| Date |
Text |
| 2005-11-28 00:00:00 | *** UNSAT *** |
| | |
| | CITY PALMS |
| | 10-STORY CONDO |
| | |
| | 1)NOTE: PLEASE KNOW, PLANS WERE |
| | SUBMITTED FOR "PLAN REVIEW" ONLY AND |
| | WERE NOT SUBMITTED FOR PERMIT BEFORE THE |
| | CODE CHANGE OF OCT 1ST, 2005 TO THE NEW |
| | 2004 FBC. |
| | PLEASE SEE THAT ANY CHANGES WILL BE |
| | NEEDED WHEN SUBMITTING FOR PERMIT. |
| | |
| | 2)NOTE: PLEASE BE SURE ALL PLANS |
| | SUBMITTED FOR PERMITTING ARE SIGNED, |
| | DATED AND SEALED BY THE ENGINEER OF |
| | RECORD. |
| | FS 471.025 |
| | |
| | 3)NOTE: PLEASE SEE 110.26 FOR MEANS OF |
| | EGRESS FROM MAIN ELECTRICAL ROOM. |
| | PLEASE SEE THIS HAD BEEN GONE OVER IN A |
| | MEETING PRE-SUBMITTAL OF PLANS AND |
| | DESIGN FOR DOOR AND STAIR LOCATIONS WERE |
| | DICUSSED FOR A CHANGE. |
| | PLEASE KNOW, THAT IT IS THE UNDER |
| | STANDING OF THIS OFFICE THAT THE DOOR |
| | WOULD INCREASE TO A 6' OPENING AND ONLY |
| | ONE MEANS OF EGRESS WOULD BE PROVIDED |
| | AND STAIRS WOULD BE REMOVED? |
| | PLEASE VERIFY THIS AND ADJSUT PLANS FOR |
| | THESE CHANGES. |
| | THE STAIRS AS A MEANS OF EGRESS INSIDE |
| | THE MAIN ELECTRICAL ROOM WOULD PROPOSE A |
| | TRIPPING HAZARD IN A SITUATION OF |
| | SOMEONE BEING BLINDED OR HAVING TO EXIT |
| | THE ROOM IN AN EMERGENCY SITUATION. |
| | PLEASE INCLUDE "NOTES" ON SHEET FOR MAIN |
| | ELECTRICAL ROOM FOR ALL MIN CLEARNECES |
| | OER 110.26, PANIC HARDWARE FOR DOORS |
| | ETC. |
| | PLEASE ALSO SEE MIN CLEARENCE FOR OTHER |
| | ELECTRICAL ROOMS SHOWN ON ROOM LAYOUT |
| | PLAN. |
| | |
| | 4)NOTE: PLEASE SEE PLANS CALL FOR |
| | BLUIDING TO BE LOCATED AT 480 HIBISCUS, |
| | HOWEVER OUR SYSTEMWITH PCN # PROVIDED |
| | INCIDICATES "430". PLEASE CORRELATE AND |
| | ADJUST PLANS/APPLICATION. ETC. |
| | |
| | 5)NOTE: PLEASE BE SURE PLANS ARE |
| | SPECIFIC TO THE 2002 NEC WHICH IS |
| | CURRENTLY IN EFFECT. |
| | PLEASE KNOW: DEPENDING ON WHEN PLANS ARE |
| | SUBMITTED FOR PERMIT, A CODE CHAMGE TO |
| | THE 2005 NEC SHOULD BE COMING ABOUT IN |
| | MID 2006. |
| | |
| | 6)NOTE: PLEASE SEE 1.01 AND ADDITIONAL |
| | SHEETS WHICH REFERENCE ABCK TO 3.02 FOR |
| | ELECTRICLA ROOM LAYOUTS, HOWEVER 3.02 |
| | DOES NOT SHOW ROOM LAYOUTS. |
| | PLEASE CORRELATE. |
| | |
| | 7)NOTE: PLEASE PROVIDE COMPLETE |
| | "PHOTOMETRICS" FOR ALL CORRIDORS, |
| | STAIRWELLS AND EGRESS AREAS PER 2003 |
| | NFPA-101 7.8 AND 7.9. |
| | PLEASE SEE A MIN OF 10 FT CANDLES IS NOW |
| | REQUIRED FOR STAIR TOWERS UNDER NORMAL |
| | EGRESS CONDITIONS. |
| | |
| | 8)NOTE: PLEASE BE SURE THERE ARE |
| | EMERGENCY BATTERY BACK UP TYPE FIXTURES |
| | LOCATED IN ALL ELECTRICAL ROOMS, |
| | ELEVATOR EQUIPMENT ROOMS, FIRE PUMP, |
| | GENERATOR, AND FIRE COMMAND ROOM. |
| | PLEASE KNOW, SOME OF THESE ARE ALREADY |
| | SHOWN ON PLANS, HOWEVER SOME AREAS MAY |
| | BE REDLINED FOR THESE. |
| | NFPA-101 7.8,7.9, NEC 700.16 ETC. |
| | |
| | 8)NOTE: PLEASE SEE THAT EGRESS |
| | CORRIDORS, AND STAIR TOWERS WILL BE |
| | REQUIRED TO CONTAIN A MIN BATTERY BACK |
| | UP TYPE OF FIXTURE FOR EMERGENCY EGRESS |
| | OF 1 FT CANDLE. |
| | 7.9 LS 101 |
| | THE TRIPPING OF A SINGLE SWITCH OR |
| | BREAKER SHALL NOT LEAVE ANY ONE AREA IN |
| | TOTAL DARKNESS. |
| | |
| | 9)NOTE: PLEASE SEE WOMENS AND MENS |
| | RESTRMS IN COMMON AREAS CONTAINING |
| | RECEPTS LOCATED IN CLOSE PROXIMITY OF |
| | LAVATORYS. PLEASE BE SURE TO INDICATE |
| | GFI PROTECTIONS FOR THESE. |
| | 210.8B1 |
| | |
| | 10)NOTE: PLEASE SEE "CLUB RM" AND ALL |
| | RECEPTSWITHIN 6' OF SINKS SAHLL BE |
| | INDICATED AS GFI/GFI PROTECTED. |
| | 210.8B |
| | |
| | 11)NOTE: PLEASE SEE RETAIL SPACE #14, |
| | WHICH INDICATES A TRANSFORMER AND PANEL |
| | AS "FUTURE", HOWEVER PLEASE SEE THERE IS |
| | AN ADDITIONAL PANEL SHOWN BUT NOT CLEAR |
| | FOR USE ETC? |
| | 215.5 |
| | |
| | 12)NOTE: PLEASE NOTE ON PLANS THE MIN |
| | CLEARNECES FOR LT FIXTURES IN PROXIMITY |
| | OF POOL AND WATER FEATURES WATER'S EDGE. |
| | PLEASE SEE A MINOF 10' IS REQUIRED FOR |
| | FIXTURES OVER 30V. |
| | PLEASE SEE 680.22 FOR A MIN OF 5' FROM |
| | WATER'S EDGE WITH EXCEPTIONS. |
| | |
| | 13)NOTE: PLEASE SEE POSSIBLE NOTES FROM |
| | REVIEWS FROM FIRE, BLDGMECH ETC, WITH |
| | RESPECT TO THE LOCATION OF GENERATOR |
| | INTAKE AND EXHAUST. THESE SEEMS TO BE |
| | LOCATED IMEDIATELY ADJACENT TO THE PUBLE |
| | RIGHT OF WAY/SIDE WALK. |
| | PLEASE KNOW, THIS IS ONLY A COMMENT FOR |
| | ELECTRICAL REVIEW , HOWEVER MAY CHANGE |
| | ELECTRICAL LAYOUT?? |
| | |
| | 14)NOTE: PLEASE SEE PANELS "HP AND "LP". |
| | TRANSFORMER LOCATED AT ELEC RM ON 2.17. |
| | PLEASE SEE MIN CLEARENCES PER 110.26 |
| | |
| | 15)NOTE: PLEASE SEE SHEETS 2.21 WHICH |
| | STATES 6TH FLR, THEN 2.22GOES TO A |
| | "TYPICAL PARTIAL FLR" AND THEN PLANS GO |
| | BACK TO A 9TH FLR DETAIL ON 2.25? |
| | PLEASE VEIRFY IF THESE ARE FLRS 7,8? |
| | |
| | 16)NOTE: PLEASE PROVIDE NOTE ON ROOF-TOP |
| | PLANS WHICH WILL STATE THAT ANY |
| | LIGHTNING PROTECTION SYSTEMS MUST BE IN |
| | COMPLIANCE WITH NFPA-780. (OR WORDS TO |
| | THAT AFFECT). |
