| 2007-07-07 16:14:18 | REVISIONDENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT P2.17 INDICATES REVISION #6 "OWNER REQ. |
| | REVISION" DATED 4-25-07. PLANS WERE ISSUED WITH A |
| | REVISION #6 "BLDG DEPT COMM" DATED 8-07-06. IN ORDER TO |
| | TRACK ALL REVISIONS, ONLY ONE REVISION PER REVISION |
| | NUMBER WILL BE ALLOWED. SECTION 106.1.3.--(NOTE THE |
| | REVIEW TIME IS INCREASED GREATLY WHEN ALL PREVIOUS |
| | APPROVED REVISION CLOUDS & REVISION TRIANGLE NUMBERS |
| | ARE STILL SHOWN ON EACH REVISION. ALSO IF THE |
| | BACKGROUND INFORMATION SUCH AS WALLS, CORRIDORS, DOORS, |
| | FIXTURES ETC. COULD BE LIGHTENED AS WELL AS PREVIOUS |
| | PIPING AND WITH THE APPLIED REVISION IN BOLD THE |
| | REVISIONS CAN BE EXPEDITED QUICKER). |
| | |
| | 2. SHT P2.19 A RELIEF VENT IS REQUIRED FOR THE AAV TO |
| | THE SINK AT THE POOL DECK LEVEL. SECTION 917.3.2. ALSO |
| | A REVISION WILL BE REQUIRED FOR THE SANITARY RISER |
| | DIAGRAM TO REFLECT THE CHANGE TO THE SANT. SYSTEM. |
| | SECTION 106.1.1.---KEY NOTES #12 THE OVERFLOW |
| | FROM THE COLLECTOR TANKS SHALL DRAIN TO STORM, NOT |
| | SANITARY.---REVISION #8 IS SHOWN ON THE FLOOR |
| | PLAN, BUT NOT INDICATED ON THE REVISION INDEX. PLEASE |
| | CLARIFY. SECTION 106.1.3.---REVISION #6 INDICATED |
| | AS COORD. REV. 01-17-07. PLANS WERE ISSUED WITH A |
| | REVISION #6 "BLDG DEPT COMM" 08-07-06. IN ORDER TO |
| | TRACK ALL REVISIONS, ONLY ONE REVISION PER REVISION |
| | NUMBER WILL BE ALLOWED. SECTION 106.1.3.---DECK |
| | DRAINS ARE ALSO IDENTIFIED AS FD. PLEASE CLARIFY AS |
| | FLOOR DRAINS ARE NOT APPROVED STORM DRAINS. SECTION |
| | 106.1.1.--- THE EMERGENCY (SECONDARY) ROOF DRAINS |
| | HAVE BEEN REDUCED IN CAPACITY & ARE NOT SIZED TO DRAIN |
| | ALL SQUARE FOOTAGE OF ALL AREAS OF THE DECK. SECONDARY |
| | ROOF DRAINS ARE REQUIRED FOR ALL SECTIONS OF THE DECK, |
| | INCLUDING THE PATIO AREAS PER SECTION 1107.3. SHOW THE |
| | SIZE OF EACH SECONDARY ROOF DRAINAND INDICATE SQUARE |
| | FOOTAGE DRAINED BY EACH SECONDARY ROOF DRAIN. |
| | |
| | 3. SHT P2.20 REVISION #6 "OWNER REQD. REV 4-27-07. |
| | PLANS WERE ISSUED WITH A REVISION #6 "BLDG DEPT COMM" |
| | DATED 8-07-06. IN ORDER TO TRACK ALL REVISIONS, ONLY |
| | ONE REVISION PER REVISION NUMBER WILL BE ALLOWED. |
| | SECTION 106.1.3.---DECK DRAINS ARE ALSO |
| | IDENTIFIED AS FD. PLEASE CLARIFY AS FLOOR DRAINS ARE |
| | NOT APPROVED STORM DRAINS. SECTION 106.1.1.--- THE |
| | EMERGENCY (SECONDARY) ROOF DRAINS HAVE BEEN REDUCED IN |
