| Plan Review Notes For Permit 05091265 |
| Permit Number |
05091265 |
|
| Review Stop |
E |
| Sequence Number |
11 |
|
| Notes |
| Date |
Text |
| 2007-08-28 12:57:30 | ** DENIED ** | | | | | | SWITCH GEAR SUBMITTALS | | | | | | 1) NOTE: PLEASE MAKE CORRECTIONS AS NOTED BY THE | | | ENGINEER AND CORRELATE WITH THE SUBMITTED STAMPED | | | PLANS. | | | | | | 2) NOTE: A MCB MAY BE REQUIRED ON EDPH, AS THE ATS DOES | | | NOT CONTAIN THE DISCONNECT NEEDED ON THE NORMAL AND | | | EMERGECNY SIDE. | | | PLEASE SEE THE STAMPED PLANS. | | | | | | PLEASE SUBMIT THE STAMPED SETS FROM THE ENGINEERS | | | OFFICES AND ONLY SUBMIT THREE SETS FOR REVIEW AND | | | STAMPING. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 |
|