| Plan Review Notes For Permit 05091091 |
| Permit Number |
05091091 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-30 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW | | | | | | 1} TWO COPIIES OF THE MANUFACTURERS | | | SPECIFICATIONS FOR THE GENERATOR AND | | | TRANSFER SWITCH. | | | | | | 2} SUBMIT A SITE PLAN SHOWING THE | | | LOCATION OF THE SERVICE EQUIPMENT AND | | | THE PROPOSED LOCATION OF THE GENERATOR | | | AND RELATED EQUIPMENT SO THAT COMPLIANCE | | | FOR 225.31 THROUGH 225.37 INCLUSIVE MAY | | | BE REVIEWED. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR | | | THE PLAN MUST PRINT AND SIGN THEIR NAME | | | TO SAME PER 104.2.1 FBC. | | | | | | 4} THE VALUE ON THE PERMIT APPLICATION | | | MUST REFLECT THE COST OF ALL LABOR AND | | | MATERIAL (EQUIPMENT) FOR THIS PROJECT | | | UNDER THE GEN RES PERMIT TYPE. SEE | | | 104.6.5.CWPB AMMENDMENTS. | | | | | | THERE MAY BE OTHER COMMENTS WHEN THESE | | | ITEMS ARE SUBMITTED.BE AWARE THAT ALL | | | DISCONNECTS MUST BE SERVICE RATED PER | | | 225.36. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|