| 2005-11-22 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- PROVIDE FLORIDA PRODUCT APPROVAL OR |
| | APPLY FOR LOCAL PRODUCT APPROVAL AS |
| | REQUIRED BY RULE 9B-72 OF DCA SINCE OCT. |
| | 1ST 2004. SEE WWW.FLORIDABUILDING.ORG |
| | FOR COMPLETE REQUIREMENTS FOR PRODUCT |
| | APPROVAL. |
| | |
| | 2- PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE ATTACHED SAMPLE. |
| | |
| | 3- ENGINEERED DESIGN WIND LOADS CHART IS |
| | MARKED INCORRECTLY. THIS IS AN EIGHT |
| | STORY BUILDING. THEREFORE MEAN ROOF |
| | HEIGHT CAN'T BE 15'-0". ENGINEER TO |
| | CLEARLY INDICATE DESIGN CRITERIA THAT |
| | APPLIES TO THIS BUILDING. ALSO, REVISE |
| | INFORMATION ON PERMIT PLOT PLAN SHEET. |
| | REVISE MEAN ROOF HEIGHT AND BUILDING |
| | DIMENSIONS TO MATCH ACTUAL BUILDING. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC |
| | 2001. |
| | |
| | 4- CONTRACTOR TO UPDATE WORKER'S |
| | COMPENSATION. |
| | |
| | 5- TABLE 1, STORM PANEL SPAN SCHEDULE ON |
| | SHEET 3 OF 4 OF ENGINERED DRAWINGS: |
| | DESIGN LOAD OF 43PSF DOESN'T MATCH |
| | DESIGN LOAD SPECIFIED ON ENGINEER'S |
| | DESIGN LOAD CHART. REVISE AS REQUIRED. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC |
| | 2001. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |