| 2006-07-21 00:00:00 | **** UNSAT 5TH REVIEW **** |
| | |
| | |
| | 1) NOTE: PLEASE SEE LOAD CALCUATIONS ARE |
| | STILL NOT BEING SUBMITTED. |
| | THE INFORMATION ON THE UPPER LEFT HAND |
| | CORNER OF PLANS ARE NOT SUFFICIENT. |
| | 220, 215.5, 106.1.2 FBC ADMIN SECT |
| | |
| | 2) NOTE: PLEASE SEE NO SPEC/MANUFACTURES |
| | CUT SHEETS WERE SUBMITTED FOR THE |
| | GENERATOR AND WP ENCLOSURE. |
| | FBC 106.1.2 90.7 |
| | |
| | 3) NOTE: PLEASE SEE POSSIBLE BLDG REVIEW |
| | NOTES AS THE ATTACHMENT OF THE GEN TO |
| | SLAB WAS NOT SPECIFIED? |
| | |
| | 4) NOTE: PLEASE SEE THAT THE FOLLOWING |
| | CODES ARE REFLECTED, AT A MIN 2002 |
| | NFPA-70, |
| | |
| | ** IMPORTANT** |
| | |
| | PLEASE SEE ZONING NOTE AS SCREENING |
| | WALLS ARE REQUIRED PER ZONING CODE. |
| | PLEASE KEEP IN MIND THE MIN CLEARENCES |
| | REQUIRED BY THE MANUFACTURE. PLEASE SEE |
| | THAT THE SPECS SHOULD INDICATE THE MIN |
| | CLEARENCES. LTRS OBTAINED BY THIS OFFICE |
| | FROM SOME MANUFACTURES REQUIRE A MIN OF |
| | 3FT FOR LIQUID COOLED UNITS. |
| | THE BRAND IS NOT KNOWN AT THIS TIME. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |