| Date |
Text |
| 2007-09-22 17:36:30 | 2007-09-22 17:36:30 |
| | |
| | ** DENIED REVISIONS ** |
| | ** PASSED REVISIONS ** |
| | |
| | ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM PREVIOUS |
| | REVIEWS FOR REVISIONS WHICH STILL NEED TO BE |
| | ADDRESSED. |
| | ** PLEASE SEE THERE ARE ONLY SOME SHEETS FOR REVISIONS |
| | SUBMITTED 8/21 WHICH ARE OK AND WILL BE STAMPED FOR |
| | ELECTRICAL. THERE IS A LIST BELOW AT THE END OF REVIEW |
| | NOTES OF SHEETS BEING STAMPED AS OK. |
| | |
| | 1) NOTE: PLEASE SEE REVIEW COMMENTS OF 6/23/07 WHICH |
| | REQUESTED REVISED EGRESS PHOTO-METRICS AS THE LIGHTING |
| | ON PLANS HAD CHANGED. THE NOTES ON PLANS MENTIONS THE |
| | LIGHTING REVISIONS PER REVISED PHOTO-METRICS HOWEVER TO |
| | THE DATE NOT REVISED PHOTO-METRICS HAVE BEEN SUBMITTED |
| | INCLUDING THE LATEST REVISIONS SUBMITTED ON 9/20/07. LS |
| | 101, 708 AND 7.9 |
| | |
| | 2) NOTE: PLEASE SEE SHEET E-7.01 AS THIS MENTIONS |
| | REVISION(S) IN TITLE BLOCK HOWEVER NOT REVISED |
| | NUMERICAL DESIGNATION COULD BE LOCATED ON SHEET FOR |
| | THIS. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES DATED 6/26/07 |
| | WHICH MENTIONED THAT REVISED ENERGY CALCULATIONS AND |
| | INPUT DATA REPORT WILL BE REQUIRED FOR REVIEW OF ALL |
| | LIGHTING. |
| | PLEASE KNOW ANY REVISIONS TO ANY OTHER SYSTEMS WHICH |
| | WITH RESPECT TO THE ENERGY CALCULATIONS WILL ALSO BE |
| | REQUIRED TO BE REVISED. |
| | PLEASE KNOW THE INPUT DATA REPORT INFORMATION WILL BE |
| | REQUIRED TO COORDINATE WITH ALL ELECTRICAL AND OTHER |
| | SYSTEMS ON PLANS. |
| | FBC CHAPTER 13, 13-415.A.1 |
| | |
| | 4) NOTE: PLEASE SEE AS OF THIS REVIEW: NO PERMITS HAVE |
| | BEEN APPLIED FOR WITH RESPECT TO THE LOW VOLTAGE WORK |
| | AS SHOWN ON PLANS. |
| | SEPARATE PERMITS ARE REQUIRED FOR THE PHONE, CATV ETC. |
| | THESE PLANS MAY BE USED FOR REFERENCE AND A |
| | *TURN-AROUND* PERMIT HOWEVER APPLICATION AND FEES BASED |
| | ON THE SCOPE OF WORK FOR ALL LV SYSTEMS IS REQUIRED. |
| | PLEASE KNOW ANY SECURITY SYSTEMS (AKA ALARMS) ARE A |
| | SEPARATE PERMIT ALSO, HOWEVER NO PLANS ARE NEEDED FOR |
| | *ALARM SYSTEMS ONLY*. ANY CLOSED CIRCUIT TV, ACCESS |
| | CONTROLS ETC FOR OTHER TYPES OF SECURITY SYSTEMS DO |
| | REQUIRE PERMITS AND PLANS. NO SYSTEMS OF THIS NATURE |
| | ARE SHOWN ON PLANS. |
| | **PLEASE SEE SOME REVISED SHEETS IN SETS ARE BEING |
| | STAMPED OK, HOWEVER PERMITS NEED TO BE APPLIED FOR. IF |
| | PERMITS ARE NOT APPLIED, THEN ELECTRICAL PERMIT FOR |
| | BASE BUILDING MAY BE PLACED IN A HOLD STATUS FOR |
| | ELECTRICAL INSPECTIONS. |
| | INFORMATION WILL ALSO BE FORWARDED TO CHIEF ELECTRICAL |
| | INSPECTOR TO VERIFY PERMITS IN FIELD. |
| | |
| | 5) NOTE: PLEASE SEE SHEET E-206 AS SOME SWITCHES ARE |
| | SHOWN AS STANDARD SWITCH DEVICES WHEN AUTOMATED ARE |
| | REQUIRED. IS THE T NEXT TO BOTH SWITCHES IN ALL THREE |
| | STORAGE ROOMS FOR BOTH SWITCHES? |
| | 13-415.1.ABC.1.1, .1.2. |
| | |
| | 6) NOTE: PLEASE SEE REVISIONS SUBMITTED AS OF SEPTEMBER |
| | 20TH, 2007 WILL BE ENTERED UNDER THE NEXT REVISION #15 |
| | IN OUR SYSTEM. THIS REVISION AND REVIEW WILL BE DONE ON |
| | THE SAME DATE OF 9/22/07 AS THIS REVISION. |
| | THESE REVIEWS COMMENTS ARE UNDER *REV #14* IN OUR |
| | SYSTEM. |
| | |
| | 7) NOTE: PLEASE SEE SHEET E2.02 AS THERE ARE STILL EXIT |
| | LIGHTS WHICH WERE ADDED TO PLANS WITH NO CIRCUITING AND |
| | SHOWN DIRECTING OCCUPANTS INTO THE COMMERCIAL TENANT |
| | BUILD OUT SPACE WHICH IS NOT PERMITTED. |
| | THIS SHEET WILL NOT BE STAMPED PLEASE BE SURE TO |
| | COORDINATE WITH OTHER REVISIONS SUBMITTED SEPTEMBER |
| | 20TH, 2007. |
| | |
| | 8) NOTE: REDLINED EQUIPMENT GROUNDING FROM MSBE TO |
| | EDPH, AS THIS IS SHOWN AS 1/0 CU WHICH IS NOT RATED FOR |
| | THE 1000AMPS. REDLINED 2/0 MIN PER 250.122 |
| | THIS WILL BE NOTED AND FAILED IN REVSIONS SUBMITTED ON |
| | 9/20/07. REV #15 IN OUR SYSTEM. |
| | |
| | |
| | ** THE FOLLOWING SHEETS ARE STAMPED AND DO NOT NEED TO |
| | BE REVISED. SOME ARE SUBMITTED AS REVISIONS SUBMITTED |
| | 9/20/07. |
| | E0.01, 2.012.01A, 2.02A, 2.03, 2.03A, 2.20A, |
| | 2.31,2.32,2.33,6.01 AND 6.02 |
| | |
| | SHEETS E3.03, 3.04, 3.05, 3.06 AND 5.02 ARE OK, HOWEVER |
| | AS NOTED ABOVE IN NOTE #4 LV PERMITS ARE STILL |
| | REQUIRED. THESE SHEETS ARE BEING STAMPED ON THE NOTICE |
| | OF PERMITS TO BE APPLIED FOR AS NOTED ABOVE. |
| | |
| | ** SHEETS E- 2.02, 2.04, 2.05, 2.06, 2.17, 2.19, 2.20 |
| | AND 7.01 ARE NOT STAMPED PER NOTES ABOVE. |
| | |
| | *** IMPORTANT** |
| | ONCE FIRE REVIEW IS DONE AND OK, NEED TO KEEP ONE SET |
| | OF ELECTRICAL SHEETS WHICH ARE STAMPED AS OK, NEED TO |
| | BE KEPT FOR FILE COPY. |
| | PLEASE DO NOT RELEASE ALL THREE SETS OF ELECTRICAL ** |
| | PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET SUBMITTED |
| | FOR REVIEW AND THE CHANGES WHICH WILL BE NEEDED FOR |
| | SERVICE A COMPLETE REVIEW CAN NOT BE DONE AT THIS |
| | TIME. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-09-22 14:21:45 | 2007-09-22 14:21:45 |
| | |
| | IN ELEC FOR REVIEW |