2005-12-27 00:00:00DENIED:CITY PALMS/10 STORY
 2004 FLORIDA BUILDING CODE
  
 1.PLANS ARE TO SIGNED, SEALED AND
 DATED BY THE ENGINEER OF RECORD IN
 ACCORDANCE WITH FS 471.025.
  
 2.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2004 FMC TABLE 403.3.
  
 3.PLAN SHEET A1.0 DOES NOT INDICATE
 TENANT SEPARATION BETWEEN THE RETAIL
 SPACES.
  
 4.PLAN SHEET M2.01 INDICATES FBC 412.5
 SMOKE EXHAUST THROUGH NATURAL
 VENTILATION FOR RETAIL SPACE.PLEASE
 NOTE, SMOKE CONTROL & EXHAUST UNDER THE
 2004 FLORIDA BUILDING CODE IS NOW
 ADDRESSED IN 513 OF THE FLORIDA
 MECHANICAL CODE.PLEASE INDICATE METHOD
 AND CALCULATIONS FOR SMOKE CONTROL.
  
 5.PLAN SHEET M2.01 AHU-12, 13 & 14 ARE
 LOCATED IN A STORAGE ROOM, PLEASE
 CLARIFY.
  
 6.AHU-13 IS NOT INDICATED ON THE
 EQUIPMENT SCHEDULE (M5.01).
  
 7.PLAN SHEET M2.01 (ROOM #006 & 011)
 FLEX DUCTS PENETRATING WALLS/PARTITIONS
 WITH FIRE RATING & FIRE DAMPERS ARE NOT
 INDICATED.DUCT SHALL COMPLY WITH 2004
 FMC 607.5.3 #2.
  
 8.PLEASE INDICATE ALL FIRE & FIRE
 SMOKE DAMPERS ON PLAN IN ACCORDANCE WTIH
 2004 FMC 607.5.3.
  
 9.PLEASE CLARIFY DETAIL OF THE
 REFRIGERANT LINE SETS ON PLAN SHEET
 M5.01.WILL LINE SETS BE IN A SHAFT?.
 DETAIL INDICATES GOOSE NECK THAT APPEARS
 TO END AT THE SLAB, BUT THE NOTE STATES
 "SLEEVE TO PROVIDE VENTILATION PER
 ASHRAE 15".PLEASE INDICATE WHERE
 SHAFTS WILL BE VENTILATED.
  
 10. PROVIDE CALCULATION FOR THE
 REFRIGERANT PER TABLE 1103.1 OF THE 2004
 FMC.
  
 11. PROVIDE MANUFACTURER'S
 SPECIFICATIONS FOR EQUIPMENT.
  
 12. PLEASE PROVIDE ENERGY CALCULATIONS
 IN ACCORDANCE WITH 2004 FBC CHAPTER 13.
  
 13. PLEASE PROVIDE SUBMITTAL FOR THE
 GENERATOR.
  