| Plan Review Notes For Permit 05091161 |
| Permit Number |
05091161 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-22 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- PROVIDE COMPLETE INSTALLATION | | | SCHEDULE. SEE ATTACHED SAMPLE. | | | | | | 2- DESIGN PRESSURES INDICATED ON THE | | | WIND LOAD CHART TAKEN FROM THE FBC 2001 | | | ARE INCORRECT. THE EFFECTIVE AREA | | | (TRIBUTARY AREA FOR THE ANCHORS) SHALL | | | BE 10PSF NOT 100PSF. REVISE AS REQUIRED. | | | OR PROVIDE COMPLETE ENGINEERING ANALYSIS | | | STATING WHY USING THE 100PSF AS THE | | | EFFECTIVE WIND AREA. SEC. 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001. | | | | | | 3- ANCHOR SCHEDULE IN STORM PANELS | | | ENGINEERED DRAWINGS: A) REVISE MARKED | | | ANCHOR TYPE AND SPACING TO BE USED | | | ACCORDING TO THE REVISED DESIGN | | | PRESSURES REQUESTED ON ITEM #2 ABOVE. | | | B) CIRCLE ONLY THE ANCHOR TYPE AND | | | SPACING THAT APPLY TO THIS JOB. | | | | | | 4- CONTRACTOR TO UPDATE LICENSE WITH THE | | | FRONT COUNTER PERMIT SPECIALISTS. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|