| 2005-12-05 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 BUILDING |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. IF THE DESIGN PROFESSIONAL IS AN |
| | ARCHITECT OR ENGINEER LEGALLY REGISTERED |
| | UNDER THE LAWS OF THIS STATE REGULATING |
| | THE PRACTICE OF ARCHITECTURE AS PROVIDED |
| | FOR IN CHAPTER 481, FLORIDA STATUTES, OR |
| | ENGINEERING AS PROVIDED FOR IN CHAPTER |
| | 471, FLORIDA STATUTES, THEN HE OR SHE |
| | SHALL AFFIX HIS OR HER OFFICIAL SEAL, |
| | SIGNATURE, AND DATE TO SAID DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA AS |
| | REQUIRED BY FLORIDA STATUTE. SECTION |
| | 106.1, FAC 61G15-23.002(2)/61G1-16.003 |
| | AND FS 471.2055/481.025. |
| | 2. SHT A1.0 MEN'S & WOMEN'S TOILET ROOMS |
| | SHALL BE ACCESSIBLE. SUBMIT DETAILS |
| | SHOWING COMPLIANCE WITH SECTIONS |
| | 11-4.16, 11-4.19, & 11-4.22 AND ALL |
| | SUBSECTIONS. |
| | 3. SHT A1.0 THE DRINKING FOUNTAIN SHALL |
| | BE ACCESSIBLE. SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH SECTIONS 11-4.15 AND ALL |
| | SUBSECTIONS AS WELL AS SECTION |
| | 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO |
| | HAVE DIFFICULTY BENDING OR STOOPING. |
| | 4. SHT A1.2 MEN'S & WOMEN'S TOILET ROOMS |
| | SHALL BE ACCESSIBLE. SUBMIT DETAILS |
| | SHOWING COMPLIANCE WITH SECTIONS |
| | 11-4.16, 11-4.19, 11-4.21, 11-4.22 AND |
| | ALL SUBSECTIONS. ALSO FOR THE BREAK ROOM |
| | SINK, 11-4.24 AND ALL SUBSECTIONS. |
| | 5. SHT A1.18 MEN'S AND WOMEN'S LOCKER |
| | ROOMS TO BE ACCESSABLE. SUBMIT DETAILS |
| | SHOWING COMPLIANCE WITH SECTION 11-4.16, |
| | 11-4.18, 11-4.19, 11-4.21, & 11-4.22 AND |
| | ALL SUBSECTIONS. |
| | 6. SHT A1.21 MEN'S & WOMEN'S TOILET |
| | ROOMS AND DRINKING FOUNTAIN SHALL BE |
| | ACCESSIBLE. (SEE COMMENTS 2 AND 5). |
| | 7. SHT A9.10 UNITS A5.2, A5 & A5.1 CLEAR |
| | FLOOR SPACE FOR SHOWERS SHALL BE |
| | PARALLEL TO THE FIXTURE AND FLUSH WITH |
| | THE CONTROLS. PAGE 7.56 PARAGRAPH TWO. - |
| | UNITS A5, & A5.1 INDICATE SIZE OF |
| | OPENING FOR W/C'S. (MINIMUM 33" REQD.). |
| | 8. SHT A9.11 UNITS A5A.2, A5A. & A5A.1 |
| | CLEAR FLOOR SPACE FOR SHOWERS SHALL BE |
| | PARALLEL TO THE FIXTURE AND FLUSH WITH |
| | THE CONTROL WALL. PAGE 7.56. |
| | 9. SHT A9.13 UNITS A7 & A7.1 CLEAR FLOOR |
| | SPACE FOR SHOWERS SHALL BE PARALLEL TO |
| | THE FIXTURE AND FLUSH WITH THE CONTROL |
| | WALL. PAGE 7.56. |
| | 10. UNITS B1D.2, & B1D.1 W/C IN MASTER |
| | BATH SHALL BE 18" OFF THE WALL TO THE |
