| Plan Review Notes For Permit 05091189 |
| Permit Number |
05091189 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-10-06 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SEE THAT A DISCONNECTING MEANS | | | IS REQUIRED AT THE SEPERATE STRUCTURE ON | | | THE EXTERIOR WHERE THE UNGROUNDED | | | CONDUCTORS ENTER THE BUILDING PER | | | 225.31. | | | | | | 2} THE ABOVE DESCRIBED DISCONNECTING | | | MEANS MUST BE GROUNDED PER 250.32. | | | PLEASE DRAW SAME ON RISER, INDICATE GEC | | | SIZE. | | | | | | 3} THE BRANCH CIRCUIT FOR THE BATHROOM | | | MUST COMLY WITH 210.11(C)(3). PLEASE | | | INDICATE SAME ON THE SCHEDULE AND WITH | | | THE CIRCUIT NUMBER ON THE DRAWING. | | | | | | NOTE: AN ELECTRICAL PERMIT IS REQUIRED | | | FOR THIS WORK. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | | | | |
|