| Plan Review Notes For Permit 05091007 |
| Permit Number |
05091007 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-10-11 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1-A) ENGINEER CALCULATIONS: CLARIFY WHY | | | THE EXTERIOR PARTITION DESIGN LOADS | | | CHART SHOWS INTERNAL PRESSURE OF 0.00. | | | IT'S NOT CLEAR IF THE DESIGN ASSUMPTION | | | IS THAT BUILDING IS ENCLOSED OR | | | PARTIALLY ENCLOSED SINCE NO VALUE WAS | | | ENTERED. ENGINEER TO REVISE/CLARIFY AS | | | REQUIRED. SEC. 104.2.1.2 CITY AMENDMENTS | | | TO FBC 2001. | | | | | | B) ENGINEER TO CLARIFY IF DOOR WILL BE | | | USED AS PART OF THE BUILDING ENVELOPE OR | | | NOT. SEE NOTE REGARDING THE DESIGN | | | PRESSURES ON ITEM #3 OF THIS WIND | | | CALCULATIONS SHEET WHICH SAYS THAT | | | "THESE LOADS ARE NOT INTENDED FOR USE | | | WITH COMPONENTS THAT PROTECT OR CREATE A | | | BUILDING ENVELOPE". | | | | | | 2- CLEARLY SPECIFY ON SHEET 2 OF 4 | | | SPECIFIC DOOR MODULE AND GLASS TYPE TO | | | BE INSTALLED TO VERIFY COMPLIANCE WITH | | | THE DESIGN PRESSURES CALCULATED BY THE | | | ENGINEER. | | | | | | | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712. |
|