| 2005-11-09 00:00:00 | FAILED: |
| | |
| | 1. PLEASE NOTE THAT CIVIL PLAN FOR THIS |
| | PROJECT MUST BE REVIEWD AND APPROVED BY |
| | THE PUBLIC UTILITIES AND ENGINEERING FOR |
| | ALL THE CONNECTIONS TO THE CITY SERVICES |
| | AND FOR ANY UNDERGROUND UTILITY UPGRADE |
| | OR ANY EASEMENT AS REQUIRED IN VICINITY |
| | OF THE PROJECT. |
| | 2. VERTICAL CLEARANCES FOR CROSSING |
| | UNDERGROUND UTILITIES FOR BOTH ON-SITE |
| | AND OFF-SITE MUST BE SHOWN. |
| | 3. SHEET WS1 OF 5, PLEASE VERIFY EX. 6" |
| | CIP AND EX. 15" VCP AND EX. 10" SAN. |
| | SEWER MAIN. |
| | 4. PLEASE SUBMIT STORM WATER CALCULATION |
| | WHICH INCLUDE PERVIOUS AND IMPERVIOUS, |
| | BUILDING AREA FOR OUR REVIEW. |
| | 5. PLEASE SUBMIT A COPY OF SFWMD PERMIT |
| | IF APPLIED, FOR OUR RECORD. |
| | 6. SHEET PD1 & PD2 OF 5, PLEASE VERIFY |
| | WEIR ELEVATION FOR THE PROPOSED CONTROL |
| | STRUCTURE. |
| | 7. PLEASE VERIFY, I.E(11.45')FOR |
| | STRUCTURE 7 AND I.E(13.0')FOR STRUCTURE |
| | 6. |
| | 8. A SEPARATE PERMIT FOR ALL THE WORK |
| | WITHIN PUBLIC R.O.W AT NO COST FROM |
| | PUBLIC UTILITIES AND ENGINEERING IS |
| | REQUIRED, PLEASE SUBMIT MOT AT THE TIME |
| | OF APPLICATION, 494-1086 WINDEL PALMER. |
| | 9. ACCESS RAMP PER INDEX 304 FDOT AT ALL |
| | SURROUNDING INTERSECTIONS MUST BE |
| | PROVIDED, PLEASE VERIFY. |
| | 10. STREETSCAPINGAND SIDEWALKS, ETC. |
| | MUST BE COORDINATED WITH LATEST FDOT |
| | PLANS FOR THE RECONSTRUCTION OF DIXIE |
| | AND SIDE STREETS. |
| | 11. PLEASE NOTE THAT CIVIL PLANS MUST BE |
| | SIGNED AND SEALED BY THE CIVIL E.O.R AT |
| | THE TIME OF ACTUAL PERMITTING. |
| | |
| | IF ANY QUESTION PLEASE CONTACT 805-6723 |
| | MOHAMMAD R. AMINI |