Plan Review Notes
Plan Review Notes For Permit 05091091
Permit Number 05091091
Review Stop E
Sequence Number 2
Notes
Date Text
2005-12-01 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW
  
 1} PLEASE GIVE LOAD CALCS FOR THE BRANCH
 CIRCUITS BEING SERVED BY THE GENERATOR.
  
 2} SUBMIT A SITE PLAN SHOWING THE
 LOCATION OF THE SERVICE EQUIPMENT AND
 THE PROPOSED LOCATION OF THE GENERATOR
 AND RELATED EQUIPMENT SO THAT COMPLIANCE
 FOR 225.31 THROUGH 225.37 INCLUSIVE MAY
 BE REVIEWED.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN MUST PRINT AND SIGN THEIR NAME
 TO SAME PER 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 OR WE COULD SET UP A MEETING TO CLARIFY
 THESE ISSUES. YOU MUST ALSO INDICATE THE
 TYPE OF FUEL AS THE PRIME MOVER AS IT
 HAS A BEARING ON THE GENERATOR OUTPUT.
  
 THERE MAY BE OTHER COMMENTS WHEN THESE
 ITEMS ARE SUBMITTED.BE AWARE THAT ALL
 DISCONNECTS MUST BE SERVICE RATED PER
 225.36.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026