Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-11-29 00:00:00******DENIED******
  
 1) BUILDING SHALL MEET THE REQUIREMENTS
 FOR HIGHRISE IN ACCORDANCE WITH NFPA
 101, CHAPTER 11 AND APPLICABLE BUILDING
 CODE.
  
 2) PARKING GARAGES SHALL MEET SEPARATION
 AND ALL OTHER REQUIREMENTS IN ACCORDANCE
 WITH FBC AND NFPA 88-A.
  
 3) HANDRAILS REQUIRED ON STAIRS LEADING
 TO MEZZANINE. OK ON STAIR DETAIL.
  
 4) DO TRASH CHUTE DOORS OBSTRUCT
 CORRIDORS GREATER THAN 1/2 THE WIDTH?
  
 5) ILLUMINATED EXIT SIGNS SHALL BE
 MOUNTED NOT MORE THAN 100' APART.
  
 6) IS THE ROOM LABELED TRASH CHUTE
 CORRECT? SHT. A- 0.3.
  
 7) PLEASE PROVIDE QUANTITY AND TYPE OF
 STORAGE THAT WILL BE KEPT IN POOL
 EQUIPMENT ROOM.
  
 8) EXIT STAIRS TO BE KEPT UP WITH
 CONSTRUCTION.
  
 9) SIGNS ARE REQUIRED IN STAIRWELLS
 INDICATING TOP, BOTTOM, FLOOR # AND ROOF
 ACCESS.
  
 10) PLEASE PROVIDE OCCUPANT LOAD FOR
 POOL AREA AND HEALTH CLUB.
  
 11) PLEASE NOTE ON PLANS THAT WALKING
 SURFACE AT POOL DECK TO BE SLIP
 RESISTANT.
  
 12) PLEASE PROVIDE MORE INFORMATION
 REGARDING EMERGENCY ROOM. USE?
  
 13) 2A-10 B,C RATED FIRE EXTINGUISHERS
 ARE REQUIRED AND SHALL BE MOUNTED TO
 SATISFY THE 75' TRAVEL DISTANCE
 REQUIREMENT.
  
 14) PLEASE INDICATE WHAT ELEVATORS ARE
 STETCHER ACCESSIBLE.
  
 15) WARNING SIGNS REQUIRED FOR ELEVATOR
 LOBBIES.
  
 16) NO STORAGE IN ELECTRICAL AND
 ELEVATOR MACHINE ROOMS.
  
 17) EXIT SIGN ON LS SHTS NEAR STAIR #1
 IS NOT AT THE STAIRWELL, BUT IS OK ON
 ELECTRICAL SHTS.
  
 18) FIRE EXTINGUISHERS ARE REQUIRED FOR
 EACH COMMERCIAL SPACE.
  
 19) NOTE A ON LS SHTS INDICATES THAT ALL
 INTERIOR FINISH TO BE CLASS A. PLEASE
 CLARIFY.
  
 20) TRAVEL DISTANCE ON LS SHTS
 ILLUSTRATES 278'. PLEASE SEE NFPA 101,
 2003 EDITION SECTION 30.2.6.4 THAT
 STATES THAT TRAVEL DISTANCE SHALL NOT
 EXCEED 250' IN SPRINKLERED BUILDING.
  
 21) PLEASE NOTE THAT SOME EXIT SIGNS ON
 LS SHTS ARE IN DIFFERENT LOCATIONS.
 PLEASE CORRULATE.
  
 22) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 23) FIRE ALARM SYSTEM TO MEET
 SURVIVABILITY REQUIREMENTS IN ACCORDANCE
 WITH NFPA 72.
  
 24) FIRE ALARM SYSTEM TO BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 25) KNOX BOX LOCKING CAPS REQUIRED FOR
 FDC'S. HIGHRISE BUILDINGS SHALL HAVE NOT
 LESS THAN (2) FDC'S.
  
 26) PLANS DON'T SHOW SMOKE DETECTOR IN
 FIRE ALARM CONTROL ROOM.
  
 27) FIRE ALARM SYSTEM TO BE CLASS A,
 STYLE D OR FULLY ADDRESSABLE.
  
 28) IT APPEARS THAT SOME SMOKE DETECTORS
 ARE MISSING IN SOME OF THE EQUIPMENT
 ROOMS AND STORAGE AREAS.
  
 29) SMOKE DETECTORS ARE REQUIRED IN ALL
 COMMON AREA CORRIDORS. NOT SHOWN ON
 PLANS.
  
 30) STANDPIPES TO BE 2 1/2" WITH 1 1/2"
 REDUCERS.
  
 31) TEMPORARY STANDPIPES REQUIRED WHEN
 BUILDING REACHED 3 STORIES OR 30" IN
 HEIGHT.
  
 32) PLEASE INDICATE THE FIRE PROTECTION
 LAYOUT WITHIN THE TRASH CHUTES.
  
 33) SEPARATE SHOP DRAWINGS, PERMIT AND
 MANUFACTURER SPEC SHTS REQUIRED FOR FIRE
 PUMP.
  
 34) NFPA 13, 2002 EDITION TO BE
 REFERENCED. SHT FP 4.02.
  
 35) NO CUTTING OR WELDING OPERATIONS TO
 OCCUR WITHOUT APPROVAL OF BUREAU OF FIRE
 PREVENTION AND COMPLIANCE WITH NFPA
 51-B.
  
 36) IN ADDITION TO ELECTRONIC SWITCHES,
 DOUBLE CHECK DETECTOR ASSEMBLY TO BE
 SECURED WITH LOCK AND CHAIN.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  