2006-01-20 00:00:00********* UNSAT 2ND REVIEW **********
  
 PLEASE SEE NOTES FROM FIRST REVIEW WHICH
 STILL NEED TO BE ADDRESSED.
  
  
 1)NOTE: NOTE #1 NO, PLEASE SUBMIT PLANS
 DESIGNED,
 SIGNED DATED AND SEALED BY AN ENGINEER
 LICENSED UNDER THE STATE OF FLORIDA.
 471.003(H).
  
 2)NOTE: NOTE #2 OK, HOWEVER MUST SUBMIT
 TWO COPIES OF ALL.
 PLEASE SEE SPECS FOR FUEL TANK SHALL BE
 SUBMITTED TO VERIFY LISTING. PLEASE
 KNOW, IT WILL ALSO BE REQUIRED UNDER THE
 SEPARATE PERMIT AS NOTED BY OTHERS.
  
 3)NOTE: NOTE #3 RISER SUBMITTED, HOWEVER
 PLEASE SEE NOTE #1 AND PLEASE ALSO SEE
 MAINS WILL BE REQUIRED AT THE BLDG
 GROUPED IN CLOSE PROXIMITY OF EXISTING
 MAINS AND SHALL BE LABELD AS REQUIRED IN
 702.8, 230.2 ETC.
 PLEASE KNOW, THE BRKRS LOCATED INSIDE
 THE GENERATOR WILL NOT BE ACCEPTED AS
 THE MEANS OF DISCONNECT FOR THESE
 FEEDERS COMING UP INTO BLDG.
 225.31-225.39
  
 4)NOTE: NOTE #4 NO, THIS WAS NOT DONE.
 PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR COMMERCIAL OCCUPANCY,
 PLEASE INCLUDE ALL CONTINUOUS LOADS AT
 125%.
 A/C LOADS ALREADY SHOWN.
 220.3,220.10,220.11,220.13,215.3,230.42
 ETC
  
 5)NOTE: NOTE #5 OK, NOT AN ELECTRICAL
 COMMENT. PLEASE SEE BLDG REVIEW COMMENTS
 FOR TIE DOWN AND SLAB DETAIL.
  
 6)NOTE: NOTE #6 OK. MIANS INDICATED
 OUTSIDE.
  
 7)NOTE:NOTE #7 OK, CORRECTED TO PVC.
  
  
 8)NOTE: PLEASE SEE THE BELOW COMMENT FOR
 SURVEY WAS NOTED ON PREVIOUS REVIEW ,
 HOWEVER THIS WAS NOT ADDRESSED.
 ***************************************
 PLEASE BE SURE TO PROVIDE A 2ND COPY OF
 SURVEY WHICH IS NOT "PENCILED".
 ***************************************
  
 NEW NOTES.
  
 1)NOTE: PLEASE SEE MAINS FOR THESE TWO
 PANELS ARE NOTED AS BEING LOCATED IN
 EXISTING 600A METER BANK, HOWEVER THE
 OCP IS NOT INDICATED.
  
 2)NOTE: PLEASE PROVIDE A COPY OF THE
 SIGNED WRITTEN PROPOSAL FOR PROPOSED
 WORK. PLEASE KNOW, VALUE SHALL INCLUDE
 ALL LABOR AND MATERIALS EVEN IF ANY
 EQUIPMENT IS OWNER SUPLIED. THIS WOULD
 INCLUDE GEN/ ATS ETC.
 PLEASE SEE MATERIALS LIST HAS VALUE
 CROSSED OUT FOR EQUIPMENT?
 FBC ADMINISTRATIVE SECTION104.6.5
  
 3)NOTE: PLEASESEE THE NOC SUBMITTED HAS
 SINCE EXPIRED AND WILL NEED TO BE
 RE-RECORDED.
 PLEASE SEE FS 713.13(2), IF WORK HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING
 NOC, SUCH NOC SHALL BECOME VOID.
  
 4)NOTE: PLEASE SEE BLDG COMMENTS, ALL
 DETAILS SHALL CONTAIN THE PRINTED NAME
 AND SIGNATURE OF ALL PERSON RESPONESIBLE
 FOR SUCH PLANS/DESIGN.
 FBC ADMIN SECTION, 104.2.1
  
 PLEASE SEE POSSIBLE NOTES FROM OTHER
 REIVEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  