| | |
| | 17)NOTE: PLEASE PROVIDE DISCONNECTS OR A |
| | "TYPICAL DETAIL" FOR ROOF-TOP CU'S. |
| | 440.11 |
| | |
| | 18)NOTE: PLEASE SEE NO CIRCUITING SHOWN |
| | FOR SOME "HOUSE AREAS". PLEASE SEE |
| | REDLINED PLANS ON 2.32, STORAGE RM ETC. |
| | |
| | 19)NOTE: PLEASE SEE 680.23 AND 680.24 |
| | WHICH REQUIRES "NO OTHER" LIGHTING OR |
| | RECEPTS ON ELEVATOR MACHINE RMS CIRUITS |
| | OR ELEV PITS. PLEASE SEE 2.34,2.35 AND |
| | ANY OTHER ARES WHICH MAY BE FED FROM ANY |
| | OF THESE CIRCUITS. |
| | |
| | 20)NOTE: PLEASE SHOW CIRCUITING FOR ALL |
| | UNITS AND CORRELATE WITH THE PANEL |
| | SCHEDULES SUBMITTED. |
| | PLEASE KNOW, CODE COMPLIANCE FOR SOME |
| | ITEMS CAN NOT BE REVIEWED AT THIS TIME. |
| | 215.5 |
| | |
| | 21)NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| | FOR AHU'S AND HEAT. |
| | PLEASE SEE MANY PANEL SCHEDULES INDICATE |
| | LOADS AT 11KW ETC @65%?? PLEASE CLARIFY |
| | AS 11KW IS SHOWN AS THE DERATED LOAD. |
| | PLEASE SEE IF 11KW IS THE DE-RATED LOAD, |
| | THEN ACTUAL KW RATING FOR AHU WOULD BE |
| | ALMOST 15KW?? |
| | |
| | 22)NOTE: PLEASE SEE WATER HEATERS SHOW |
| | #8 AWG? PLEASE KNOW THIS IS ONLY A |
| | COMMENT AS #8 IS OK, HOWEVER MAY NOT BE |
| | REQUIRED. |
| | PLEASE SEE THE FOLLOWING COMMENT** |
| | |
| | 23)NOTE: PLEASE VERIFYOCP SHOWN FOR |
| | SOME WATER HEATERS AS 2POLE 30A AND SOME |
| | AS 2-POLE 40A?? |
| | PLEASE SEE 4.5KW IS THE SAME LOAD FOR |
| | BOTH AT 208V. |
| | PLEASE KNOW, THE CODE REQUIRES A MIN OCP |
| | AT 125% (422.13) , HOWEVER THE CODE ALSO |
| | LIMITS THE OCP AT 150%. 422.11. |
| | PLEASE ADJUST OCP AND ANY AWG. |
| | |
| | 24)NOTE: PLEASE SEE PANEL SCHEDULE NOTES |
| | LISTEDON EACH SHEET, HOWEVER THE NOTES |
| | ARE NOT LABLED TO PANELS. |
| | 215.5 |
| | |
| | 25)NOTE: PLEASE SEE MEDIA BOXES/PANELS |
| | ARE SHOWN IN CLOSETS ABOVE STORAGE |
| | SHELVES. |
| | PLEASE KNOW, ANY RECEPT REQUIRED FOR ANY |
| | TYPE OF PLUG-IN TRANSFORMER MAYNOT BE |
| | AT THIS LOCATION ABOVE OR IN CLOSE |
| | PROXIMITY TO ANY COMBUSTIBLES. |
| | 110.26,240.24 |
| | * NOTE:, ANY RECEPTS FOR ANY PLUG-IN |
| | TYPE OF TRANSFORMERS, MAY BE LOCATED |
| | ABOVE DOOR WAY.* |
| | |
| | 26)NOTE: PLEASE SEE NOTE #8, ON PANEL |
| | SCHEDULE NOTES. PLEASE SEE 310.15B6, |
| | WHICH DOES NOTES INLCUDE 120/208V |
| | SYSTEMS.THIS IS FOR INFORMATION ONLY. |
| | |
| | 27)NOTE: PLEASE VERIFY PLANS INDICATE |
| | BOTH A WASHER AND A DRYER, HOWEVER PLANS |
| | SEEM TO INDICATE LOCATION FOR STACKABLE |
| | UNITS ONLY.? |