| | CAPACITY & ARE NOT SIZED TO DRAIN ALL SQUARE FOOTAGE OF |
| | ALL AREAS OF THE DECK. SECONDARY ROOF DRAINS ARE |
| | REQUIRED FOR ALL SECTIONS OF THE DECK, INCLUDING THE |
| | PATIO AREAS PER SECTION 1107.3. SHOW THE SIZE OF EACH |
| | SECONDARY ROOF DRAINAND INDICATE SQUARE FOOTAGE |
| | DRAINED BY EACH SECONDARY ROOF DRAIN. |
| | |
| | 4. SHT P2.31 REVISION #1 HAS BEEN DELETED FROM THE |
| | REVISION INDEX. PLEASE CLARIFY.---REVISIONS #2 |
| | HAS BEEN CHANGED TO REVISION #4 ON THE REVISION INDEX. |
| | PLEASE CLARIFY. REVISION NUMBERS SHALL REMAIN THE SAME |
| | THROUGHOUT THE LIFE OF THE PLANS IN ORDER TO BE ABLE TO |
| | TRACK ALL CHANGES TO THE STAMPED SET OF REVIEWED PLANS. |
| | SECTION 106.1.3.---REVISION #7 SHOWN ON THE ROOF |
| | PLAN, BUT NOT SHOWN ON THE REVISION INDEX. PLEASE |
| | CLARIFY.---KEY NOTES 4 & 5 ARE NOT CLOUDED OR |
| | INDICATED AS REVISIONS WITH A REVISION NUMBER. PLEASE |
| | CLOUD AND NUMBER ALL REVISIONS.---REVISION #6 & |
| | KEY NOTE #3 STATES CONDENSATE PIPING TO TURN DOWN TO |
| | FLOOR BELOW, BUT IS SHOWN TURNED DOWN ON THE ROOF. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 5. SHT P2.33A 3" VTR IS SHOWN UNDER RTU-5. THIS WILL |
| | NEED TO BE OFFSET 10' PAST AIR INTAKE. SECTION 904.5. |
| | ---VTR OFFSET & CONDENSATE LINE FROM RTU-5 IS NOT |
| | CLOUDED NOR INDICATED AS A REVISIONS WITH A REVISION |
| | NUMBER. PLEASE CLARIFY. ---REVISION #2 HAS BEEN |
| | DELETED FROM THE REVISION PLEASE CLAIFY.--- REVISION |
| | #2 HAS BEEN CHANGED TO REVISION #3 AT COL. LINE 23/I-G. |
| | ---REVISION #3 HAS BEEN CHANGED TO REVISION #4 AT |
| | COL. LINE 22/I.---REVISION #4 HAS BEEN CHANGED TO |
| | REVISION #5 AT COL. LINE 23/G-D.-TO TRACK REVISIONS |
| | AND TO KEEP PUBLIC RECORDS, THE REVISION NUMBERS SHALL |
| | STAY THE SAME THROUGH THE LIFE OF THE JOB/PLANS. |
| | SECTION 106.1.3. |
| | |
| | 6. SHT P3.12 RISER DP/4 THE SHOWER DECK DRAIN IS NOT |
| | SHOWN, THE SQUARE FOOTAGE FOR TWO DECK DRAINS DOES NOT |
| | REFLECT THE FLOOR PLAN, AND THE PIPING TO DECK DRAIN |
| | (140SF) DOES NOT REFLECT THE FLOOR PLAN NOR DOES THE |
| | BRANCH PIPING AT THE OFFSET UPSTREAM OF SAID DD.--- |
| | DOWNSTREAM OF THE BASE OF RISER DP/5 DECREASES TO 4" |
| | FROM 6" RISER. THIS IS NOT APPROVED. SECTION 704.2. |
| | |
| | 7. SHT P3.14 DETAIL 2 (EMERGENCY DRAINS) IS NOT |
| | APPROVED. THE SECONDARY ROOF SYSTEM DRAINS SHALL DRAIN |
| | THE TOTAL AREA EQUIVALENT TO THE AREA DRAINED GY THE |
| | TOTAL OF ALL PRIMARY ROOF DRAINS. SECTION 1107.3. |
| | |
| | REVIEW BY KEN STEVENS |