Plan Review Notes
Plan Review Notes For Permit 05091226
Permit Number 05091226
Review Stop E
Sequence Number 4
Notes
Date Text
2006-08-28 00:00:00 
  
 PROVISO
  
 THIS PERMIT IS BEING ISSUED TO
 FACILITATE THE START OF THIS
 PROJECT.PLEASE MAKE THE FOLLOWING
 CORRECTIONS FOR CODE COMPLIANCE AND
 RESUBMIT FOR REVIEW PRIOR TO ROUGH
 INSPECTION.
  
 THIS CORRECTION WAS ON THE PREVIOUS
 REVIEW.
  
  
 3} THE HEAT PUMP IS LISTED AS 230 WATTS
 ON A SINGLE POLE 60 AMP BREAKER. SEE
 310.16.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  