| Notes |
| Date |
Text |
| 2005-09-25 00:00:00 | THE TWO SMALL BATHROOMS NEED GFI OUTLETS | | | 210.8A1 | | | | | | MASTER BATH NEEDS ADDITIONAL GFI WITHIN | | | 3' OF THE SINKS BOTH SINKS 210.52D | | | | | | NEED AN OUTLET ON BACK OF HOUSE | | | 210.8A3, 210.52E | | | | | | OUTLET SPACING NOT TO CODE IN MASTER | | | BDROOM AND BDROOM TO THE LEFT | | | 210.52A1,2 | | | | | | OUTLETS IN BDROOMS TO BE ARC FAULT | | | PROTECTED210.12B | | | | | | NEED A PANEL SCHEDULE SHOWING BREAKER | | | SIZES AND WIRE SIZES PER CODE. |
|