| 2005-11-10 00:00:00 | ******** UNSAT ******** | | | | | | 1)NOTE: PLEASE SEE PLANS ARE NOW COMING | | | BACK SHOWING PANEL "HA AND LA" AS | | | EXISTING. THIS OK, HOWEVER PLEASE SHOW | | | ALL CIRCUITING ON PLANS AND CORRELATE | | | WITH PANEL SCHEDULES AS PREVIOUSLY | | | REQUESTED. | | | *** PLEASE KNOW *** | | | ALL ELECTRICAL ON PLANS ARE NOW SHOWN | | | CIRCUITED TO THE HIGH VOLTAGE PANEL | | | "HA". THIS IS NOT POSSIBLE AS , RECEPTS | | | AND OTHER MISC LOADS ARE PROBABLY NOT | | | 277/480V. | | | PLEASE VERIFY TRACK LIGHTING AND ALL | | | ELECTRICAL. PLEASE ADJUST CIRCUITING AND | | | SUBMIT LA PANEL SCHEDULE FOR 120/208 OR | | | 240V LOADS. | | | | | | 2)NOTE: PLEASE SEE PANEL "HA" IS SHOWN | | | AS 150A'S AND 225A'S. | | | PLEASE SEE RISER SHOWS 150A'S | | | PLEASE CORRELATE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|