDULE FOR
 F-9 ARE NOT OF SUFFICIENT SIZE FOR THE 800AMP BREAKER
 AS SHOWN FROM GENERATOR.
 240.4, 310.16.
 PLEASE ALSO VERIFY THE NEW ALUM FEEDERS FOR F-8 WHICH
 IS ONLY RATED FOR 205AMPS PER 310.16 AND BREAKER OVER
 CURRENT PROTECTION IS 250AMPS.
  
 4) NOTE: PLEASE SEE THE EQUIPMENT GROUNDING CONDUCTOR
 AS SHOWN FOR THE FEEDERS FROM MSBE TO EDPH IS SHOWN AS
 2/0 ON RISER AND 1/0 ON MSBE SCHEDULE.
 PLEASE SEE THE 2/0 ON RISER IS OK, HOWEVER THE 1/0 IS
 NOT LARGE ENOUGH PER 250.122.
 PLEASE ADJUST.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  