| 2005-11-16 00:00:00 | ******** UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SUBMIT PLANS DESIGNED, |
| | SIGNED DATED AND SEALED BY AN ENGINEER |
| | LICENSED UNDER THE STATE OF FLORIDA. |
| | 471.003(H). |
| | |
| | 2)NOTE: PLEASE SUBMIT ALL MANUFACTURES |
| | CUT/SPEC SHEETS FOR GENERATOR, ATS |
| | SWITCHES, AND PROPANE TANK,(REVIEWED BY |
| | OTHERS). |
| | GEN, ATS TO BE REVIEWED BY FIRE , |
| | ELECTRICA ETC. |
| | |
| | 3)NOTE: PLEASE SUBMIT A RISER DIAGRMA ON |
| | ALL EXISTING AND NEW EELCTRICAL WHICH |
| | WILL INCLUDE ANY EXISTING MAINS AND |
| | LOCATIONS. |
| | PLEASE SEE RISER SHOWS PANELS AS MLO? |
| | PLEASE CLARIFY WHERE MAINS ARE? |
| | PLEASE VERIFY GROUPING OF MAINS AND |
| | DISCONNECTING MEANS REQUIRED FOR |
| | GENERATOR. |
| | PLEASE SEE 230.72,230.76.230.79, |
| | 225.31-225.39. |
| | |
| | 4)NOTE: PLEASE SUBMIT COMPLETE LOAD |
| | CALCULATIONS FOR COMMERCIAL OCCUPANCY, |
| | PLEASE INCLUDE ALL CONTINUOUS LOADS AT |
| | 125%. |
| | A/C LOADS ALREADY SHOWN. |
| | 220.3,220.10,220.11,220.13,215.3,230.42 |
| | ETC |
| | |
| | 5)NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | FOR TIE DOWN AND SLAB DETAIL. |
| | |
| | 6)NOTE: PLEASE SEE 250.6,250.24, |
| | "EQUIPMENT GROUNDING CONDUCTORS" ARE |
| | ONLY INSTALLED AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 7)NOTE: PLEASE SEE "EMT" IS INDICATED AS |
| | DIRECT BURIED , PLEASE SEE USES |
| | PERMITTED, AS EMT MAY NOT BE USED.358.12 |
| | |
| | *************************************** |
| | PLEASE BE SURE TO PROVIDE A 2ND COPY OF |
| | SURVEY WHICH IS NOT "PENCILED". |
| | *************************************** |
| | |
| | |
| | PLEASE SEE POSSIBLE NOTES FROM OTHER |
| | REIVEWERS WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |