2005-09-30 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW
  
 1} TWO COPIIES OF THE MANUFACTURERS
 SPECIFICATIONS FOR THE GENERATOR AND
 TRANSFER SWITCH.
  
 2} SUBMIT A SITE PLAN SHOWING THE
 LOCATION OF THE SERVICE EQUIPMENT AND
 THE PROPOSED LOCATION OF THE GENERATOR
 AND RELATED EQUIPMENT SO THAT COMPLIANCE
 FOR 225.31 THROUGH 225.37 INCLUSIVE MAY
 BE REVIEWED.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN MUST PRINT AND SIGN THEIR NAME
 TO SAME PER 104.2.1 FBC.
  
 4} THE VALUE ON THE PERMIT APPLICATION
 MUST REFLECT THE COST OF ALL LABOR AND
 MATERIAL (EQUIPMENT) FOR THIS PROJECT
 UNDER THE GEN RES PERMIT TYPE. SEE
 104.6.5.CWPB AMMENDMENTS.
  
 THERE MAY BE OTHER COMMENTS WHEN THESE
 ITEMS ARE SUBMITTED.BE AWARE THAT ALL
 DISCONNECTS MUST BE SERVICE RATED PER
 225.36.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026