Plan Review Notes
Plan Review Notes For Permit 05091189
Permit Number 05091189
Review Stop E
Sequence Number 1
Notes
Date Text
2005-10-06 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SEE THAT A DISCONNECTING MEANS
 IS REQUIRED AT THE SEPERATE STRUCTURE ON
 THE EXTERIOR WHERE THE UNGROUNDED
 CONDUCTORS ENTER THE BUILDING PER
 225.31.
  
 2} THE ABOVE DESCRIBED DISCONNECTING
 MEANS MUST BE GROUNDED PER 250.32.
 PLEASE DRAW SAME ON RISER, INDICATE GEC
 SIZE.
  
 3} THE BRANCH CIRCUIT FOR THE BATHROOM
 MUST COMLY WITH 210.11(C)(3). PLEASE
 INDICATE SAME ON THE SCHEDULE AND WITH
 THE CIRCUIT NUMBER ON THE DRAWING.
  
 NOTE: AN ELECTRICAL PERMIT IS REQUIRED
 FOR THIS WORK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW