Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop E
Sequence Number 14
Notes
Date Text
2007-09-22 17:36:302007-09-22 17:36:30
  
 ** DENIED REVISIONS **
 ** PASSED REVISIONS **
  
 ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM PREVIOUS
 REVIEWS FOR REVISIONS WHICH STILL NEED TO BE
 ADDRESSED.
 ** PLEASE SEE THERE ARE ONLY SOME SHEETS FOR REVISIONS
 SUBMITTED 8/21 WHICH ARE OK AND WILL BE STAMPED FOR
 ELECTRICAL. THERE IS A LIST BELOW AT THE END OF REVIEW
 NOTES OF SHEETS BEING STAMPED AS OK.
  
 1) NOTE: PLEASE SEE REVIEW COMMENTS OF 6/23/07 WHICH
 REQUESTED REVISED EGRESS PHOTO-METRICS AS THE LIGHTING
 ON PLANS HAD CHANGED. THE NOTES ON PLANS MENTIONS THE
 LIGHTING REVISIONS PER REVISED PHOTO-METRICS HOWEVER TO
 THE DATE NOT REVISED PHOTO-METRICS HAVE BEEN SUBMITTED
 INCLUDING THE LATEST REVISIONS SUBMITTED ON 9/20/07. LS
 101, 708 AND 7.9
  
 2) NOTE: PLEASE SEE SHEET E-7.01 AS THIS MENTIONS
 REVISION(S) IN TITLE BLOCK HOWEVER NOT REVISED
 NUMERICAL DESIGNATION COULD BE LOCATED ON SHEET FOR
 THIS.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES DATED 6/26/07
 WHICH MENTIONED THAT REVISED ENERGY CALCULATIONS AND
 INPUT DATA REPORT WILL BE REQUIRED FOR REVIEW OF ALL
 LIGHTING.
 PLEASE KNOW ANY REVISIONS TO ANY OTHER SYSTEMS WHICH
 WITH RESPECT TO THE ENERGY CALCULATIONS WILL ALSO BE
 REQUIRED TO BE REVISED.
 PLEASE KNOW THE INPUT DATA REPORT INFORMATION WILL BE
 REQUIRED TO COORDINATE WITH ALL ELECTRICAL AND OTHER
 SYSTEMS ON PLANS.
 FBC CHAPTER 13, 13-415.A.1
  
 4) NOTE: PLEASE SEE AS OF THIS REVIEW: NO PERMITS HAVE
 BEEN APPLIED FOR WITH RESPECT TO THE LOW VOLTAGE WORK
 AS SHOWN ON PLANS.
 SEPARATE PERMITS ARE REQUIRED FOR THE PHONE, CATV ETC.
 THESE PLANS MAY BE USED FOR REFERENCE AND A
 *TURN-AROUND* PERMIT HOWEVER APPLICATION AND FEES BASED
 ON THE SCOPE OF WORK FOR ALL LV SYSTEMS IS REQUIRED.
 PLEASE KNOW ANY SECURITY SYSTEMS (AKA ALARMS) ARE A
 SEPARATE PERMIT ALSO, HOWEVER NO PLANS ARE NEEDED FOR
 *ALARM SYSTEMS ONLY*. ANY CLOSED CIRCUIT TV, ACCESS
 CONTROLS ETC FOR OTHER TYPES OF SECURITY SYSTEMS DO
 REQUIRE PERMITS AND PLANS. NO SYSTEMS OF THIS NATURE
 ARE SHOWN ON PLANS.
 **PLEASE SEE SOME REVISED SHEETS IN SETS ARE BEING
 STAMPED OK, HOWEVER PERMITS NEED TO BE APPLIED FOR. IF
 PERMITS ARE NOT APPLIED, THEN ELECTRICAL PERMIT FOR
 BASE BUILDING MAY BE PLACED IN A HOLD STATUS FOR
 ELECTRICAL INSPECTIONS.
 INFORMATION WILL ALSO BE FORWARDED TO CHIEF ELECTRICAL
 INSPECTOR TO VERIFY PERMITS IN FIELD.
  
 5) NOTE: PLEASE SEE SHEET E-206 AS SOME SWITCHES ARE
 SHOWN AS STANDARD SWITCH DEVICES WHEN AUTOMATED ARE
 REQUIRED. IS THE T NEXT TO BOTH SWITCHES IN ALL THREE
 STORAGE ROOMS FOR BOTH SWITCHES?
 13-415.1.ABC.1.1, .1.2.
  
 6) NOTE: PLEASE SEE REVISIONS SUBMITTED AS OF SEPTEMBER
 20TH, 2007 WILL BE ENTERED UNDER THE NEXT REVISION #15
 IN OUR SYSTEM. THIS REVISION AND REVIEW WILL BE DONE ON
 THE SAME DATE OF 9/22/07 AS THIS REVISION.
 THESE REVIEWS COMMENTS ARE UNDER *REV #14* IN OUR
 SYSTEM.
  
 7) NOTE: PLEASE SEE SHEET E2.02 AS THERE ARE STILL EXIT
 LIGHTS WHICH WERE ADDED TO PLANS WITH NO CIRCUITING AND
 SHOWN DIRECTING OCCUPANTS INTO THE COMMERCIAL TENANT
 BUILD OUT SPACE WHICH IS NOT PERMITTED.
 THIS SHEET WILL NOT BE STAMPED PLEASE BE SURE TO
 COORDINATE WITH OTHER REVISIONS SUBMITTED SEPTEMBER
 20TH, 2007.
  
 8) NOTE: REDLINED EQUIPMENT GROUNDING FROM MSBE TO
 EDPH, AS THIS IS SHOWN AS 1/0 CU WHICH IS NOT RATED FOR
 THE 1000AMPS. REDLINED 2/0 MIN PER 250.122
 THIS WILL BE NOTED AND FAILED IN REVSIONS SUBMITTED ON
 9/20/07. REV #15 IN OUR SYSTEM.
  
  
 ** THE FOLLOWING SHEETS ARE STAMPED AND DO NOT NEED TO
 BE REVISED. SOME ARE SUBMITTED AS REVISIONS SUBMITTED
 9/20/07.
 E0.01, 2.012.01A, 2.02A, 2.03, 2.03A, 2.20A,
 2.31,2.32,2.33,6.01 AND 6.02
  
 SHEETS E3.03, 3.04, 3.05, 3.06 AND 5.02 ARE OK, HOWEVER
 AS NOTED ABOVE IN NOTE #4 LV PERMITS ARE STILL
 REQUIRED. THESE SHEETS ARE BEING STAMPED ON THE NOTICE
 OF PERMITS TO BE APPLIED FOR AS NOTED ABOVE.
  
 ** SHEETS E- 2.02, 2.04, 2.05, 2.06, 2.17, 2.19, 2.20
 AND 7.01 ARE NOT STAMPED PER NOTES ABOVE.
  
 *** IMPORTANT**
 ONCE FIRE REVIEW IS DONE AND OK, NEED TO KEEP ONE SET
 OF ELECTRICAL SHEETS WHICH ARE STAMPED AS OK, NEED TO
 BE KEPT FOR FILE COPY.
 PLEASE DO NOT RELEASE ALL THREE SETS OF ELECTRICAL **
 PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET SUBMITTED
 FOR REVIEW AND THE CHANGES WHICH WILL BE NEEDED FOR
 SERVICE A COMPLETE REVIEW CAN NOT BE DONE AT THIS
 TIME.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]