| Date |
Text |
| 2007-12-18 09:19:33 | REVIEW #: REV.16 |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | PAGES RELATED TO OUTSTANDING REVIEW COMMENTS WHICH HAVE |
| | NOT BEEN ADDRESSED WILL NOT BE STAMPED UNTIL ALL |
| | OUTSTANDING ISSUES ARE ADDRESSED. PLEASE SEE REVIEW |
| | COMMENTS PUBLISHED ON 6/26/07 AND 10/21/07. |
| | |
| | 1 THROUGH 4: OK FROM PREVIOUS REVIEW. |
| | |
| | 5. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 6. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 7. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 8. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 9 THROUGH 11: OK FROM PREVIOUS REVIEW. |
| | |
| | 12. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 13. THE MAJORITY OF ISSUES RAISED IN PREVIOUS REVIEWS |
| | AS COMMENT #13 HAVE NOT BEEN ADDRESSED. THE NOTE ON |
| | M0.00, M2.01, M2.03 CLAIMING NATURAL VENTILATION FOR |
| | SMOKE CONTROL UNDER THE 2001 CODE HAS NOT BEEN REMOVED. |
| | SEE FBC 403.15 FOR REQUIREMENTS UNDER FBC 2004. THERE |
| | HAS BEEN NO RATIONAL ANALYSIS SUBMITTED FOR THE SMOKE |
| | CONTROL SYSTEM AS REQUIRED BY FBC 909.2, 909.4 AND FBC, |
| | M 513.4, 513.4. NO INFORMATION HAS BEEN PROVIDED |
| | REGARDING THE SUITABILITY OF AHU 12 AND RELATED SUPPLY |
| | DUCTWORK FOR USE AS PART OF THE SMOKE CONTROL SYSTEM |
| | (APPARENTLY) TO DELIVER MAKE-UP AIR. IT WAS REQUESTED |
| | IN PREVIOUS REVIEW TO SHOW THESE COMPONENTS TO BE IN |
| | COMPLIANCE WITH FBC, M 513.10.2 AND FBC 513.10.5. |
| | |
| | ALSO, IS MECHANICAL ROOM 051 TO BE USED AS A PLENUM FOR |
| | BOTH AIR CONDITIONING AND SMOKE CONTROL MODES? IN SMOKE |
| | CONTROL MODE, THIS ROOM APPEARS TO BE SERVING AS AN |
| | EXHAUST DUCT. THE SUITABILITY OF THIS ROOM FOR USE AS A |
| | PART OF THE SMOKE EXHAUST DUCT SYSTEM SHOULD BE PART OF |
| | THE RATIONAL ANALYSIS FOR THE FOLLOWING REASON: AMONG |
| | OTHER REQUIREMENTS, 513.10.2 REQUIRES EXHAUST DUCTS TO |
| | BE CONSTRUCTED IN ACCORDANCE WITH FBC, M CHAPTER 6. |
| | FBC, M 602.2 LIMITS THE USE OF GYPSUM PLENUMS TO |
| | SYSTEMS WHERE THE AIR TEMPERATURE DOES NOT EXCEED 125 |
| | DEGREES F. |
| | NOTE: THESE REQUIREMENTS APPLY TO ALL DUCT AND |
| | EQUIPMENT WHICH WILL BE USED AS PART OF THE SMOKE |
| | CONTROL SYSTEM, SUCH AS AHUS 13 AND 14. |
| | |
| | IN ADDITION, THE DESIGN OF THE SUPPLY, RETURN AND |
| | EXHAUST DUCT AND DAMPER SYSTEMS RELATED TO SEF-5, |
| | SEF-7, AHU-13 AND AHU-14 IS UNCLEAR ON THE PLANS DUE TO |
| | THE AMOUNT OF INTERSECTING DUCTS, REFRIGERANT LINES AND |
| | WALLS WITHIN THIS SMALL AREA. PLEASE PROVIDE A CLEAR |
| | DEPICTION OF THIS AREA (PERHAPS A LARGER SCALE DETAIL |
| | OF THIS AREA) TO DISCERN THE DESIGN INTENT IN ORDER TO |
| | FACILITATE A COMPLETE REVIEW FOR COMPLIANCE WITH FBC, M |
| | 513. |
| | NOTE: SEVERAL DUCT PENETRATIONS OF RATED WALL AND |
| | FLOOR/CEILING ASSEMBLIES ARE SHOWN TO BE PROTECTED WITH |
| | FIRE DAMPERS. WHERE THE INSTALLATION OF A FIRE DAMPER |
| | WILL INTERFERE WITH THE OPERATION OF A REQUIRED SMOKE |
| | CONTROL SYSTEM IN ACCORDANCE WITH SECTION 513, APPROVED |
| | ALTERNATIVE PROTECTION SHALL BE UTILIZED IN ACCORDANCE |
| | WITH FBC, M 607.2.1. IN ADDITION TO FIRE PROTECTION, |
| | DUCTS AND AIR TRANSFER OPENINGS ARE REQUIRED TO BE |
| | PROTECTED WITH A MINIMUM CLASS II, 250DEGREE F SMOKE |
| | DAMPER COMPLYING WITH THE FLORIDA BUILDING CODE, |
| | BUILDING IN ACCORDANCE WITH FBC, M 513.2.1. |
| | |
| | FURTHERMORE, THE SMOKE CONTROL MAKE-UP AIR INTAKE AND |
| | EXHAUST OUTLET LOCATIONS ASSOCIATED WITH SEF-5 AND |
| | SEF-7 ARE NOT LOCATED SO AS TO MINIMIZE THE POTENTIAL |
| | FOR INTRODUCING SMOKE OR FLAME INTO THE BUILDING. |
| | EXHAUST OUTLETS SHALL BE SO LOCATED AS TO MINIMIZE |
| | REINTRODUCTION OF SMOKE INTO THE BUILDING IN ACCORDANCE |
| | WITH FBC, M 513.10.3. |
| | PLEASE ADDRESS ALL THESE ISSUES, WITH SUPPORTING |
| | DOCUMENTATION IF APPLICABLE, WHEN RESUBMITTING. |
| | |
| | 14. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 15. REGARDING SMOKE CONTROL AS SHOWN ON M2.02 AND |
| | M2.05, PLEASE SEE COMMENT 13 ABOVE AS ALL RELATED |
| | COMMENTS APPLY IN THESE AREAS. FBC, M SEC.513. |
| | |
| | 16 AND 17: OK |
| | |
| | 18. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 19. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 20. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | |
| | 21. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 22 AND 23: OK |
| | |
| | 24. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 25. OK |
| | |
| | 26. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 27. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | NOTE: THE CONDITIONS RELATED TO PREVIOUS COMMENT ALSO |
| | APPLY TO PG M2.16. |
| | |
| | 28. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 29 AND 30: OK |
| | |
| | 31. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 32. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 33. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 34. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 35. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | NOTE: SEE THE SUPPLY DUCT CROSSING THE CORRIDOR AT |
| | MEN?S AND WOMEN?S LOCKER ROOMS. |
| | |
| | 36. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 37. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 38. OK |
| | |
| | 39. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | NOTE: SEVERAL PAGES RELATED TO THIS COMMENT WERE NOT |
| | RESUBMITTED WITH THIS REVISION. |
| | |
| | 40. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | NOTE: THE PAGE RELATED TO THIS COMMENT WAS NOT |
| | RESUBMITTED WITH THIS REVISION. |
| | |
| | 41. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | NOTE: SEVERAL PAGES RELATED TO THIS COMMENT WERE NOT |
| | RESUBMITTED WITH THIS REVISION. |
| | |
| | 42 THROUGH 44: OK |
| | |
| | 45. NO PAGES RELATED TO THIS COMMENT WERE RESUBMITTED. |
| | IF THERE ARE NO CHANGES FROM THE PERMIT SET, |
| | RESUBMISSION IS NOT NECESSARY. |
| | |
| | 46. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | 47. OK EXCEPT, M4.01 RISER OAR-4 STILL HAS NO SIZE |
| | SHOWN FOR BRANCH OFFS ON MEZZANINE AND GROUND LEVELS. |
| | |
| | 48 AND 49: OK |
| | |
| | A: M2.01: BASED ON THE LATEST REVISED ARCHITECTURAL |
| | PLANS ON FILE IN THE PERMIT SET (REV.18 DATED 9-18-07), |
| | THE LOCATIONS OF FIRE DAMPERS SHOWN ON THIS PAGE STILL |
| | DO NOT CORRESPOND WITH THE LOCATIONS OF RATED WALLS. |
| | EXAMPLES: 1) 12X12 TRANSFER DUCT FROM COPY 004 TO |
| | RECEPTION 004 SHOWS FD IN A NON-RATED WALL. 2) 6 INCH |
| | FLEX DUCT ENTERING CONFERENCE 008 THROUGH A RATED WALL |
| | WITH NO FD. 3) 12X8 SUPPLY FEEDING RECEPTION 004 SHOWS |
| | A FD WHERE THERE IS NO WALL OF ANY KIND. THERE ARE |
| | SEVERAL OTHER LOCATIONS. PLEASE CHECK THE ENTIRE AREA |
| | AND COORDINATE LOCATIONS OF REQUIRED FIRE DAMPERS WITH |
| | LOCATIONS OF RATED WALLS ON ARCHITECTURAL PLANS. DO NOT |
| | SHOW FDS IN NON-RATED WALLS AS THEY WOULD NOT BE |
| | INSTALLED IN ACCORDANCE WITH THEIR LISTING AS REQUIRED |
| | BY FBC, M 607.2. |
| | |
| | B. OK |
| | |
| | C. OK |
| | |
| | D. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | E. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | F. M2.04: SEF-5 DUCT (AND POSSIBLY SEF-7 DUCT) STILL |
| | SHOWS FIRE DAMPERS. SHOW OPENING PROTECTIVES WHICH ARE |
| | IN COMPLIANCE WITH FBC, M 607.2.1. |
| | |
| | G. M2.06: O.A. DUCT HAS BEEN ADDED. HOWEVER, O.A. RATE |
| | FOR AHU ST-11 IS NOT SHOWN ON EQUIPMENT SCHEDULE. SEE |
| | M-5.01. ALSO, VENTILATION SYSTEMS SHALL BE DESIGNED TO |
| | BE CAPABLE OF REDUCING THE SUPPLY OF OUTDOOR AIR TO THE |
| | MINIMUM VENTILATION RATES REQUIRED BY SECTION 6.1.3 OF |
| | ASHRAE 62 IN COMPLIANCE WITH FBC 13-409.1.ABC.1.1. |
| | THERE IS NO VOLUME DAMPER ON O.A. DUCT. |
| | |
| | H. THIS HAS GENERALLY BEEN CORRECTED. HOWEVER, ON M2.07 |
| | AND M2.08 THE C.O. SENSORS HAVE A DESIGNATION FOR |
| | ?GEF-5&R.? PLEASE SHOW A DESIGNATION WHICH CORRESPONDS |
| | WITH THE FANS SERVING THE FLOOR WHERE THE C.O. SENSORS |
| | ARE LOCATED. |
| | |
| | I. OK |
| | |
| | J. O.A. RATES FOR AHU 18 IS NOW ON PLANS. HOWEVER, |
| | COOLING LOAD CALCS, AS PREVIOUSLY REQUESTED, WERE NOT |
| | PROVIDED AS REQUIRED BY FBC 13-407.1.ABC.1. ALSO, THE |
| | ENERGY CALCULATION FORM SUBMITTED IS NOT THE CORRECT |
| | VERSION. AS THIS PERMIT APPLICATION WAS SUBMITTED PRIOR |
| | TO DEC. 8, 2006 THE CORRECT FORM IS 400A V2.11. IN |
| | ADDITION, THE ADDRESS ON THE PROJECT SUMMARY SHEET IS |
| | INCORRECTLY STATED AS 430 HIBISCUS, RATHER THAN THE |
| | PERMITTED ADDRESS OF 480 HIBISCUS. PLEASE ALSO SEE THAT |
| | THE OWNER/AGENT HAS NOT SIGNED THE FORM AS REQUIRED BY |
| | FBC 13-103.1. PLEASE MAKE ALL NECESSARY CORRECTIONS AND |
| | RESUBMIT ENERGY CALCULATIONS. |
| | |
| | K. OK |
| | |
| | L.PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | NOTE: PG M2.33 WAS NOT RESUBMITTED WITH REV.16. |
| | |
| | M. OK EXCEPT, M2.31 WAS NOT RESUBMITTED WITH REV.16. |
| | THE CURRENT M2.31 (REV.4) SHOWS THE RELIEF VENT FOR |
| | STAIR #3 AS 36X36 WHILE THE RISER DIAGRAM FOR STAIR #3 |
| | ON M4.03 (REV.16) SHOWS THE RELIEF VENT AS 18X18. WHICH |
| | IS CORRECT? PLEASE CLARIFY. |
| | |
| | N. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | O. OK. HAVE THESE SHAFT ENCLOSURES BEEN INCORPORATED |
| | INTO THE ARCHITECTURAL PLANS? |
| | |
| | P. THIS PAGE WILL BE REVIEWED IN CONJUNCTION WITH |
| | RESUBMITTED ENERGY CALCULATIONS. |
| | |
| | Q. COMMENT 33(A) WAS NOT ADDRESSED. |
| | |
| | R. M6.02 WAS NOT RESUBMITTED AS PART OF REV.16. |
| | |
| | S. OK |
| | |
| | T. OK |
| | |
| | U. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | V. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON |
| | PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND |
| | COMPLIANCE WITH CITED CODE SECTION AS STATED IN |
| | PREVIOUS REVIEW COMMENTS. |
| | |
| | NOTE: REVISIONS TO MECHANICAL PLANS CONTINUE TO BE |
| | ADDED WITHOUT PREVIOUS REVIEW COMMENTS BEING ADEQUATELY |
| | ADDRESSED. THESE CHANGES HAVE NOT BEEN INCORPORATED |
| | INTO THE PERMIT SET OF PLANS. WE ARE NOW AT A POINT |
| | WHERE IT BECOMES IMPRACTICAL TO REVIEW FOR CHANGES |
| | UNTIL ALL OUTSTANDING REVIEW COMMENTS HAVE BEEN |
| | ADDRESSED AND THE RELATED CODE DEFICIENCIES ARE |
| | CORRECTED. NO FURTHER CHANGES TO MECHANICAL PLANS WILL |
| | BE REVIEWED UNTIL ALL OUTSTANDING COMMENTS HAVE BEEN |
| | ADEQUATELY ADDRESSED. |
| | |
| | AS THE ABOVE COMMENTS INDICATE, THE MAJORITY OF |
| | PREVIOUS REVIEW COMMENTS ARE STILL OUTSTANDING. PLEASE |
| | PROVIDE A WRITTEN RESPONSE TO EACH COMMENT WITH A |
| | DESCRIPTION OF HOW EACH COMMENT HAS BEEN ADDRESSED. |
| | THIS WILL HELP TO FACILITATE A TIMELY REVIEW. ONE SET |
| | OF REV.16 PLANS WILL BE RETAINED BY THIS OFFICE FOR THE |
| | PURPOSE OF DOCUMENTING REPEAT CODE DEFICIENCIES AND TO |
| | ASSIST IN IDENTIFYING CHANGES DURING SUBSEQUENT |
| | REVIEWS. |
| | |