2005-11-28 00:00:00*** UNSAT ***
  
 CITY PALMS
 10-STORY CONDO
  
 1)NOTE: PLEASE KNOW, PLANS WERE
 SUBMITTED FOR "PLAN REVIEW" ONLY AND
 WERE NOT SUBMITTED FOR PERMIT BEFORE THE
 CODE CHANGE OF OCT 1ST, 2005 TO THE NEW
 2004 FBC.
 PLEASE SEE THAT ANY CHANGES WILL BE
 NEEDED WHEN SUBMITTING FOR PERMIT.
  
 2)NOTE: PLEASE BE SURE ALL PLANS
 SUBMITTED FOR PERMITTING ARE SIGNED,
 DATED AND SEALED BY THE ENGINEER OF
 RECORD.
 FS 471.025
  
 3)NOTE: PLEASE SEE 110.26 FOR MEANS OF
 EGRESS FROM MAIN ELECTRICAL ROOM.
 PLEASE SEE THIS HAD BEEN GONE OVER IN A
 MEETING PRE-SUBMITTAL OF PLANS AND
 DESIGN FOR DOOR AND STAIR LOCATIONS WERE
 DICUSSED FOR A CHANGE.
 PLEASE KNOW, THAT IT IS THE UNDER
 STANDING OF THIS OFFICE THAT THE DOOR
 WOULD INCREASE TO A 6' OPENING AND ONLY
 ONE MEANS OF EGRESS WOULD BE PROVIDED
 AND STAIRS WOULD BE REMOVED?
 PLEASE VERIFY THIS AND ADJSUT PLANS FOR
 THESE CHANGES.
 THE STAIRS AS A MEANS OF EGRESS INSIDE
 THE MAIN ELECTRICAL ROOM WOULD PROPOSE A
 TRIPPING HAZARD IN A SITUATION OF
 SOMEONE BEING BLINDED OR HAVING TO EXIT
 THE ROOM IN AN EMERGENCY SITUATION.
 PLEASE INCLUDE "NOTES" ON SHEET FOR MAIN
 ELECTRICAL ROOM FOR ALL MIN CLEARNECES
 OER 110.26, PANIC HARDWARE FOR DOORS
 ETC.
 PLEASE ALSO SEE MIN CLEARENCE FOR OTHER
 ELECTRICAL ROOMS SHOWN ON ROOM LAYOUT
 PLAN.
  
 4)NOTE: PLEASE SEE PLANS CALL FOR
 BLUIDING TO BE LOCATED AT 480 HIBISCUS,
 HOWEVER OUR SYSTEMWITH PCN # PROVIDED
 INCIDICATES "430". PLEASE CORRELATE AND
 ADJUST PLANS/APPLICATION. ETC.
  
 5)NOTE: PLEASE BE SURE PLANS ARE
 SPECIFIC TO THE 2002 NEC WHICH IS
 CURRENTLY IN EFFECT.
 PLEASE KNOW: DEPENDING ON WHEN PLANS ARE
 SUBMITTED FOR PERMIT, A CODE CHAMGE TO
 THE 2005 NEC SHOULD BE COMING ABOUT IN
 MID 2006.
  
 6)NOTE: PLEASE SEE 1.01 AND ADDITIONAL
 SHEETS WHICH REFERENCE ABCK TO 3.02 FOR
 ELECTRICLA ROOM LAYOUTS, HOWEVER 3.02
 DOES NOT SHOW ROOM LAYOUTS.
 PLEASE CORRELATE.
  
 7)NOTE: PLEASE PROVIDE COMPLETE
 "PHOTOMETRICS" FOR ALL CORRIDORS,
 STAIRWELLS AND EGRESS AREAS PER 2003
 NFPA-101 7.8 AND 7.9.
 PLEASE SEE A MIN OF 10 FT CANDLES IS NOW
 REQUIRED FOR STAIR TOWERS UNDER NORMAL
 EGRESS CONDITIONS.
  
