| 2006-01-20 00:00:00 | ********* UNSAT 2ND REVIEW ********** |
| | |
| | PLEASE SEE NOTES FROM FIRST REVIEW WHICH |
| | STILL NEED TO BE ADDRESSED. |
| | |
| | |
| | 1)NOTE: NOTE #1 NO, PLEASE SUBMIT PLANS |
| | DESIGNED, |
| | SIGNED DATED AND SEALED BY AN ENGINEER |
| | LICENSED UNDER THE STATE OF FLORIDA. |
| | 471.003(H). |
| | |
| | 2)NOTE: NOTE #2 OK, HOWEVER MUST SUBMIT |
| | TWO COPIES OF ALL. |
| | PLEASE SEE SPECS FOR FUEL TANK SHALL BE |
| | SUBMITTED TO VERIFY LISTING. PLEASE |
| | KNOW, IT WILL ALSO BE REQUIRED UNDER THE |
| | SEPARATE PERMIT AS NOTED BY OTHERS. |
| | |
| | 3)NOTE: NOTE #3 RISER SUBMITTED, HOWEVER |
| | PLEASE SEE NOTE #1 AND PLEASE ALSO SEE |
| | MAINS WILL BE REQUIRED AT THE BLDG |
| | GROUPED IN CLOSE PROXIMITY OF EXISTING |
| | MAINS AND SHALL BE LABELD AS REQUIRED IN |
| | 702.8, 230.2 ETC. |
| | PLEASE KNOW, THE BRKRS LOCATED INSIDE |
| | THE GENERATOR WILL NOT BE ACCEPTED AS |
| | THE MEANS OF DISCONNECT FOR THESE |
| | FEEDERS COMING UP INTO BLDG. |
| | 225.31-225.39 |
| | |
| | 4)NOTE: NOTE #4 NO, THIS WAS NOT DONE. |
| | PLEASE SUBMIT COMPLETE LOAD |
| | CALCULATIONS FOR COMMERCIAL OCCUPANCY, |
| | PLEASE INCLUDE ALL CONTINUOUS LOADS AT |
| | 125%. |
| | A/C LOADS ALREADY SHOWN. |
| | 220.3,220.10,220.11,220.13,215.3,230.42 |
| | ETC |
| | |
| | 5)NOTE: NOTE #5 OK, NOT AN ELECTRICAL |
| | COMMENT. PLEASE SEE BLDG REVIEW COMMENTS |
| | FOR TIE DOWN AND SLAB DETAIL. |
| | |
| | 6)NOTE: NOTE #6 OK. MIANS INDICATED |
| | OUTSIDE. |
| | |
| | 7)NOTE:NOTE #7 OK, CORRECTED TO PVC. |
| | |
| | |
| | 8)NOTE: PLEASE SEE THE BELOW COMMENT FOR |
| | SURVEY WAS NOTED ON PREVIOUS REVIEW , |
| | HOWEVER THIS WAS NOT ADDRESSED. |
| | *************************************** |
| | PLEASE BE SURE TO PROVIDE A 2ND COPY OF |
| | SURVEY WHICH IS NOT "PENCILED". |
| | *************************************** |
| | |
| | NEW NOTES. |
| | |
| | 1)NOTE: PLEASE SEE MAINS FOR THESE TWO |
| | PANELS ARE NOTED AS BEING LOCATED IN |
| | EXISTING 600A METER BANK, HOWEVER THE |
| | OCP IS NOT INDICATED. |
| | |
| | 2)NOTE: PLEASE PROVIDE A COPY OF THE |
| | SIGNED WRITTEN PROPOSAL FOR PROPOSED |
| | WORK. PLEASE KNOW, VALUE SHALL INCLUDE |
| | ALL LABOR AND MATERIALS EVEN IF ANY |
| | EQUIPMENT IS OWNER SUPLIED. THIS WOULD |
| | INCLUDE GEN/ ATS ETC. |
| | PLEASE SEE MATERIALS LIST HAS VALUE |
| | CROSSED OUT FOR EQUIPMENT? |
| | FBC ADMINISTRATIVE SECTION104.6.5 |
| | |
| | 3)NOTE: PLEASESEE THE NOC SUBMITTED HAS |
| | SINCE EXPIRED AND WILL NEED TO BE |
| | RE-RECORDED. |
| | PLEASE SEE FS 713.13(2), IF WORK HAS NOT |
| | COMMENCED WITHIN 90 DAYS OF RECORDING |
| | NOC, SUCH NOC SHALL BECOME VOID. |
| | |
| | 4)NOTE: PLEASE SEE BLDG COMMENTS, ALL |
| | DETAILS SHALL CONTAIN THE PRINTED NAME |
| | AND SIGNATURE OF ALL PERSON RESPONESIBLE |
| | FOR SUCH PLANS/DESIGN. |
| | FBC ADMIN SECTION, 104.2.1 |
| | |
| | PLEASE SEE POSSIBLE NOTES FROM OTHER |
| | REIVEWERS WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |