Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop B
Sequence Number 1
Notes
Date Text
2006-01-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05091265
 ADD: 430 HIBISCUS
 CONT:PROJECT
 TEL: (561)586-2913
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECT: COHEN, FREEDMAN, ENCINOSA
 & ASSOC. STUART COHEN/ GULLERMO ENCINOSA
 8085 N. W. 155 ST
 MIAMI, FL
 T(305)826-4155
  
 STRUCTURAL: DE LOS REYESENGINEERING, INC
 8726 S. W. 26 TH STREET SUITE 1&2
 HECTOR DE LOS REYES
 MIAMI, FL
 T(305)477-8826
  
 1ST REVIEW
 ACTION: DENIED
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 COMMENTS FROM THE FOUNDATION PERMIT WILL
 ALSO APPLY TO THIS PERMIT AS WELL.
  
 1ST REVIEW
 ACTION: DENIED
 FROM FOUNDATION PERMIT:
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 NOTE: 713.13.(2) IF WORK HASN'T STARTED
 WITHIN 90 DAYS OF THE NOC BEING RECORDED
 SUCH NOTICE WILL BE VOID AND NO FURTHER
 IN EFFECT CAUSING IT TO BE RE-RECORDED.
  
 2) THERE SEEMS TO BE A DISCREPANCY
 BETWEEN THE PERMIT APPLICATION AND PLANS
 AS TO THE ADDRESS AS WELL AS THE
 PROPERTY CONTROL NUMBER.
 2A) PERMIT APPLICATION INDICATES 430
 HIBISCUS WHERE AS THE PLANS INDICATE 480
 HIBISCUS.
 2B) THE PCN SUPPLIED ON THE PERMIT
 APPLICATION INDICATES A SINGLE LOT. A0.2
 APPEARS TO TAKE MOST OF THE BLOCK AND
 CROSSING THE ALLEYWAY. PROVIDE A REPLAT
 INDICATING A SINGLE LOT AND NEW PCN.
 2C) BEFORE THE FOUNDATION PLAN IS
 RESUBMITTED CORRALATE ALL PLANS INTO
 THREE COMPLETE SETS AND STAPLED.
 106.1.2 ADDITIONAL DATA. THE BUILDING
 OFFICIAL MAY REQUIRE DETAILS,
 COMPUTATIONS, STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
  
 3A) 104.4.5. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT
 OR ENLARGE A BUILDING HAS BEEN FILED, &
 PENDING ISSURANCE OF SUCH PERMIT, THE
 BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR
 THE FOUNDATION ONLY, UPON WRITTEN RE-
 QUEST OF THE OWNER AND CONTRACTOR. THE
 HOLDER OF SUCH A SPECIAL PERMIT IS PRO-
 CEEDING AT HIS OR HER OWN RISK AND WITH-
 OUT ASSURANCE THAT A PERMIT FOR THE
 REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE RE-
 QUIRED IN ORDER TO MEET THE PROVISIONS
 OF THE TECHNICAL CODE.
 3B) WHEN A FOUNDATION PERMIT IS APPLIED
 FOR IT IS UNDERSTOOD THAT INCLUDES FLOOR
 SLABS REQUIRING MEP PLANS. IF LOOKING
 FOR A PERMIT TO START WORK WITHOUT THE
 REQUIRED MEP SHEETS INDICATE WHAT WORK
 WILL BE COMPLETED UNDER THIS PERMIT.
 THE PERMIT APPLICATION BOX DESCRIPTION
 OF PROJECT SHOULD INCLUDE WHAT TYPE OF
 WORK IS TO BE COMPLETED UNDER THIS
 FOUNDATION PERMIT.
  
 4)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 5) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 6) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CON- TAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 7)106.1.2 ADDITIONAL DATA. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS,
 COMPUTATIONS, STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
 THE STRUCTURAL PLANS START WITH
 SHEET S-1.0 BUT THE STRUCTURAL NOTES
 START WITH NUMBER (4).
 THERE IS NO MENTION OF SOILS
 REQUIREMENTS, SOILS REPORTS,
 DENSEIFICATION, NOR AUGER PILE GRADE
 BEAMS, ETC?S1.1 SOIL NOTE SOIL TO BE
 DENSIFIED TO 8,000 BY VIBROFLOTATION,
 PROVIDE REPORT.
  
 8) SEE SHEET S-1.0 FOR IMPORTANCE
 FACTOR, ASCE 7-98 TABLE 1-1/ TABLE 6-1,
 BUILDINGS AND OTHER STRUCTURES WHERE
 MORE THAN 300 PEOPLE CONGREGATE IN ONE
 AREA WILL REQUIRE THE BUILDING CATEGORY
 BE A III AND THE IMPORTANCE FACTOR OF
 1.15. SEE POOL DECK AND WALKWAYS OF
 11,697 SQ FT / 30= 390 OCCUPANT LOAD.
  
 9) SHEET S1.1 FOOTING# 440140 NOT ON
 FOOTING SCHEDULE.STEEL?
  
 10) SHEET S1.1 FOOTING 200160 NOT ON
 FOOTING SCHEDULE. STEEL? THERE ARE
 NUMEROUS FOOTERS THAT ARE NOT ON THE
 SCHEDULE AND WILL REQUIRE STEEL PLEASE
 PROVIDE INFORMATION.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PERMIT:
 12) 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSLY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT
 HISTORICSURFACE WATER DRAINAGE FLOWS
 SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGNCOMPLYING
 WITH ENGINEERING STANDARDS TO PRESERVE
 THE POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 13) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 14)W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 15) A0.2 BUILDING DATA PLANS INDICATE
 ONLY A TYPE I BUILDING NOT GIVEN IF
 DESIGNED AS A TYPE IA OR IB.TABLE 601
 PROVIDE INFO TABLE 601.
  
 16) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 17) A0.2 BUILDING DATA THE WRONG CODE
 FOR ACCESSIBILITY, 2004 FBC CHAPTER 11
  
 18) A0.2 PARKING CALCULATIONS INDICATE
 (9) HANDICAPPED PARKING SPACES, INDICATE
 COMPLIANCE WITH 11-4.1.2(5)(B)
 IN PARKING STRUCTURES, ONE IN EVERY
 EIGHTACCESSIBLE SPACES, BUT NOT LESS
 THAN ONE, SHALL BE "VAN ACCESSIBLE"
 AND SHALL BE DESIGNED AS REQUIRED BY
 11-4.6.3.THE VERTICAL CLEARANCE AT
 SUCH SPACES SHALL COMPLY WITH 11-4.6.5.
 ALL SUCH SPACES MAY BE GROUPED ON ONE
 LEVEL OF A PARKING STRUCTURE.WHEN SUCH
 SPACES ARE PROVIDED IN A PARKING
 STRUCTURE AND ONLY ONE IN EIGHT MEET
 THE HEIGHT REQUIREMENT OF 11-4.6.5, THEY
 SHALL BE DESIGNATED AS REQUIRED BY
 11-4.6.4.
  
 19) A0.2 PARKING CALCULATION INDICATES
 COMPLIANCE WITH 11-4.1.2 WITH 8 H.C.
 SPACES SEE TABLE 401-500 SPACES REQUIRES
 9 H.C. SPACES, PLEASE CORRECT.
  
 20) LIFE SAFETY PLANS DOES NOT INDICATE
 THE OCCUPANT LOAD PER FLOOR AND HOW THIS
 OCCUPANT LOAD IS DISTRIBUTED THROUGH
 DOORWAYS NOR THROUGH STAIRWAYS TO THE
 EXIT DISCHARGE.PLEASE ILLUSTRATE.
 106.1.2 ADDITIONAL DATA. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS,
 COMPUTATIONS, STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
  
  
 21) A0.4 MEZZANINE LEVEL PROVIE THE
 SQUARE FOOT OF EACH COMMERCIAL TEANANT
 FOR THE FIRST FLOOR LEVEL AS WELL AS THE
  
 MEZZANINE LEVEL. 505.2 AREA LIMITATION.
 THE AGGREGATE AREA OF A MEZZANINE OR
 MEZZANINES WITHIN A ROOM SHALL NOT
 EXCEED ONE-THIRD OF THE AREA OF THAT
 ROOM OR SPACE IN WHICH THEY ARE LOCATED.
 THE ENCLOSED PORTIONS OF ROOMS SHALL NOT
 BE INCLUDED IN A DETERMINATION OF THE
 SIZE OF THE ROOM IN WHICH THE MEZZANINE
 IS LOCATED. IN DETERMINING THE ALLOWABLE
 MEZZANINE AREA, THE AREA OF THE
 MEZZANINE SHALL NOT BE INCLUDED IN THE
 AREA OF THE ROOM.
  
 22)SHEET A1.0/ A1.1
 A) DOOR# 14 PLEASE SEE NOTE ON PLANS ALL
 COMMON AREA DOORS 45 MIN RATED BUT ON
 THE DOOR SCHEDULE ONLY THE 1 1/2 HR
 RATED DOORS SHOW ON SCHEDULE. THE DOOR
 SCHEDULE WILL NEED TO SHOW ALL DOOR
 RATINGS.
  
 B)DOOR 14 AND 36 BOTH ARE OVERHEAD DOORS
 ON THE REFUSE ROOM. 707.1.13.4 REQUIRES
 THESE OVERHEAD DOOR TO BE 3/4 RATED &
 THERE ENCLOSURE, SHOW COMPLIANCE. THE
 SECOND ISSUE IS THESE UNITS ARE TO BE
 EITHER SELF CLOSING OR AUTOMATICALLY TO
 CLOSE IF SMOKE IS DETECTED.
  
 23) A1.2
 A)DOORWAY# 7 HALLWAY DOOR TO OFFICE# 004
 IS MISSING THE 18" CLEARENCE ON THE PULL
 SIDE OF LATCHING DEVISE.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 B) PROVIDE INFORMATION ON THE H.C. LIFT?
 11-4.11.2IF PLATFORM LIFTS (WHEELCHAIR
 LIFTS) AREUSED, THEY SHALL COMPLY WITH
 11-4.2.4, 11-4.5, 11-4.27, AND ASME
 A17.1 SAFETY CODE FOR ELEVATORS AND
 ESCALATORS, SECTION XX, 1990.
  
 C) EXTERIOR STAIRS @ DOOR# 35 MISSING
 THE MAEUVERING CLEARENCES ON THE PULL
 SIDE OF LATCH, 11-4.13.6
  
 D) DOOR # 30 MISSING THE 18" REQUIRED ON
 THE LATCH SIDE OF THE DOOR, PULL SIDE.
 11-4.13.6.
  
 E) THE ELECTRICAL PLAN AND ARCHITECTURAL
 FOR THIS PORTION OF THE BUILDING DOESN'T
  
 MATCH DOOR LOCATIONS SOME ARE MISSING OR
 PLACED IN VARIOUS AREAS DEPENDING ON THE
 PLAN THE SAME ISSUE WITH STAIRS.
 106.1.2 ADDITIONAL DATA. THE BUILDING
 OFFICIAL MAY REQUIRE DETAILS,
 COMPUTATIONS, STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
  
 F) ROOM 024 IS LABELED THE EMERGENCY
 ROOM, ELECTRICAL PLANS INDICATE LARGE
 WALL VENTS WHEREAS THE BUILDING A SOLID
 WALL, CORRECT.
  
 24) A1.3: ELEVATOR# 3 PROVIDE A CROSS
 SECTION OF WALL ACROSS FROM ELEVATOR, IS
 THIS WALL A GLASS WALL OR IS IT ONLY A
 HANDRAIL? THE PLANS APPEAR TO BE A TRUE
 MEZZANINE WHICH WILL NOT REQUIRE ATRIUM
 REQUIREMENTS. SEE ATRIUM REQUIREMENTS IF
 APPLICABLE, SEE 404.5.
  
 25) A.14: ROOM 040 PROVIDE THE OCCUPANCY
 CLASSIFICATION ON PLAN S-1 MODERATE
 HAZARD.PROVIDE WALL AND DOOR RATINGS,
 OPEMNING PROTECTIVES. TABLE 705.4,
 TABLE 715.3. ROOM 040 IS NOT AN
 ANCILLARY TO THE PARKING GARAGE.
  
 26)A1.5: ELEVATOR# 1&2/ MEZZANINE LEVEL.
 SAME SITUATION AS QUESTION# 23.
  
 27) A1.6/ A1.8 THIS SITUATION DEALS WITH
 THE 2ND FLOOR THROUGH TO & INCLUDING THE
 TOP FLOOR.
 A) ELEVATORS 1/2 & 3/4 TO COMPLY WITH:
 707.14.1 ELEVATOR LOBBY.
 ELEVATORS OPENING INTO A
 FIRE-RESISTANCE-RATED CORRIDOR AS
 REQUIRED BY SECTION 1016.1 (R2> 10 OCC
 LOAD REQUIRES 1HR RATED CORRIDORS)
 SHALL BE PROVIDED WITH AN ELEVATOR LOBBY
 AT EACH FLOOR CONTAINING SUCH A
 CORRIDOR. THE LOBBY SHALL SEPARATE THE
 ELEVATORS FROM THE CORRIDOR BY FIRE
 PARTITIONS AND THE REQUIRED OPENING
 PROTECTION. ELEVATOR LOBBIES SHALL HAVE
 AT LEAST ONE MEANS OF EGRESS COMPLYING
 WITH CHAPTER 10 AND OTHER PROVISIONS
 WITHIN THIS CODE.
  
 B) PLANS INDICATE STORAGE UNITS, WHEN
 YOU GO TO THE 1/4" SCALE PLAN 2.4 THE
 PLANS STILL DO NOT PROVIDE WALL SECTIONS
 AS TO TYPE OF CONSTRUCTION AS FOUND ON
 A2.37. PLANS ARE INCOMPLETE AS TO WALL
 TYPES FOR MOST OF THE FLOORS.CORRECT.
 S1 STORAGE REQUIRES A 3HR WALL AND
 OPENING PROTECTIVES. SEE FIRE BARRIER
 T 715.3
  
 28) A1.21:
 A) THE EAST SIDE OF THE COVERED VARANDA
 & HEALTH CLUB DOES NOT HAVE ANY
 DIMENSION AS TO THE PROPERTY LINE, &
 PLANS DO NOT PROVIDE IF TYPE IA OR IB,
 WHICH WILL MAKE A DIFFERENCE IN
 ALLOWABLE OPENINGS
  
 B) RAMP TO SPA,
 11-4.8.2 SLOPE & RISE. THE LEAST
 POSSIBLE SLOPE SHALL BE USED FOR ANY
 RAMP. THE MAXIMUM SLOPE FOR A RAMP IN
 NEW CONSTRUCTION SHALL BE 1 TO 12. THE
 MAXIMUM RISE FOR RUN SHALL BE 30" (SEE
 FIGURE 16).
 11-4.8.4(3) IF RAMPS CHANGE DIREC-
 TION AT LANDINGS, THE MINIMUM LANDING
 SIZE SHALL BE 60" X 60".
 11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE.
 11.4.8.5. HANDRAILS: IF A RAMP HAS
 A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 C) THE PLANS SHOW THE ELEVATION AT 0'-0"
 WITH NO CHANGE IN GRADE TO THE INTERIOR?
  
 D) PLANS INDICATE USE OF METAL TRUSSES
 ON THE HEALTH CLUB BUT NO MENTION OF
 TYPE OF DECKING ? SEE TABLE 601 FOR 1
 1/2 HR RATING.
  
 E) PLANS INDICATE FLOOR OR ROOF DRAINS
 SEE SECTION A8.7 DETAIL E, THIS DETAIL
 INDICATES SEE SEE MECH DRAWINGS? WHERE?
 THE PLUMBING SHEET 21.9 ALSO INDICATES
 FLOOR DRAINS BUT NO SECTION THROUGH THE
 SLAB INDICATING COMPLIANCE WITH 712.4.1
 THROUGH PENETRATIONS OF HORIZONTAL
 ASSEMBLIES.
 712.4.1.1PENETRATIONS SHALL BE
 INSTALLED AS TESTED IN AN APPROVED FIRE
 RESISTANCE-RATED ASSEMBLY. PROVIDE
 ADDITIONAL INFORMATION.
  
 29) A3.0
 A) THE DOOR SCHEDULE INDICATES (2) TYPES
 OF RATED DOORS #14 & #15. THE DETAILS ON
 THIS PAGE INDICATE FRAMES AND SILLS BUT
 NO MENTION TO DOORS 14 OR 15.
  
 708.6 OPENINGS IN FIRE PARTITIONS SHALL
 BE PROTECTEDIN ACCORDANCE WITH SECTION
 715.. 715.3.3 FIRE DOOR ASEMBLIES SHALL
 ALSO MEET THE REQUIREMENTS FOR A SMOKE
 AND DRAFT CONTROL DOOR ASSEMBLIES TESTED
 IN ACCORDANCE WITH UL 1784 WITH AN
 ARTIFICIAL BOTTOM SEAL INSTALLED ACROSS
 THE FULL WIDTH OF THE BOTTOM OF THE DOOR
 ASSEMBLY.
  
 710.5.2 SMOKE AND DRAFT CONTROL DOORS,
 DOORS IN SMOKE PARTITIONS SHALL BE
 TESTED IN ACCORDANCE WITH UL 1784 WITH
 AN ARTIFICIAL BOTTOM SEAL INSTALLED
 ACROSS THE FULL WIDTH OF THE BOTTOM OF
 THE DOOR ASSEMBLY.
  
 30) A1.31:
 A) PLANS INDICATE USSE OF METAL
 TRUSSES BUT NO MENTION AS TO THE TYPE OF
 DECKING MATERIAL? TABLE 601 1 1/2 HR
 RATING.
  
 B) PLANS INDICATE A STORAGE OCCUPANCY ON
 THE ROOF? WHAT TYPE OF MATERIALS WILL BE
 STORED THERE, S1 VS S2?
  
 31) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 32)W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 33) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR WINDOWS FIXED
 B) EXTERIOR WINDOWS OPERATABLE
 C) MULLIONS
 D) EXTERIOR GLAZED DOORS
 E) EXTERIOR ROLL UP DOORS
 F) LOUVERS
 G) TRUSS ANCHOR ATTACHMENTS
 H) STORM SHUTTERS
 I) EFIS SYSTEMS
 J) EXTERIOR RAILINGS
 K) ROOFING ASSEMBLIES FLAT AND SLOPED
 ALL OF THE ABOVE MENTIONED PRODUCTS
 WILL REQUIRE THE DESIGNER OF RECORD TO
 SIGN OFF THAT THE REPORTS HAVE BEEN
 REVIEWEDAND APROVED BY THEIR OFFICE.
  
 34)A3.2
 A) WHY DOES THE WINDOW TYPES INDICATE
 TOWNHOUSES?
 B) NOTE # 7 INDICATES THAT THE WINDOWS
 AND DOORS ARE GOING TO BE UNDER SEPERATE
 PERMIT. THIS MEANS THIS BUILDING IS
 ACTUALLY DESIGNED AS OPEN AND NOT
 CLOSED! THE WINDOW AND DOORS WILL BE
 REQUIRED TO BE SUBMITTED AND READY FOR
 PERMIT BEFORE THE BUILDING PERMIT WIL BE
 LET.
  
 35) A4.0,A4.1, A4.2 & A4.3
 A) ALL INDICATE WOOD TRIM BRACKETS SEE
 1406.2.2ARCHITECTURAL TRIM THAT
 EXCEEDS 40 FEET (12 192 MM) IN HEIGHT
 ABOVE GRADE PLANE SHALL BE CONSTRUCTED
 OF APPROVED NONCOMBUSTIBLE MATERIALS AND
 SHALL BE SECURED TO THE WALL WITH METAL
 OR OTHER APPROVED NONCOMBUSTIBLE
 BRACKETS.
 NONCOMBUSTIBLE- MATERIALS WHICH PASS THE
 TEST PROCEDURE SET FORTH IN ASTM E 136.
  
 B)NOTE:STANDING SEAM METAL ROOF ON
 METAL TRUSSES FOR AWNING TYPE
 SHADES.PROVIDE ENGINEERING HOW THIS
 SYSTEM IS TO BE BUILT AND IF THIS SYSTEM
 IS TO STAY IN THE OPEN POSITION DURING A
 HIGH WINDEVENT PROVIDE CALCULATIONS.
  
 C) INDICATE ON THE ELEVATIONS, PRESSURE
 ZONES FOR OPENINGS +/- FOR THE INTERIOR
 AND END ZONES (ZONES 4 & 5). ALSO
 PROVIDE THE ROOF PRESSURE ZONES FOR
 ZONES 1,2& 3.
  
 D) ELEVATIONS DO NOT PROVIDE WHERE THE
 PROPERTY LINES ARE LOCATED?
  
 36)A7.4
 A) STAIRWELL# 4 INDICATES THE USE OF A
 MECHANICAL SHAFT BUT NO DESIGNATION AS
 TO WALL TYPE? 2 HR RATED.
  
 B) A7.5 SAME STAIRWELL# 4 INDICATES THE
 MECHANICAL SHAFT INTRUDING INTO THE
 STAIRWELL NOT STOPPING AT THE 2ND FLOOR
 LEVEL.707.4 SHAFT ENCLOSURES SHALL HAVE
 A FIRE-RESISTANCE RATING NOT LESS THAN
 THE FLOOR ASSEMBLY PENETRATED, BUT NEED
 NOT EXCEED 2 HOURS.
  
 37) A7.6/A7.7 ELEVATOR MACHINE ROOMS
 MISING INFORMATION ON VENTS:
 A)3004.2 LOCATION OF VENTS.
 VENTS SHALL BE LOCATED BELOW THE FLOOR
 OR FLOORS AT THE TOP OF THE HOISTWAY,
 AND SHALL OPEN EITHER DIRECTLY TO THE
 OUTER AIR OR THROUGH NONCOMBUSTIBLE
 DUCTS TO THE OUTER AIR. NONCOMBUSTIBLE
 DUCTS SHALL BE PERMITTED TO PASS THROUGH
 THE ELEVATOR MACHINE ROOM PROVIDED THAT
 PORTIONS OF THE DUCTS LOCATED OUTSIDE
 THE HOISTWAY OR MACHINE ROOM ARE
 ENCLOSED BY CONSTRUCTION HAVING NOT LESS
 THAN THE FIRE PROTECTION RATING REQUIRED
 FOR THE HOISTWAY. HOLES IN THE MACHINE
 ROOM FLOORS FOR THE PASSAGE OF ROPES,
 CABLES OR OTHER MOVING ELEVATOR
 EQUIPMENT SHALL BE LIMITED SO AS NOT TO
 PROVIDE GREATER THAN 2 INCHES (51 MM) OF
 CLEARANCE ON ALL SIDES.
  
 B) 3004.3 AREA OF VENTS.
 EXCEPT AS PROVIDED FOR IN SECTION
 3004.3.1 , THE AREA OF THE VENTS SHALL
 NOT BE LESS THAN 3? PERCENT OF THE AREA
 OF THE HOISTWAY NOR LESS THAN 3 SQUARE
 FEET (0.28 M 2 ) FOR EACH ELEVATOR CAR,
 AND NOT LESS THAN 3? PERCENT NOR LESS
 THAN 0.5 SQUARE FOOT (0.047 M 2 ) FOR
 EACH DUMBWAITER CAR IN THE HOISTWAY,
 WHICHEVER IS GREATER. OF THE TOTAL
 REQUIRED VENT AREA, NOT LESS THAN
 ONE-THIRD SHALL BE OF THE PERMANENTLY
 OPEN TYPE UNLESS ALL VENTS ACTIVATE UPON
 DETECTION OF SMOKE FROM ANY OF THE
 ELEVATOR LOBBY SMOKE DETECTORS.
  
 38) A7.8 & A7.9 INDICATE USE OF 6" BLOCK
 FOR 2 HR WALL RATING. A U.L. LISTING OF
 WHAT TYPE OF BLOCK IS NOT PROVIDING THE
 FIRE RESISTANT RATING BASED ON
 EQUIVALENT THICKNESS OF THE MASONARY
 UNIT AND TYPE OF AGGREGATE USED. THIS
 SHALL BE PROVIDED BY THE BLOCK
 MANUFACTURER.
  
 39) A.80 DETAIL# 25 IS A SHAFT WALL
 PARTITION DESIGN UL U-415. THIS DESIGN
 IS MISSING THE REQUIRED C-H STUDS IN THE
 DESIGN. CORRECT.SAME DETAIL SHOWN ON
 LS.0 CORRECT.
  
 40) A8.1 DETAIL"N" IS FOR A ROLL DOWN
 FIRE RATED DOOR WITHIN A RATED WALL.
 PROVIDE THE UL RATING FOR THE WAY THE
 ROLL DOWN ASSEMBLY BOX TAKES THE PLACE
 OF THE RATED WALL?
  
 41) A8.3 DETAIL H APPEARS THIS DETAIL IS
 MISSING THE VERTICAL BARS AT THE BOTTOM
 OF THE DETAIL THAT WILL KEEP THE 4"
 SPHERE FROM PASSING THROUGH. 1012.3
 OPENING LIMITATION.
  
 42) S-1.0 AS STATED UNDER FOUNDATION
 PERMIT NOTES START WITH NOTE# 4 FOR
 CONCRETE.
  
 A) NOTE A REFRENCES ACI 301-99
 STRUCTURAL CONCRETE,1901.2/1901.3
 CORRECT TO ACI 318-02.
  
 B) MISSING WIND DESIGN:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO
 WIND LOADS SHALL BE SHOWN, REGARDLESS OF
 WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL-FORCE-RESISTING SYSTEM OF
 THE BUILDING:
 1.BASIC WIND SPEED (3-SECOND GUST),
 MILES PER HOUR (KM/HR).
 2.WIND IMPORTANCE FACTOR, I W , AND
 BUILDING CLASSIFICATION FROM TABLE
 1604.5 OR TABLE 6-1, ASCE 7 AND BUILDING
 CLASSIFICATION IN TABLE 1-1, ASCE 7.
 3.WIND EXPOSURE, IF MORE THAN ONE
 WIND EXPOSURE IS UTILIZED, THE WIND
 EXPOSURE AND APPLICABLE WIND DIRECTION
 SHALL BE INDICATED.
 4.THE APPLICABLE ENCLOSURE
 CLASSIFICATIONS AND, IF DESIGNING WITH
 ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5.COMPONENTS AND CLADDING. THE
 DESIGN WIND PRESSURES IN TERMS OF PSF
 (KN/M 2 ) TO BE USED FOR THE DESIGN OF
 EXTERIOR COMPONENT AND CLADDING
 MATERIALS NOT SPECIFICALLY DESIGNED BY
 THE REGISTERED DESIGN PROFESSIONAL.
  
 43) S1-3.4- S1-3.6 TRUSS DIAGRAMS
 MISSING THE MAGNITUDE OF LOADS TO BE
 REISTED, UPLIFT, HORIZONTAL AND GRAVITY
 LOADS.
  
 44) S-4.1 SAME COMMENT 9 & 10 FOUNDATION
 SCHEDULE NOT COMPLETE.
  
 45) S-8.1-S-8.3 ELEVATIONS WITH
 PRESSURES ZONES ARE SO SMALL THE NUMBERS
 BECOME SMUGED AND ILLEGIBLE.
  
 46) PROVIDE ENERGY CALCS FOR BUILDING:
 13-400.1 PRESCRIPTIVE REQUIREMENTS.
 WHERE A PRESCRIPTIVE REQUIREMENT
 SPECIFIC TO A METHOD IS MORE STRINGENT
 THAN THE BASIC PRESCRIPTIVE REQUIREMENT,
 THE MORE RESTRICTIVE REQUIREMENT SHALL
 BE MET.
  
 47) PLANS ARE CURRENTLY IN FOR PLAN
 REVIEW, BUT WHEN PLANS ARE SUBMITTED TO
 THE BUILDING DEPARTMENT FOR PERMIT
 APPLICATION:
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715