 8)NOTE: PLEASE BE SURE THERE ARE
 EMERGENCY BATTERY BACK UP TYPE FIXTURES
 LOCATED IN ALL ELECTRICAL ROOMS,
 ELEVATOR EQUIPMENT ROOMS, FIRE PUMP,
 GENERATOR, AND FIRE COMMAND ROOM.
 PLEASE KNOW, SOME OF THESE ARE ALREADY
 SHOWN ON PLANS, HOWEVER SOME AREAS MAY
 BE REDLINED FOR THESE.
 NFPA-101 7.8,7.9, NEC 700.16 ETC.
  
 8)NOTE: PLEASE SEE THAT EGRESS
 CORRIDORS, AND STAIR TOWERS WILL BE
 REQUIRED TO CONTAIN A MIN BATTERY BACK
 UP TYPE OF FIXTURE FOR EMERGENCY EGRESS
 OF 1 FT CANDLE.
 7.9 LS 101
 THE TRIPPING OF A SINGLE SWITCH OR
 BREAKER SHALL NOT LEAVE ANY ONE AREA IN
 TOTAL DARKNESS.
  
 9)NOTE: PLEASE SEE WOMENS AND MENS
 RESTRMS IN COMMON AREAS CONTAINING
 RECEPTS LOCATED IN CLOSE PROXIMITY OF
 LAVATORYS. PLEASE BE SURE TO INDICATE
 GFI PROTECTIONS FOR THESE.
 210.8B1
  
 10)NOTE: PLEASE SEE "CLUB RM" AND ALL
 RECEPTSWITHIN 6' OF SINKS SAHLL BE
 INDICATED AS GFI/GFI PROTECTED.
 210.8B
  
 11)NOTE: PLEASE SEE RETAIL SPACE #14,
 WHICH INDICATES A TRANSFORMER AND PANEL
 AS "FUTURE", HOWEVER PLEASE SEE THERE IS
 AN ADDITIONAL PANEL SHOWN BUT NOT CLEAR
 FOR USE ETC?
 215.5
  
 12)NOTE: PLEASE NOTE ON PLANS THE MIN
 CLEARNECES FOR LT FIXTURES IN PROXIMITY
 OF POOL AND WATER FEATURES WATER'S EDGE.
 PLEASE SEE A MINOF 10' IS REQUIRED FOR
 FIXTURES OVER 30V.
 PLEASE SEE 680.22 FOR A MIN OF 5' FROM
 WATER'S EDGE WITH EXCEPTIONS.
  
 13)NOTE: PLEASE SEE POSSIBLE NOTES FROM
 REVIEWS FROM FIRE, BLDGMECH ETC, WITH
 RESPECT TO THE LOCATION OF GENERATOR
 INTAKE AND EXHAUST. THESE SEEMS TO BE
 LOCATED IMEDIATELY ADJACENT TO THE PUBLE
 RIGHT OF WAY/SIDE WALK.
 PLEASE KNOW, THIS IS ONLY A COMMENT FOR
 ELECTRICAL REVIEW , HOWEVER MAY CHANGE
 ELECTRICAL LAYOUT??
  
 14)NOTE: PLEASE SEE PANELS "HP AND "LP".
 TRANSFORMER LOCATED AT ELEC RM ON 2.17.
 PLEASE SEE MIN CLEARENCES PER 110.26
  
 15)NOTE: PLEASE SEE SHEETS 2.21 WHICH
 STATES 6TH FLR, THEN 2.22GOES TO A
 "TYPICAL PARTIAL FLR" AND THEN PLANS GO
 BACK TO A 9TH FLR DETAIL ON 2.25?
 PLEASE VEIRFY IF THESE ARE FLRS 7,8?
  
