| Plan Review Notes For Permit 05091226 |
| Permit Number |
05091226 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-08-16 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR | | | THE DESIGN MUST PRINT AND SIGN THEIR | | | NAME TO SAME PER 106.3.4.2. | | | | | | 2} THE MANUFACTUREERS SPECIFICATIONS | | | THAT WERE REQUESTED ON THE PREVIOUS | | | REVIEW HAVE NOT BEEN SUBMITTED. | | | | | | 3} THE HEAT PUMP IS LISTED AS 230 WATTS | | | ON A SINGLE POLE 60 AMP BREAKER. SEE | | | 310.16. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | |
|