Plan Review Notes
Plan Review Notes For Permit 05091244
Permit Number 05091244
Review Stop E
Sequence Number 2
Notes
Date Text
2005-11-10 00:00:00******** UNSAT ********
  
 1)NOTE: PLEASE SEE PLANS ARE NOW COMING
 BACK SHOWING PANEL "HA AND LA" AS
 EXISTING. THIS OK, HOWEVER PLEASE SHOW
 ALL CIRCUITING ON PLANS AND CORRELATE
 WITH PANEL SCHEDULES AS PREVIOUSLY
 REQUESTED.
 *** PLEASE KNOW ***
 ALL ELECTRICAL ON PLANS ARE NOW SHOWN
 CIRCUITED TO THE HIGH VOLTAGE PANEL
 "HA". THIS IS NOT POSSIBLE AS , RECEPTS
 AND OTHER MISC LOADS ARE PROBABLY NOT
 277/480V.
 PLEASE VERIFY TRACK LIGHTING AND ALL
 ELECTRICAL. PLEASE ADJUST CIRCUITING AND
 SUBMIT LA PANEL SCHEDULE FOR 120/208 OR
 240V LOADS.
  
 2)NOTE: PLEASE SEE PANEL "HA" IS SHOWN
 AS 150A'S AND 225A'S.
 PLEASE SEE RISER SHOWS 150A'S
 PLEASE CORRELATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  