| Plan Review Notes For Permit 05091241 |
| Permit Number |
05091241 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-01-25 00:00:00 | BUILDING REVIEW 3RD CHECKLIST: | | | 1- DETAIL G: SOFFIT CONNECTION | | | DETAIL ON SHEET 3 OF 5 OF DRAWING 05-417 | | | IS LIMITED TO 84" MAX. PANEL SPAN FOR | | | 57PSF DESIGN PRESSURES. ACCORDION | | | SHUTTERS FOR OPENINGS #1, #2, #5, #9, | | | #10, #15, #17, #18 DON'T WORK. | | | | | | ***NOTE: | | | MAKE SURE SHUTTER SPAN IS MEASURED | | | PROPERLY. | | | | | | 2- INSTALLATION SCHEDULE AND KEY PLAN | | | DON'T MATCH.DIMENSIONS ARE DIFFERENT. | | | DON'T KNOW WHICH ONE HAS THE CORRECT | | | DIMENSIONS. | | | | | | 3- INSTALLATION SCHEDULE IS INCOMPLETE. | | | SOME OPENINGS ARE MISSING THE | | | DIMENSIONS. SOME OPENINGS ARE MISSING | | | THE DESIGN PRESSURES. REVISE AS | | | REQUIRED. USE ATTACHED COPY OF | | | INSTALLATION SCHEDULE THAT WAS REVISED | | | TO FACILITATE PLAN REVIEW, INSPECTIONS | | | AND EVEN INSTALLATION. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|