| 2006-06-07 00:00:00 | PROVISO:2001 FBC/BUILDING 5/6 UNITS |
| | |
| | PLEASE REVISE PLANS TO REFLECT THE |
| | IMPLEMENTATION OF THE FOLLOWING |
| | PROVISO'S: |
| | |
| | 1.PLAN SHEET M0.1 THE AHU MOUNTING |
| | DETAIL NOTE 15 STATES "NO COMBUSTIBLES |
| | ALLOWED IN THE MECHANICAL CLOSET" AS |
| | THIS SERVES AS A RETURN AIR PLENUM.THE |
| | DOOR SCHEDULE ON PLAN A-4.1.1. INDICATES |
| | A WOOD LOUVERED DOOR.PLEASE VERIFY |
| | WITH THE DOOR MANUFACTURE THAT THIS |
| | MEETS THE REQUIREMENT OF 25 FLAME/50 |
| | SMOKE INDEX AS SPECIFIED IN 2001 FMC |
| | 602.2.1. |
| | |
| | 2.OUTSIDE AIR CALCULATIONS INDICATED |
| | ON M0.1 ARE BASED ON INFILTRATION RATES. |
| | THE INFILTRATION RATES ARE THE "MAXIMUM" |
| | ALLOWED BY CODE & MAY NOT BE A |
| | "TRUE/ACTUAL" RATE.PLEASE PROVIDE |
| | CALCS IN ACCORDANCE WITH 2001 FMC |
| | 402.2., 402.2.1 OR TABLE 403.3.PLEASE |
| | NOTE, PLAN SHEET M2 INDICATES A 6" O.A. |
| | DUCT, IF THIS IS NOT UTILIZED, PLEASE |
| | REMOVE FROM THE PLANS. |
| | |
| | 3.SPECIFIC DRYERS ARE TO BE INSTALLED |
| | BY FINAL INSPECTION. |
| | |
| | 4.RETURN AIR INDICTED ON THE FIRST |
| | FLOOR BETWEEN THE GARAGE AND THE FOYER |
| | DOOR IS NOT REQUIRED PER 2001 FMC 601.4 |
| | EXCEPTION #3, AS THIS IS NOT A HABITABLE |
| | SPACE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |