Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop P
Sequence Number 12
Notes
Date Text
2007-07-07 16:14:18REVISIONDENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P2.17 INDICATES REVISION #6 "OWNER REQ.
 REVISION" DATED 4-25-07. PLANS WERE ISSUED WITH A
 REVISION #6 "BLDG DEPT COMM" DATED 8-07-06. IN ORDER TO
 TRACK ALL REVISIONS, ONLY ONE REVISION PER REVISION
 NUMBER WILL BE ALLOWED. SECTION 106.1.3.--(NOTE THE
 REVIEW TIME IS INCREASED GREATLY WHEN ALL PREVIOUS
 APPROVED REVISION CLOUDS & REVISION TRIANGLE NUMBERS
 ARE STILL SHOWN ON EACH REVISION. ALSO IF THE
 BACKGROUND INFORMATION SUCH AS WALLS, CORRIDORS, DOORS,
 FIXTURES ETC. COULD BE LIGHTENED AS WELL AS PREVIOUS
 PIPING AND WITH THE APPLIED REVISION IN BOLD THE
 REVISIONS CAN BE EXPEDITED QUICKER).
  
 2. SHT P2.19 A RELIEF VENT IS REQUIRED FOR THE AAV TO
 THE SINK AT THE POOL DECK LEVEL. SECTION 917.3.2. ALSO
 A REVISION WILL BE REQUIRED FOR THE SANITARY RISER
 DIAGRAM TO REFLECT THE CHANGE TO THE SANT. SYSTEM.
 SECTION 106.1.1.---KEY NOTES #12 THE OVERFLOW
 FROM THE COLLECTOR TANKS SHALL DRAIN TO STORM, NOT
 SANITARY.---REVISION #8 IS SHOWN ON THE FLOOR
 PLAN, BUT NOT INDICATED ON THE REVISION INDEX. PLEASE
 CLARIFY. SECTION 106.1.3.---REVISION #6 INDICATED
 AS COORD. REV. 01-17-07. PLANS WERE ISSUED WITH A
 REVISION #6 "BLDG DEPT COMM" 08-07-06. IN ORDER TO
 TRACK ALL REVISIONS, ONLY ONE REVISION PER REVISION
 NUMBER WILL BE ALLOWED. SECTION 106.1.3.---DECK
 DRAINS ARE ALSO IDENTIFIED AS FD. PLEASE CLARIFY AS
 FLOOR DRAINS ARE NOT APPROVED STORM DRAINS. SECTION
 106.1.1.--- THE EMERGENCY (SECONDARY) ROOF DRAINS
 HAVE BEEN REDUCED IN CAPACITY & ARE NOT SIZED TO DRAIN
 ALL SQUARE FOOTAGE OF ALL AREAS OF THE DECK. SECONDARY
 ROOF DRAINS ARE REQUIRED FOR ALL SECTIONS OF THE DECK,
 INCLUDING THE PATIO AREAS PER SECTION 1107.3. SHOW THE
 SIZE OF EACH SECONDARY ROOF DRAINAND INDICATE SQUARE
 FOOTAGE DRAINED BY EACH SECONDARY ROOF DRAIN.
  
 3. SHT P2.20 REVISION #6 "OWNER REQD. REV 4-27-07.
 PLANS WERE ISSUED WITH A REVISION #6 "BLDG DEPT COMM"
 DATED 8-07-06. IN ORDER TO TRACK ALL REVISIONS, ONLY
 ONE REVISION PER REVISION NUMBER WILL BE ALLOWED.
 SECTION 106.1.3.---DECK DRAINS ARE ALSO
 IDENTIFIED AS FD. PLEASE CLARIFY AS FLOOR DRAINS ARE
 NOT APPROVED STORM DRAINS. SECTION 106.1.1.--- THE
 EMERGENCY (SECONDARY) ROOF DRAINS HAVE BEEN REDUCED IN
 CAPACITY & ARE NOT SIZED TO DRAIN ALL SQUARE FOOTAGE OF
 ALL AREAS OF THE DECK. SECONDARY ROOF DRAINS ARE
 REQUIRED FOR ALL SECTIONS OF THE DECK, INCLUDING THE
 PATIO AREAS PER SECTION 1107.3. SHOW THE SIZE OF EACH
 SECONDARY ROOF DRAINAND INDICATE SQUARE FOOTAGE
 DRAINED BY EACH SECONDARY ROOF DRAIN.
  
