Plan Review Notes
Plan Review Notes For Permit 05091151
Permit Number 05091151
Review Stop E
Sequence Number 5
Notes
Date Text
2006-07-21 00:00:00**** UNSAT 5TH REVIEW ****
  
  
 1) NOTE: PLEASE SEE LOAD CALCUATIONS ARE
 STILL NOT BEING SUBMITTED.
 THE INFORMATION ON THE UPPER LEFT HAND
 CORNER OF PLANS ARE NOT SUFFICIENT.
 220, 215.5, 106.1.2 FBC ADMIN SECT
  
 2) NOTE: PLEASE SEE NO SPEC/MANUFACTURES
 CUT SHEETS WERE SUBMITTED FOR THE
 GENERATOR AND WP ENCLOSURE.
 FBC 106.1.2 90.7
  
 3) NOTE: PLEASE SEE POSSIBLE BLDG REVIEW
 NOTES AS THE ATTACHMENT OF THE GEN TO
 SLAB WAS NOT SPECIFIED?
  
 4) NOTE: PLEASE SEE THAT THE FOLLOWING
 CODES ARE REFLECTED, AT A MIN 2002
 NFPA-70,
  
 ** IMPORTANT**
  
 PLEASE SEE ZONING NOTE AS SCREENING
 WALLS ARE REQUIRED PER ZONING CODE.
 PLEASE KEEP IN MIND THE MIN CLEARENCES
 REQUIRED BY THE MANUFACTURE. PLEASE SEE
 THAT THE SPECS SHOULD INDICATE THE MIN
 CLEARENCES. LTRS OBTAINED BY THIS OFFICE
 FROM SOME MANUFACTURES REQUIRE A MIN OF
 3FT FOR LIQUID COOLED UNITS.
 THE BRAND IS NOT KNOWN AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  