| 2005-12-27 00:00:00 | DENIED:CITY PALMS/10 STORY |
| | 2004 FLORIDA BUILDING CODE |
| | |
| | 1.PLANS ARE TO SIGNED, SEALED AND |
| | DATED BY THE ENGINEER OF RECORD IN |
| | ACCORDANCE WITH FS 471.025. |
| | |
| | 2.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS PER 2004 FMC TABLE 403.3. |
| | |
| | 3.PLAN SHEET A1.0 DOES NOT INDICATE |
| | TENANT SEPARATION BETWEEN THE RETAIL |
| | SPACES. |
| | |
| | 4.PLAN SHEET M2.01 INDICATES FBC 412.5 |
| | SMOKE EXHAUST THROUGH NATURAL |
| | VENTILATION FOR RETAIL SPACE.PLEASE |
| | NOTE, SMOKE CONTROL & EXHAUST UNDER THE |
| | 2004 FLORIDA BUILDING CODE IS NOW |
| | ADDRESSED IN 513 OF THE FLORIDA |
| | MECHANICAL CODE.PLEASE INDICATE METHOD |
| | AND CALCULATIONS FOR SMOKE CONTROL. |
| | |
| | 5.PLAN SHEET M2.01 AHU-12, 13 & 14 ARE |
| | LOCATED IN A STORAGE ROOM, PLEASE |
| | CLARIFY. |
| | |
| | 6.AHU-13 IS NOT INDICATED ON THE |
| | EQUIPMENT SCHEDULE (M5.01). |
| | |
| | 7.PLAN SHEET M2.01 (ROOM #006 & 011) |
| | FLEX DUCTS PENETRATING WALLS/PARTITIONS |
| | WITH FIRE RATING & FIRE DAMPERS ARE NOT |
| | INDICATED.DUCT SHALL COMPLY WITH 2004 |
| | FMC 607.5.3 #2. |
| | |
| | 8.PLEASE INDICATE ALL FIRE & FIRE |
| | SMOKE DAMPERS ON PLAN IN ACCORDANCE WTIH |
| | 2004 FMC 607.5.3. |
| | |
| | 9.PLEASE CLARIFY DETAIL OF THE |
| | REFRIGERANT LINE SETS ON PLAN SHEET |
| | M5.01.WILL LINE SETS BE IN A SHAFT?. |
| | DETAIL INDICATES GOOSE NECK THAT APPEARS |
| | TO END AT THE SLAB, BUT THE NOTE STATES |
| | "SLEEVE TO PROVIDE VENTILATION PER |
| | ASHRAE 15".PLEASE INDICATE WHERE |
| | SHAFTS WILL BE VENTILATED. |
| | |
| | 10. PROVIDE CALCULATION FOR THE |
| | REFRIGERANT PER TABLE 1103.1 OF THE 2004 |
| | FMC. |
| | |
| | 11. PROVIDE MANUFACTURER'S |
| | SPECIFICATIONS FOR EQUIPMENT. |
| | |
| | 12. PLEASE PROVIDE ENERGY CALCULATIONS |
| | IN ACCORDANCE WITH 2004 FBC CHAPTER 13. |
| | |
| | 13. PLEASE PROVIDE SUBMITTAL FOR THE |
| | GENERATOR. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |
| | |
| | |
| | |