Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop M
Sequence Number 10
Notes
Date Text
2007-08-14 10:57:09SUBMITTAL WITH NEW REFRIGERANT RISER CALCULATIONS,
 SHOWING LOCATIONS OF REQUIRED SHAFTS BASED ON
 REFRIGERANT QUANTITIES AND THE THROUGH-PENETRATION
 FIRESTOP SYSTEMS TO BE USED WHERE SHAFTS WILL NOT BE
 REQUIRED. ONLY ONE COPY HAS BEEN SUBMITTED. THEREFORE,
 IT WILL BE RETAINED PENDING RECEIPT OF REVISED PLANS
 SHOWING LOCATION OF SHAFTS. AT THAT TIME, THE SUBMITTAL
 WILL BE USED TO ENSURE THAT SHAFT LOCATIONS ARE ORRECT
 IN CONJUNCTION WITH RISER CALCULATIONS IN THE
 SUBMITTAL.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]
2007-08-10 13:52:38REFRIGERANT CHASES - UPDATED 8/14/07
  
 8/13/07 - AS OF THIS TIME, THE SUBMITTAL STATES THAT A
 DETAIL FOR A TREMCO THROUGH-PENETRATION FIRESTOP SYSTEM
 IS SINCLUDED IN THE PACKAGE. HOWEVER, NONE COULD BE
 LOCATED IN THE PACKAGE. A CALL WAS PLACED TO TONY
 SPEZZA AT THE FELLER OFFICE. TONY SUPPLIED A DETAIL OF
 A SYSTEM INTENDED FOR USE IN THIS APPLICATION. HOWEVER,
 THE ASSEMBLY PROVIDED DOES NOT MEET THE F AND T RATING
 OF THE FLOOR BEING PENETRATED AS IS REQUIRED BY FBC
 712.4.1.2.
  
 PER THE REQUEST OF JACK NEDLIN, A COPY OF PREVIOUS PLAN
 REVIEW COMMENTS IS BEING FAXED TO HIS OFFICE. THE
 REVIEW OF THIS SUBMITTAL IS BEING PLACED ON HOLD, AGAIN
 AT THE REQUEST OF JACK NEDLIN, UNTIL A RESPONSE IS
 PROVIDED BY JACK NEDLIN OR OTHER AUTHORIZED AGENT FOR
 STEVEN FELLER, PE.
  
 8/14/07 - RECEIVED MISSING INFORMATION FROM MARC
 COLEMAN AT HH DEVELOPMENT. THE SUBMITTAL IS CURRENTLY
 UNDER REVIEW.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]