| | WILL ELECTRICAL BE INSTALLED FOR BOTH? |
| | |
| | 28)NOTE: PLEASE SEE UNIT A-6 AS IT SEEMS |
| | WASHER/DRYER IS LOCATED ON KITCHEN |
| | COUNTERSPACE? |
| | |
| | 29)NOTE: PLEASE SEE UNIT A-8 FOR MISSING |
| | RECEPT PER 210.52. |
| | PLEASE BE SURE TO CHECK REDLINED PLANS |
| | FOR ANY OTHER POSSIBLE LOCATIONS WHICH |
| | MAY REQUIRE A RECEPT. |
| | |
| | 30)NOTE: PLEASE PROVIDE NOTES FOR |
| | PLACEMENT OF ALL SD'S PER 2002 NFPA-72 |
| | 11.8.3 |
| | |
| | 31)NOTE: PLEASE SEE MANY UNITS DO NOT |
| | INDICATE THE LV MEDIA BOXES AS SHOWN IN |
| | OTHER UNITS? PLEASE SEE UNITS, B1, |
| | B1B,B1F, B1E ETC. |
| | PLEASE VERIFY |
| | |
| | 32)NOTE: PLEASE SEE UNIT B1F, WHICH |
| | SEEMS TO INDICATE THE AN ENTIRE RECEPT |
| | AS BEING SWITCHED? PLEASE KNOW, THE CODE |
| | PERMITS A 1/2 SW RECEPT IF USING THE |
| | RECEPT FOR 210.70, 210.52 OR PLEASE ADD |
| | RECEPT TO MEET 210.52. |
| | SEE REDLINED PLANS. |
| | |
| | 33)NOTE: PLEASE SEE MSBH ON 5.01 SHOWS |
| | AS 2000A'S , YET 6.01 SHOWS 1200A WITH |
| | 1000A MCB. |
| | PLEASE CORRELATE: |
| | |
| | 34)NOTE: PLEASE SEE COMPLETE RISER |
| | DIAGRAM WITH LABELING OF FEEDERS FOR |
| | FEEDER SCHEDULE AND CORRELATING ALL |
| | NUMERCICAL IDENTIFICATION. |
| | |
| | 35)NOTE: PLEASE PROVIDE THE FOLLOWING |
| | FOR COMPLETETION OF GROUNDIOG ELECTRODE |
| | SYSTEM. |
| | PLEASE PROVIDE DETAIL FOR MAIN GROUNDING |
| | ELECTRODE SYSTEM TO ALSO INCLUDE THE |
| | REQUIRED FOOTER STEEL.250.50 |
| | |
| | PLEASE PROVIDE A GROUND RISER FOR |
| | CONNECTION OF ALL OTHER SEPARATELY |
| | DERIVED SYSTEMS/TRANSFORMER ATTACHMENTS |
| | TO THE MAIN GROUNDIGN ELECTRODE SYSTEM. |
| | 250.30 |
| | PLEASE PROVIDE THIS ON THE RISER DIAGRAM |
| | SHEET. |
| | |
| | 36)NOTE:PLEASE SUBMIT ALL INFORMATION |
| | FOR FIRE PUMP AND FIRE PUMP CONTROLLER. |
| | PLEASE ALSO PROVIDE MANUFACTURES |
| | SPECS/CUT SHEETS FOR ABOVE. |
| | |
| | 37)NOTE: PLEASE SUBMIT ALL INFORMATION |
| | FOR GENERATOR/ ATS. PLEASE SUBMIT THE |
| | SPECS/CUT FROM MANUFACTURE. |
| | PLEASE VERIFY OF THE ATS WILL BE A |
| | 4-POLE SWITCH. |
| | PLEASE SEE 700.7D AND IF YOU HAVE THE |
| | HANDBOOK, SEE EXPLANATION OF ARTICLE. |
| | I HAVE ATTACHED BOTH, JUST IN CASE. |
| | |
| | (D) GROUND FAULT. TO INDICATE A GROUND |
| | FAULT IN SOLIDLY GROUNDED WYE |
| | EMERGENCY SYSTEMS OF MORE THAN 150 VOLTS |
| | TO GROUND AND CIRCUIT-PROTECTIVE |
| | DEVICES RATED 1000 AMPERES OR MORE. THE |
| | SENSOR FOR THE GROUND-FAULT SIGNAL |
| | DEVICES SHALL BE LOCATED AT, OR AHEAD |
| | OF, THE MAIN SYSTEM DISCONNECTING |
| | MEANS FOR THE EMERGENCY SOURCE, AND THE |
| | MAXIMUM SETTING OF THE SIGNAL |
| | DEVICES SHALL BE FOR A GROUND-FAULT |
| | CURRENT OF 1200 AMPERES. INSTRUCTIONS |
| | ON THE COURSE OF ACTION TO BE TAKEN IN |
| | EVENT OF INDICATED GROUND FAULT |
| | SHALL BE LOCATED AT OR NEAR THE SENSOR |
| | LOCATION. |
| | |
| | ALTHOUGH 700.26 INDICATES THAT |
| | GROUND-FAULT PROTECTION OF EQUIPMENT IS |
| | NOT |
| | REQUIRED ON THE ALTERNATE SOURCE FOR |
| | EMERGENCY SYSTEMS, GROUND FAULTS CAN |
| | OCCUR ON SUCH SYSTEMS, AND THEY CAN |
| | RESULT IN EQUIPMENT BURNDOWN. BECAUSE |
| | OF THE EMERGENCY NATURE OF SUCH SYSTEMS, |
| | AUTOMATIC DISCONNECT IN THE EVENT |
| | OF A GROUND FAULT IS INAPPROPRIATE. |
| | DETECTION OF SUCH A FAULT, HOWEVER, IS |
| | DESIRABLE SO THAT THE CONDITION CAN BE |
| | CORRECTED. |
| | IN MY READING AND THE INFORMATION FROM A |
| | COUPLE OF MANUFACTURES OF ATS SWITCHES, |
| | A 4-POLE ATS IS REQUIRED. PLEASE RESERCH |
| | THE INFORMATION AND ADJUST. |
| | |
| | 38)NOTE: PLEASE PROVIDE OCP LOCATED AT |
| | GENERATOR. |
| | THIS INFORMATION COULD NOT BE FOUND ON |
| | PLANS/OR RISER DIAGRAM. |
| | |
| | 39)NOTE: PLEASE COMPLETE DRAWING |
| | KEYNOTES TO CORRELATE WITH PLANS. |
| | |
| | 40)NOTE: PLEASE VERIFY RISER DIAGRAM |
| | SEC'S AND CONDUITS FOR FIRE PUMP, RISER |
| | APPEARS TO SHOW FEED OVERHEAD? |
| | PLEASE SEE NFPA-20, 70 WHICH REQUIRES |
| | COMPLETE ENCASEMENT OF FEEDS. |
| | |
| | 41)NOTE: PLEASE COMPLETE ALL PANELS, |
| | WITH INFORMATION ON PANELS, SIZE, MLO, |
| | MCB ETC. |
| | PLEASE COMPLETE LOAD CALCULATIONS FOR |
| | REVIEW. |
| | |
| | 42)NOTE: PLEASE PROVIDE WIND LOAD |
| | CALCUALTIONS FOR BLDG REVIEW OF ANY SITE |
| | LIGHTING/ROOF TOP LT POLES. |
| | |
| | ** PLEASE SEE LOCATIONS ON PLANS IN |
| | WHICH MANY OF THE ABOVE ITEMS HAVE BEEN |
| | REDLINED AT LOCATIONS OF COMMENTS. |
| | |
| | ** PLEASE BE AWARE OF ANY COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY HAVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | ** PLEASE SUBMIT COMPLETED PLANS FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| 2005-11-17 00:00:00 | ONE ROLL IN ELECTRIC FOR REVIEW. |
| | |
| | |
| | ************************************** |
| | PLEASE KNOW, PLANS ONLY SUBMITTED FOR |
| | "PLAN REVIEW" BEFORE OCT 1ST, 2005 AND |
| | THE CODE CHANGE TO THE 2004 FBC. |
| | |
| | PLEASE KNOW THE EXSITNG "PROJECT" NUMBER |
| | MAY CHANGE WHEN PLANS ARE SUBMITTED FOR |
| | PERMIT AFTER OCT 1ST. |