| 2005-11-29 00:00:00 | ******DENIED****** |
| | |
| | 1) BUILDING SHALL MEET THE REQUIREMENTS |
| | FOR HIGHRISE IN ACCORDANCE WITH NFPA |
| | 101, CHAPTER 11 AND APPLICABLE BUILDING |
| | CODE. |
| | |
| | 2) PARKING GARAGES SHALL MEET SEPARATION |
| | AND ALL OTHER REQUIREMENTS IN ACCORDANCE |
| | WITH FBC AND NFPA 88-A. |
| | |
| | 3) HANDRAILS REQUIRED ON STAIRS LEADING |
| | TO MEZZANINE. OK ON STAIR DETAIL. |
| | |
| | 4) DO TRASH CHUTE DOORS OBSTRUCT |
| | CORRIDORS GREATER THAN 1/2 THE WIDTH? |
| | |
| | 5) ILLUMINATED EXIT SIGNS SHALL BE |
| | MOUNTED NOT MORE THAN 100' APART. |
| | |
| | 6) IS THE ROOM LABELED TRASH CHUTE |
| | CORRECT? SHT. A- 0.3. |
| | |
| | 7) PLEASE PROVIDE QUANTITY AND TYPE OF |
| | STORAGE THAT WILL BE KEPT IN POOL |
| | EQUIPMENT ROOM. |
| | |
| | 8) EXIT STAIRS TO BE KEPT UP WITH |
| | CONSTRUCTION. |
| | |
| | 9) SIGNS ARE REQUIRED IN STAIRWELLS |
| | INDICATING TOP, BOTTOM, FLOOR # AND ROOF |
| | ACCESS. |
| | |
| | 10) PLEASE PROVIDE OCCUPANT LOAD FOR |
| | POOL AREA AND HEALTH CLUB. |
| | |
| | 11) PLEASE NOTE ON PLANS THAT WALKING |
| | SURFACE AT POOL DECK TO BE SLIP |
| | RESISTANT. |
| | |
| | 12) PLEASE PROVIDE MORE INFORMATION |
| | REGARDING EMERGENCY ROOM. USE? |
| | |
| | 13) 2A-10 B,C RATED FIRE EXTINGUISHERS |
| | ARE REQUIRED AND SHALL BE MOUNTED TO |
| | SATISFY THE 75' TRAVEL DISTANCE |
| | REQUIREMENT. |
| | |
| | 14) PLEASE INDICATE WHAT ELEVATORS ARE |
| | STETCHER ACCESSIBLE. |
| | |
| | 15) WARNING SIGNS REQUIRED FOR ELEVATOR |
| | LOBBIES. |
| | |
| | 16) NO STORAGE IN ELECTRICAL AND |
| | ELEVATOR MACHINE ROOMS. |
| | |
| | 17) EXIT SIGN ON LS SHTS NEAR STAIR #1 |
| | IS NOT AT THE STAIRWELL, BUT IS OK ON |
| | ELECTRICAL SHTS. |
| | |
| | 18) FIRE EXTINGUISHERS ARE REQUIRED FOR |
| | EACH COMMERCIAL SPACE. |
| | |
| | 19) NOTE A ON LS SHTS INDICATES THAT ALL |
| | INTERIOR FINISH TO BE CLASS A. PLEASE |
| | CLARIFY. |
| | |
| | 20) TRAVEL DISTANCE ON LS SHTS |
| | ILLUSTRATES 278'. PLEASE SEE NFPA 101, |
| | 2003 EDITION SECTION 30.2.6.4 THAT |
| | STATES THAT TRAVEL DISTANCE SHALL NOT |
| | EXCEED 250' IN SPRINKLERED BUILDING. |
| | |
| | 21) PLEASE NOTE THAT SOME EXIT SIGNS ON |
| | LS SHTS ARE IN DIFFERENT LOCATIONS. |
| | PLEASE CORRULATE. |
| | |
| | 22) SEPARATE SHOP DRAWINGS AND PERMITS |
| | REQUIRED FOR FIRE SPRINKLER AND FIRE |
| | ALARM SYSTEMS. |
| | |
| | 23) FIRE ALARM SYSTEM TO MEET |
| | SURVIVABILITY REQUIREMENTS IN ACCORDANCE |
| | WITH NFPA 72. |
| | |
| | 24) FIRE ALARM SYSTEM TO BE UL CERTIFIED |
| | FOR CENTRAL STATION SERVICE. |
| | |
| | 25) KNOX BOX LOCKING CAPS REQUIRED FOR |
| | FDC'S. HIGHRISE BUILDINGS SHALL HAVE NOT |
| | LESS THAN (2) FDC'S. |
| | |
| | 26) PLANS DON'T SHOW SMOKE DETECTOR IN |
| | FIRE ALARM CONTROL ROOM. |
| | |
| | 27) FIRE ALARM SYSTEM TO BE CLASS A, |
| | STYLE D OR FULLY ADDRESSABLE. |
| | |
| | 28) IT APPEARS THAT SOME SMOKE DETECTORS |
| | ARE MISSING IN SOME OF THE EQUIPMENT |
| | ROOMS AND STORAGE AREAS. |
| | |
| | 29) SMOKE DETECTORS ARE REQUIRED IN ALL |
| | COMMON AREA CORRIDORS. NOT SHOWN ON |
| | PLANS. |
| | |
| | 30) STANDPIPES TO BE 2 1/2" WITH 1 1/2" |
| | REDUCERS. |
| | |
| | 31) TEMPORARY STANDPIPES REQUIRED WHEN |
| | BUILDING REACHED 3 STORIES OR 30" IN |
| | HEIGHT. |
| | |
| | 32) PLEASE INDICATE THE FIRE PROTECTION |
| | LAYOUT WITHIN THE TRASH CHUTES. |
| | |
| | 33) SEPARATE SHOP DRAWINGS, PERMIT AND |
| | MANUFACTURER SPEC SHTS REQUIRED FOR FIRE |
| | PUMP. |
| | |
| | 34) NFPA 13, 2002 EDITION TO BE |
| | REFERENCED. SHT FP 4.02. |
| | |
| | 35) NO CUTTING OR WELDING OPERATIONS TO |
| | OCCUR WITHOUT APPROVAL OF BUREAU OF FIRE |
| | PREVENTION AND COMPLIANCE WITH NFPA |
| | 51-B. |
| | |
| | 36) IN ADDITION TO ELECTRONIC SWITCHES, |
| | DOUBLE CHECK DETECTOR ASSEMBLY TO BE |
| | SECURED WITH LOCK AND CHAIN. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |