| Notes |
| Date |
Text |
| 2005-10-06 00:00:00 | *** PROVISO *** | | | 1) RETURN AIR TRANSFER DUCTS NEED TO BE | | | 1 1/2 TIMES LARGER THAN SUPPLY AIR | | | DUCTS, PER 2001 FBC/M 601.4 . PLECSE | | | MAKE RETURN DUCTS 10" . | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|