Plan Review Notes
Plan Review Notes For Permit 05091151
Permit Number 05091151
Review Stop E
Sequence Number 1
Notes
Date Text
2005-11-16 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE SUBMIT PLANS DESIGNED,
 SIGNED DATED AND SEALED BY AN ENGINEER
 LICENSED UNDER THE STATE OF FLORIDA.
 471.003(H).
  
 2)NOTE: PLEASE SUBMIT ALL MANUFACTURES
 CUT/SPEC SHEETS FOR GENERATOR, ATS
 SWITCHES, AND PROPANE TANK,(REVIEWED BY
 OTHERS).
 GEN, ATS TO BE REVIEWED BY FIRE ,
 ELECTRICA ETC.
  
 3)NOTE: PLEASE SUBMIT A RISER DIAGRMA ON
 ALL EXISTING AND NEW EELCTRICAL WHICH
 WILL INCLUDE ANY EXISTING MAINS AND
 LOCATIONS.
 PLEASE SEE RISER SHOWS PANELS AS MLO?
 PLEASE CLARIFY WHERE MAINS ARE?
 PLEASE VERIFY GROUPING OF MAINS AND
 DISCONNECTING MEANS REQUIRED FOR
 GENERATOR.
 PLEASE SEE 230.72,230.76.230.79,
 225.31-225.39.
  
 4)NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR COMMERCIAL OCCUPANCY,
 PLEASE INCLUDE ALL CONTINUOUS LOADS AT
 125%.
 A/C LOADS ALREADY SHOWN.
 220.3,220.10,220.11,220.13,215.3,230.42
 ETC
  
 5)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FOR TIE DOWN AND SLAB DETAIL.
  
 6)NOTE: PLEASE SEE 250.6,250.24,
 "EQUIPMENT GROUNDING CONDUCTORS" ARE
 ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 7)NOTE: PLEASE SEE "EMT" IS INDICATED AS
 DIRECT BURIED , PLEASE SEE USES
 PERMITTED, AS EMT MAY NOT BE USED.358.12
  
 ***************************************
 PLEASE BE SURE TO PROVIDE A 2ND COPY OF
 SURVEY WHICH IS NOT "PENCILED".
 ***************************************
  
  
 PLEASE SEE POSSIBLE NOTES FROM OTHER
 REIVEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  