| 2005-09-27 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- PROVIDE FLORIDA PRODUCT APPROVAL OR |
| | APPLY FOR LOCAL PRODUCT APPROVAL FOR |
| | DURO-LAST PVC ROOF SYSTEM AS REQUIRED BY |
| | RULE 9B-72 OF DCA.AS PER THE BUILDING |
| | OFFICIAL DADE COUNTY NOA ALONE IS NOT |
| | AUTOMATICALLY AN STATE WIDE PRODUCT |
| | APPROVAL. MANUFACTURER MAY APPLY FOR |
| | LOCAL PRODUCT APPROVAL USING THE DADE |
| | COUNTY NOA AND COMPLETING THE LOCAL |
| | PRODUCT APPROVAL FORM DOWNLOADED FROM |
| | WWW.FLORIDABUILDING.ORG. |
| | |
| | 3- ENGINEERING CALCS REFER TO MIAMI-DADE |
| | COUNTY NOA #01-0420.01. PRODUCT APPROVAL |
| | SUBMITTED IS FL4800.13. THESE ARE TWO |
| | DIFFERENT REPORTS. IF ENGINEER STILL |
| | WANTS TO USE THE DADE COUNTY NOA, THEN, |
| | PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL THAT MATCHES THAT REPORT. |
| | OTHERWISE, ENGINEER TO USE THE FLORIDA |
| | PRODUCT APPROVAL FL4800.13 TO MAKE HIS |
| | CALCULATIONS. |
| | |
| | 4- ENGINEERING REPORT FL4800.13 IS |
| | MISSING PAGES. ONLY PAGE 2 OF 5 WAS |
| | SUBMITTED. |
| | |
| | 5- CLEARLY SPECIFY HOW MUCH AREA IS FLAT |
| | ROOF SYSTEM AND HOW MUCH AREA IS METAL |
| | ROOF MANSARD. |
| | |
| | 6- ENGINEER TO PROVIDE ALL HIS |
| | INFORMATION INCLUDING NAME OF ENGINEER |
| | AND LICENSE NUMBER AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTES AND |
| | 61G15-23.002 FLORIDA ADMINISTRATIVE CODE |
| | |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712. |