| | CENTER OF THE FIXTURE. PLEASE SHOW ON |
| | THE PLANS. PAGES 7.43 THRU 7.46. |
| | 11. SHT A9.24 UNITS C1.1, C1.2, & C1 |
| | OPENING FOR WATER CLOSET IN BATH #2 |
| | SHALL BE MINIMUM 33" . PLEASE INDICATE |
| | ON PLANS. PAGE 7.44 |
| | 12. SHTS A9.2 THRU A9.24 ALL UNITS. |
| | CLEAR FLOOR SPACE FOR THE WATER CLOSETS |
| | SHALL BE APPLIED OR SUPERIMPOSED OVER A |
| | PLAN PER PAGE 7.43 PARAGRAPH ONE. |
| | 13. SHTS A9.2 THRU A9.24 PER PAGE 7.7 |
| | MINIMUM CLEARANCES BETWEEN COUNTERS AND |
| | ALL OPPOSING ELEMENTS IS 40". PLEASE |
| | INDICATE ON THE PLANS THE MINIMUM |
| | CLEARANCE FOR ALL KITCHENS. |
| | 14. SHT P2.01 NO PIPING SHOWN TO 3 PAD'S |
| | PLEASE CLARIFY. SECTION 106.1.1 - SHOW |
| | ALL PIPE SIZES FOR ALL PIPE SYSTEMS ON |
| | THE FLOOR PLAN. TABLES 710.1 & 1106.3. - |
| | TRAPS REQUIRED ON THE DRAIN LINES FOR |
| | THE FIRE DRAIN RISERS. SECTION 802.2. - |
| | FITTINGS SHALL BE INSTALLED TO GUIDE |
| | SEWAGE AND WASTE IN THE DIRECTION OF |
| | FLOW. SECTION 706.3 (SEE CD & D LINES TO |
| | THE LEFT OF THE MANHOLE. - INDICATE |
| | WHERE SD LINE IS GOING AT COL. LINE 12 |
| | BETWEEN COLS. P & Q. SECTION 106.1.1. |
| | 15. SHT P2.02 RISERS 9 & 10 ARE |
| | MISLABLED AT COL. LINE 6-E. SECTION |
| | 106.1.1. - NO PIPING SHOWN TO 2 PAD'S. |
| | SECTION 106.1.1. - SHOW ALL PIPE SIZING |
| | FO U/G BUILDING SANT. , STORM, COND., |
| | AND DRAIN PIPING. SECTION 106.1.1. |
| | 16. SHT P2.03 SANT. PIPING NOT APPROVED |
| | IN THE EGRESS STAIRWELL AT COL LINE 22-I |
| | PER NFPA-101 SECTION 7.1.3.2.1(6). - 2" |
| | DRAIN LINE TO THE RIGHT OF COL. LINE 28 |
| | REQUIRES A VENT. SECTION 901.2.1. - |
| | FOUNTAIN WATER SUPPLY REQUIRES BACKFLOW |
| | PROTECTION PER SECTION 608.13. INDICATE |
| | METHOD OF PROTECTION. - KEY NOTES 4 & 7 |
| | NOT FOUND. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | 17. SHT P2.04 SANT. PIPING NOT ALLOWED |
| | IN THE STAIRWELL PER NFPA-101 SECTION |
| | 7.1.3.2.1(6). |
| | 18. SHTS P2.16 & P2.17 KEY NOTE 2 |
| | INDICATES, AND PLAN SHOWS RISER THRU |
| | NEXT FLOOR, WHEN THEY SHOUD INDICATE |
| | "TURN DOWN". PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | 19. SHTS P2.19 & P2.20 SUBMIT |
| | CALCULATIONS FOR PRIMARY AND SECONDARY |
| | STORM DRAINS. SHOW SQUARE FEET, 1/2 AREA |
| | OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS, AND AREA OF ROOFS DRAINING TO |
| | DECK AREA FROM ABOVE IN THE CALCULATIONS |
| | PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECITONS. - SHOW THE LOCATION OF ALL |
| | SECONDARY DRAINS. |
| | 20 SHTS P2.28, P2.29, & P2.30 ARE |
| | SHOWING ALL 37 RWL'S. PREVIOUS LEVELS |
| | SHOW JUST A FEW IF ANY RWL LOCATIONS. |
| | PLEASE SHOW ALL RWL'S ON EACH LEVEL. |
| | SECTION 106.1.1. |
| | 21. SUBMIT A STORM DRAIN COLLECTION |
| | ISOMETRIC RISER DIAGRAM. (SHT P3.13 |
| | SHOWN ON THE INDEX PAGE WAS NOT |
| | SUBMITTED). - SHOW ALL PIPE SIZES, |
| | SQUARE FOOTAGE AS IT ACCUMULATES IN THE |
| | SYSTEM & LOCATION OF EACH RWL RISER. |
| | SECTION 106.1.1. - SUBMIT STORM RISER |
| | DIAGRAMS SHOWING ALL PIPE SIZES, |
| | OFFSETS, AND SQUARE FOOTAGE ECT. SECTION |
| | 106.3.5.1.3(7)(13). |
| | 22. SHT P3.01 RECALCULATE FU'S FOR RISER |
| | 11 & DOWNSTREAM. (11 NOT ADDED IN FU'S.) |
| | SECTION 106.1.1 & TABLE 710.1(1). - ALL |
| | FIRE DRAIN LINES REQUIRE A TRAP PER |
| | SECTION 802.2. - RISERS 49 & 55 APPEAR |
| | TO RISE TO THE 7TH FLOOR. PLEASE CLARIFY |
| | SECTION 106.1.1. - PARTIAL SANITARY |
| | COLLECTION ISOMETRIC DOES NOT REFLECT |
| | THE FLOOR PLAN UPSTREAM OF THE TRASH |
| | ROOM FLOOR DRAIN, AND DOWNSTREAM OF THE |
| | MOP SINK. PLEASE CORRELATE RISER AND |
| | FLOOR PLAN. SECTION 106.1.1. |
| | 23. SHT P3.02 2-WAY CLEANOUTS ARE |
| | REQUIRED ON BOTH THE ENTRANCE AND EXIT |
| | OF THE GREASE INTERCEPTOR PER UTILITY |
| | STANDARDS. - FIXTURE UNIT VALUE NOT |
| | SHOWN FOR 3 FURTURE STUB UPS. TABLE |
| | 710.1(1). - 10" 2679FU REQUIRES 12" PIPE |
| | OR SHALL BE SHOWN AS 1/8"FT THE ENTIRE |
| | RUN. TABLE 710.1(1) AND SECTION 704.1. - |
| | 10" 2689FU REQUIRES 12" PIPE OR SHALL BE |
| | SHOWN AS 1/8"FT THE ENTIRE RUN. TABLE |
| | 710.1(1) & SECTION 704.1. - 12" 4402FU |
| | REQUIRES 15" PIPE OR SHALL BE SHOWN AS |
| | 1/8"FT THE ENTIRE RUN. TABLE 710.1(1) & |
| | SECTION 704.1. |
| | 24. SHT P3.03 RISERS S/27, S/36, S/78, |
| | S/94 & S/31, S/89, S/147, S/149 VENT |
| | STACK REQUIRED PER TABLE 903.2 |
| | 25. SHTS P3.05, P3.06, & P3.07 SHT PX |
| | INDICATED ON EACH SHEET WAS NOT LOCATED. |
| | PLEASE SUBMIT SHT PX. SECTION 106.1.1. |
| | 26. SHT P3.08 KEY NOTES INFORMATION IS |
| | REVERSED FROM RISERS. PLEASE CORRELATE |
| | KEY NOTES AND RISERS. SECTION 106.1.1. |
| | 27. SHT P3.10 WATER RISER FOR UNIT A3.1 |
| | AND REV. A3.1 INDICATE 2 W/M'S. FLOOR |
| | PLAN ONLY INDICATES ONE. PLEASE |
| | CORRELATE FLOOR PLAN & RISER DIAGRAM. |
| | SECTION 106.1.1. |
| | 28. SHT P3.12 PAD RISER TO THE LEFT OF |
| | LIFT STATION AND PIPING WHERE THE PIPING |
| | SPLITS LEFT & RIGHT PRIOR TO THE LIFT |
| | STATION DO NOT REFLECT THE FLOOR PLAN. |
| | ALSO 6 RISERS SHOW 2 FOURTH FLOORS. |
| | PLEASE CORRELATE RISERS & FLOOR PLANS. |
| | SECTION 106.1.1. |
| | 29. SHT P3.13 NOT SUBMITTED. (SHOWN ON |
| | THE INDEX SHEET). |
| | 30. SHT P3.14 6 STORM MANHOLES ARE SHOWN |
| | ON THE GROUND FLOOR PLUMBING PLANS. |
| | THESE ARE NOW REFERED TO AS STORM DRAIN |
| | LIFT STATIONS, AND ONLY 4 ARE SHOWN. |
| | PLEASE CORRELATE THE TERMINOLOGY AND |
| | INDICATE WHERE THE OTHER LIFT STATIONS |
| | ARE LOCATED. NONE OF THE RISERS DIAGRAMS |
| | REFLECT THE FLOOR PLANS. - PLEASE NUMBER |
| | OR PLACE A DESIGNATION ON THE LIFT |
| | STATIONS BOTH ON THE RISER DIAGRAMS AND |
| | THE FLOOR PLANS TO HELP EXPEDITE THE |
| | PLAN REVIEW. - RISER (4" 2830SF) DOES |
| | NOT APPEAR TO PICK UP ANY DRAINS. PLEASE |
| | CLARIFY. - 2" DRAIN UPSTREAM OF 4" HD IS |
| | SHOWN TO BE ON THE SANT. SYSTEM ON THE |
| | FLOOR PLAN. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | 31. SHT P3.15 FITTINGS SHALL BE |
| | INSTALLED TO GUIDE SEWAGE AND WASTE IN |
| | THE DIRECTION OF FLOW. SECTION 706.3. |
| | SEE FITTING UPSTREAM OF MANHOLE (OR LIFT |
| | STATION). - DOES NOT REFLECT THE FLOOR |
| | PLAN. RISERS CD/37 & DR/37 NOT SHOWN ON |
| | RISER DIAGRAM. |
| | 32. DOMESTIC BOOSTER PUMPS, STORM LIFT |
| | STATION PUMPS SHALL BE LISTED. PLEASE |
| | SUBMIT MANUF. SPECIFICATION SHEETS FOR |
| | EACH. SECTION 303. |
| | 33. GREASE INTECEPTOR SHALL BE SIZED BY |
| | THE ENVIRONMENTAL COMPLIANCE MANAGER. |
| | PLEASE CONTACT LYNN MASSON (561) |
| | 822-2271 OR BY FAX (561) 822-2279 OR BY |
| | E-MAIL [email protected]. |
| | 34. SHT P309 KEY NOTES 7 - A/C CLOSET IS |
| | A PLENUM AND AS SUCH SHALL HAVE NO |
| | COMBUSTABLE MATERIAL. PLEASE INDICATE |
| | THE MATERIAL BEING USED FOR THE THERMAL |
| | EXPANSION VALVE DRAIN, THE P&T RELIEF |
| | VALVE DISCHARGE DRAIN, AND THE EMERGENCY |
| | PAN DRAIN FOR THE WATER HEATER. |
| | 35. PLANS SHOW A VENT IN THE WALL AND AN |
| | OPEN 2" DRAIN IN THE PLENUM. MORE |
| | INFORMATION IS REQUIRED. WILL THE ROOM |
| | AS A PLENUM PULL THE AIR FROM THE 2" |
| | OPEN DRAIN AND INTRODUCE THE HUMID, WARM |
| | AIR INTO THE AIR CONDITIONED AIR OF THE |
| | UNIT? IS THIS PRACTICE ACCEPTABLE TO THE |
| | MECHNAICAL ENGINEER? - ALSO THE VENT |
| | TERMINATION SHALL EITHER VENT THRU THE |
| | ROOF OR TERMINATE ABOVE THE CEILING 6" |
| | ABOVE THE INSULATION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |