| Plan Review Notes For Permit 05091151 |
| Permit Number |
05091151 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-10 00:00:00 | 1. ALL ELECTRICAL INSTALLATIONS TO | | | COMPLY WITH THE NATIONAL ELECTRICAL | | | CODE, NFPA 70. | | | | | | 2. WHAT DEVICES OR EQUIPMENT IN THE | | | NEW GENERATOR SUPPLYING POWER TO. | | | | | | 3. ARE THERE ANY DOORS, OR WINDOW | | | OPENINGS LOCATED NEAR THE PROPOSED | | | GENERATOR LOCATION. | | | | | | 4. PAPERWORK DISPLAYS AN UNDERGROUND | | | GAS LIBE BUT DOES NOT INDICATE SIZE OR | | | ANY VALVES. | | | | | | 5. DRAWING INDICATES ABOVE GROUND | | | PROPANE TANK BUT THE DRAWINGS INDICATES | | | A BURIED PROPANE TANK. WHICH IS IT. | | | | | | 6. A 10,000 GALLON PROPANE TANK ABOVE | | | GROUND WILL NOT BE ALLOWED TO BE | | | INSTALLED. ALSO NO INFORMATION PROVIDED | | | WITH REGARDS TO SAFETY, SECURITY, OR | | | MECHANICAL PROTECTION PLANNED FOR ANY | | | TYPE OF PROPANE TANK. | | | | | | 7. NO CUT SHEETS PROVIDED FOR GENERATOR. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|