 4. SHT P2.31 REVISION #1 HAS BEEN DELETED FROM THE
 REVISION INDEX. PLEASE CLARIFY.---REVISIONS #2
 HAS BEEN CHANGED TO REVISION #4 ON THE REVISION INDEX.
 PLEASE CLARIFY. REVISION NUMBERS SHALL REMAIN THE SAME
 THROUGHOUT THE LIFE OF THE PLANS IN ORDER TO BE ABLE TO
 TRACK ALL CHANGES TO THE STAMPED SET OF REVIEWED PLANS.
 SECTION 106.1.3.---REVISION #7 SHOWN ON THE ROOF
 PLAN, BUT NOT SHOWN ON THE REVISION INDEX. PLEASE
 CLARIFY.---KEY NOTES 4 & 5 ARE NOT CLOUDED OR
 INDICATED AS REVISIONS WITH A REVISION NUMBER. PLEASE
 CLOUD AND NUMBER ALL REVISIONS.---REVISION #6 &
 KEY NOTE #3 STATES CONDENSATE PIPING TO TURN DOWN TO
 FLOOR BELOW, BUT IS SHOWN TURNED DOWN ON THE ROOF.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 5. SHT P2.33A 3" VTR IS SHOWN UNDER RTU-5. THIS WILL
 NEED TO BE OFFSET 10' PAST AIR INTAKE. SECTION 904.5.
 ---VTR OFFSET & CONDENSATE LINE FROM RTU-5 IS NOT
 CLOUDED NOR INDICATED AS A REVISIONS WITH A REVISION
 NUMBER. PLEASE CLARIFY. ---REVISION #2 HAS BEEN
 DELETED FROM THE REVISION PLEASE CLAIFY.--- REVISION
 #2 HAS BEEN CHANGED TO REVISION #3 AT COL. LINE 23/I-G.
 ---REVISION #3 HAS BEEN CHANGED TO REVISION #4 AT
 COL. LINE 22/I.---REVISION #4 HAS BEEN CHANGED TO
 REVISION #5 AT COL. LINE 23/G-D.-TO TRACK REVISIONS
 AND TO KEEP PUBLIC RECORDS, THE REVISION NUMBERS SHALL
 STAY THE SAME THROUGH THE LIFE OF THE JOB/PLANS.
 SECTION 106.1.3.
  
 6. SHT P3.12 RISER DP/4 THE SHOWER DECK DRAIN IS NOT
 SHOWN, THE SQUARE FOOTAGE FOR TWO DECK DRAINS DOES NOT
 REFLECT THE FLOOR PLAN, AND THE PIPING TO DECK DRAIN
 (140SF) DOES NOT REFLECT THE FLOOR PLAN NOR DOES THE
 BRANCH PIPING AT THE OFFSET UPSTREAM OF SAID DD.---
 DOWNSTREAM OF THE BASE OF RISER DP/5 DECREASES TO 4"
 FROM 6" RISER. THIS IS NOT APPROVED. SECTION 704.2.
  
 7. SHT P3.14 DETAIL 2 (EMERGENCY DRAINS) IS NOT
 APPROVED. THE SECONDARY ROOF SYSTEM DRAINS SHALL DRAIN
 THE TOTAL AREA EQUIVALENT TO THE AREA DRAINED GY THE
 TOTAL OF ALL PRIMARY ROOF DRAINS. SECTION 1107.3.
  
 REVIEW BY KEN STEVENS