 16)NOTE: PLEASE PROVIDE NOTE ON ROOF-TOP
 PLANS WHICH WILL STATE THAT ANY
 LIGHTNING PROTECTION SYSTEMS MUST BE IN
 COMPLIANCE WITH NFPA-780. (OR WORDS TO
 THAT AFFECT).
  
 17)NOTE: PLEASE PROVIDE DISCONNECTS OR A
 "TYPICAL DETAIL" FOR ROOF-TOP CU'S.
 440.11
  
 18)NOTE: PLEASE SEE NO CIRCUITING SHOWN
 FOR SOME "HOUSE AREAS". PLEASE SEE
 REDLINED PLANS ON 2.32, STORAGE RM ETC.
  
 19)NOTE: PLEASE SEE 680.23 AND 680.24
 WHICH REQUIRES "NO OTHER" LIGHTING OR
 RECEPTS ON ELEVATOR MACHINE RMS CIRUITS
 OR ELEV PITS. PLEASE SEE 2.34,2.35 AND
 ANY OTHER ARES WHICH MAY BE FED FROM ANY
 OF THESE CIRCUITS.
  
 20)NOTE: PLEASE SHOW CIRCUITING FOR ALL
 UNITS AND CORRELATE WITH THE PANEL
 SCHEDULES SUBMITTED.
 PLEASE KNOW, CODE COMPLIANCE FOR SOME
 ITEMS CAN NOT BE REVIEWED AT THIS TIME.
 215.5
  
 21)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU'S AND HEAT.
 PLEASE SEE MANY PANEL SCHEDULES INDICATE
 LOADS AT 11KW ETC @65%?? PLEASE CLARIFY
 AS 11KW IS SHOWN AS THE DERATED LOAD.
 PLEASE SEE IF 11KW IS THE DE-RATED LOAD,
 THEN ACTUAL KW RATING FOR AHU WOULD BE
 ALMOST 15KW??
  
 22)NOTE: PLEASE SEE WATER HEATERS SHOW
 #8 AWG? PLEASE KNOW THIS IS ONLY A
 COMMENT AS #8 IS OK, HOWEVER MAY NOT BE
 REQUIRED.
 PLEASE SEE THE FOLLOWING COMMENT**
  
 23)NOTE: PLEASE VERIFYOCP SHOWN FOR
 SOME WATER HEATERS AS 2POLE 30A AND SOME
 AS 2-POLE 40A??
 PLEASE SEE 4.5KW IS THE SAME LOAD FOR
 BOTH AT 208V.
 PLEASE KNOW, THE CODE REQUIRES A MIN OCP
 AT 125% (422.13) , HOWEVER THE CODE ALSO
 LIMITS THE OCP AT 150%. 422.11.
 PLEASE ADJUST OCP AND ANY AWG.
  
 24)NOTE: PLEASE SEE PANEL SCHEDULE NOTES
 LISTEDON EACH SHEET, HOWEVER THE NOTES
 ARE NOT LABLED TO PANELS.
 215.5
  
 25)NOTE: PLEASE SEE MEDIA BOXES/PANELS
 ARE SHOWN IN CLOSETS ABOVE STORAGE
 SHELVES.
 PLEASE KNOW, ANY RECEPT REQUIRED FOR ANY
 TYPE OF PLUG-IN TRANSFORMER MAYNOT BE
 AT THIS LOCATION ABOVE OR IN CLOSE
 PROXIMITY TO ANY COMBUSTIBLES.
 110.26,240.24
 * NOTE:, ANY RECEPTS FOR ANY PLUG-IN
 TYPE OF TRANSFORMERS, MAY BE LOCATED
 ABOVE DOOR WAY.*
  
 26)NOTE: PLEASE SEE NOTE #8, ON PANEL
 SCHEDULE NOTES. PLEASE SEE 310.15B6,
 WHICH DOES NOTES INLCUDE 120/208V
 SYSTEMS.THIS IS FOR INFORMATION ONLY.
  
 27)NOTE: PLEASE VERIFY PLANS INDICATE
 BOTH A WASHER AND A DRYER, HOWEVER PLANS
 SEEM TO INDICATE LOCATION FOR STACKABLE
 UNITS ONLY.?
 WILL ELECTRICAL BE INSTALLED FOR BOTH?
  
 28)NOTE: PLEASE SEE UNIT A-6 AS IT SEEMS
 WASHER/DRYER IS LOCATED ON KITCHEN
 COUNTERSPACE?
  
 29)NOTE: PLEASE SEE UNIT A-8 FOR MISSING
 RECEPT PER 210.52.
 PLEASE BE SURE TO CHECK REDLINED PLANS
 FOR ANY OTHER POSSIBLE LOCATIONS WHICH
 MAY REQUIRE A RECEPT.
  
 30)NOTE: PLEASE PROVIDE NOTES FOR
 PLACEMENT OF ALL SD'S PER 2002 NFPA-72
 11.8.3
  
 31)NOTE: PLEASE SEE MANY UNITS DO NOT
 INDICATE THE LV MEDIA BOXES AS SHOWN IN
 OTHER UNITS? PLEASE SEE UNITS, B1,
 B1B,B1F, B1E ETC.
 PLEASE VERIFY
  
 32)NOTE: PLEASE SEE UNIT B1F, WHICH
 SEEMS TO INDICATE THE AN ENTIRE RECEPT
 AS BEING SWITCHED? PLEASE KNOW, THE CODE
 PERMITS A 1/2 SW RECEPT IF USING THE
 RECEPT FOR 210.70, 210.52 OR PLEASE ADD
 RECEPT TO MEET 210.52.
 SEE REDLINED PLANS.
  
 33)NOTE: PLEASE SEE MSBH ON 5.01 SHOWS
 AS 2000A'S , YET 6.01 SHOWS 1200A WITH
 1000A MCB.
 PLEASE CORRELATE:
  
 34)NOTE: PLEASE SEE COMPLETE RISER
 DIAGRAM WITH LABELING OF FEEDERS FOR
 FEEDER SCHEDULE AND CORRELATING ALL
 NUMERCICAL IDENTIFICATION.
  
 35)NOTE: PLEASE PROVIDE THE FOLLOWING
 FOR COMPLETETION OF GROUNDIOG ELECTRODE
 SYSTEM.
 PLEASE PROVIDE DETAIL FOR MAIN GROUNDING
 ELECTRODE SYSTEM TO ALSO INCLUDE THE
 REQUIRED FOOTER STEEL.250.50
  
 PLEASE PROVIDE A GROUND RISER FOR
 CONNECTION OF ALL OTHER SEPARATELY
 DERIVED SYSTEMS/TRANSFORMER ATTACHMENTS
 TO THE MAIN GROUNDIGN ELECTRODE SYSTEM.
 250.30
 PLEASE PROVIDE THIS ON THE RISER DIAGRAM
 SHEET.
  
 36)NOTE:PLEASE SUBMIT ALL INFORMATION
 FOR FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE ALSO PROVIDE MANUFACTURES
 SPECS/CUT SHEETS FOR ABOVE.
  
 37)NOTE: PLEASE SUBMIT ALL INFORMATION
 FOR GENERATOR/ ATS. PLEASE SUBMIT THE
 SPECS/CUT FROM MANUFACTURE.
 PLEASE VERIFY OF THE ATS WILL BE A
 4-POLE SWITCH.
 PLEASE SEE 700.7D AND IF YOU HAVE THE
 HANDBOOK, SEE EXPLANATION OF ARTICLE.
 I HAVE ATTACHED BOTH, JUST IN CASE.
  
 (D) GROUND FAULT. TO INDICATE A GROUND
 FAULT IN SOLIDLY GROUNDED WYE
 EMERGENCY SYSTEMS OF MORE THAN 150 VOLTS
 TO GROUND AND CIRCUIT-PROTECTIVE
 DEVICES RATED 1000 AMPERES OR MORE. THE
 SENSOR FOR THE GROUND-FAULT SIGNAL
 DEVICES SHALL BE LOCATED AT, OR AHEAD
 OF, THE MAIN SYSTEM DISCONNECTING
 MEANS FOR THE EMERGENCY SOURCE, AND THE
 MAXIMUM SETTING OF THE SIGNAL
 DEVICES SHALL BE FOR A GROUND-FAULT
 CURRENT OF 1200 AMPERES. INSTRUCTIONS
 ON THE COURSE OF ACTION TO BE TAKEN IN
 EVENT OF INDICATED GROUND FAULT
 SHALL BE LOCATED AT OR NEAR THE SENSOR
 LOCATION.
  
 ALTHOUGH 700.26 INDICATES THAT
 GROUND-FAULT PROTECTION OF EQUIPMENT IS
 NOT
 REQUIRED ON THE ALTERNATE SOURCE FOR
 EMERGENCY SYSTEMS, GROUND FAULTS CAN
 OCCUR ON SUCH SYSTEMS, AND THEY CAN
 RESULT IN EQUIPMENT BURNDOWN. BECAUSE
 OF THE EMERGENCY NATURE OF SUCH SYSTEMS,
 AUTOMATIC DISCONNECT IN THE EVENT
 OF A GROUND FAULT IS INAPPROPRIATE.
 DETECTION OF SUCH A FAULT, HOWEVER, IS
 DESIRABLE SO THAT THE CONDITION CAN BE
 CORRECTED.
 IN MY READING AND THE INFORMATION FROM A
 COUPLE OF MANUFACTURES OF ATS SWITCHES,
 A 4-POLE ATS IS REQUIRED. PLEASE RESERCH
 THE INFORMATION AND ADJUST.
  
 38)NOTE: PLEASE PROVIDE OCP LOCATED AT
 GENERATOR.
 THIS INFORMATION COULD NOT BE FOUND ON
 PLANS/OR RISER DIAGRAM.
  
 39)NOTE: PLEASE COMPLETE DRAWING
 KEYNOTES TO CORRELATE WITH PLANS.
  
 40)NOTE: PLEASE VERIFY RISER DIAGRAM
 SEC'S AND CONDUITS FOR FIRE PUMP, RISER
 APPEARS TO SHOW FEED OVERHEAD?
 PLEASE SEE NFPA-20, 70 WHICH REQUIRES
 COMPLETE ENCASEMENT OF FEEDS.
  
 41)NOTE: PLEASE COMPLETE ALL PANELS,
 WITH INFORMATION ON PANELS, SIZE, MLO,
 MCB ETC.
 PLEASE COMPLETE LOAD CALCULATIONS FOR
 REVIEW.
  
 42)NOTE: PLEASE PROVIDE WIND LOAD
 CALCUALTIONS FOR BLDG REVIEW OF ANY SITE
 LIGHTING/ROOF TOP LT POLES.
  
 ** PLEASE SEE LOCATIONS ON PLANS IN
 WHICH MANY OF THE ABOVE ITEMS HAVE BEEN
 REDLINED AT LOCATIONS OF COMMENTS.
  
 ** PLEASE BE AWARE OF ANY COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT COMPLETED PLANS FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
2005-11-17 00:00:00ONE ROLL IN ELECTRIC FOR REVIEW.
  
  
 **************************************
 PLEASE KNOW, PLANS ONLY SUBMITTED FOR
 "PLAN REVIEW" BEFORE OCT 1ST, 2005 AND
 THE CODE CHANGE TO THE 2004 FBC.
  
 PLEASE KNOW THE EXSITNG "PROJECT" NUMBER
 MAY CHANGE WHEN PLANS ARE SUBMITTED FOR
 PERMIT AFTER OCT 1ST.