| Date |
Text |
| 2005-10-03 00:00:00 | ************ UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE PANEL SCHEDULE NOTES |
| | MENTIONS "TWO NEW PANELS", HOWEVER NO |
| | REVISED RISER DIAGRAM WAS SUBMITTED? |
| | PLANS ALSO MENTIONS, EXISTING RISER TO |
| | REMAIN?? |
| | PLEASE CORRELATE. |
| | |
| | 2)NOTE: PLEASE SEE PANEL HA IS SHOWN |
| | BEING 120/208, HOWEVER THIS PANEL ALSO |
| | INDICATES FEEDING A NEW PANEL "A' VIA |
| | TRANSFORMER. PLEASE VERIFY VOLTAGE OF |
| | PANEL "A" . |
| | PLEASE SUBMIT A PANEL SCHEDULE FOR NEW |
| | PANEL "A". |
| | PLEASE BE SURE ALL NEW CIRCUITING SHOWN |
| | ON PLANS, CORRELATES WIHT THE SUBMITTED |
| | PANELSCHEDULES.215.3 |
| | PLEASE BE AWARE AN NEW EELCTRICAL |
| | SERVICE WORK FOR 277/480V SYSTEMS IS |
| | REQUIRED TO BE DONE BY A PE. |
| | FS 471.003H2 |
| | |
| | 3)NOTE: PLEASE SEE 700.12E WHICH |
| | REQUIRES THE BRANCH CIRCUIT FEEDING THE |
| | EM/EXT LTS IS THE SAME CIRCUIT FEEDING |
| | LOCAL LIGHTING. |
| | |
| | 4)NOTE: LOADS FOR TRK LIGHTING TO BE |
| | INDICATED PER 220.12B |
| | |
| | PLEASE KNOW, A COMPLETE REVIEW FOR CODE |
| | COMPLIANCE CAN NOT BE DONE AT THIS TIME. |
| | |
| | PLEASE BE SURE TO REMOVED ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | ONE SET OF THE OLD VOIDED SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW AND IF THERE ARE ANYQUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | PLEASE SUBMIT THE ABOVE |